Overview

The “External tripping of a busbar section (direct)” makes it possible to link an external signal for tripping all bays of one busbar section. The busbar protection evaluates the disconnector image to determine which bays are connected to the affected busbar section.

For more detailed information on “External Tripping Busbar Section (Direct)” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Embedding the External Tripping of a Busbar Section (direct) Function

Embedding the External Tripping of a Busbar Section (direct) Function

Setting Parameters


Setting parameters for External Tripping Busbar Section (Direct)

Addr. Parameter C Setting Options Default Setting
Ext. trip BZ
_:100 Ext. trip BZ:Superv.t. Rel. ext. trip BZ   0.06 s to 1.00 s 0.06 s

Logic Diagrams & highlights


Logic Diagram of the External Tripping of a Busbar Section (Direct)

Logic Diagram of the External Tripping of a Busbar Section (Direct)

Waveform for Supervision (_:11881:315) No Ext. trip release

Waveform for Supervision (_:11881:315) No Ext. trip release

Waveform for Supervision (_:11971:302) BI rel. ext.trip dist.

Waveform for Supervision (_:11971:302) BI rel. ext.trip dist.

Waveform for Supervision (_:11881:314) BI External trip dist.

Waveform for Supervision (_:11881:314) BI External trip dist.