Overview

The “External trip initiation 3-pole” function processes any signals from external protection or supervision devices. It enables the integration of any signals from external protection equipment in the indication and tripping
processing, for example from transient ground-fault relays or Buchholz protection. It also enables direct tripping of the circuit breaker in conjunction with busbar-protection applications and direct tripping of the circuit breaker in the case of circuit-breaker failure at the other line end.

For more detailed information on “External trip initiation 3-pole” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the External trip initiation Function

Setting Parameters


Setting parameters of the Function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:901:1 Stage 1:Mode   off
on
test
on
_:901:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:901:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Logic Diagram for the External Trip-Initiation Stage

Logic Diagram for the External trip initiation Stage