Siemens / End fault protection in busbar protection _ Setting & highlights _ SI5104

Table of Contents

Overview

The “End fault protection” function protects the section between the current transformer and the open circuit breaker. The switch position of the circuit breaker must be available for the effectiveness of the function. The protection range is determined by the installation location of the current transformer.

For more detailed information on “End fault protection in busbar protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for End fault protection in busbar protection

Addr. Parameter C Setting Options Default Setting
50EF 1/3pole
_:1 50EF 1/3pole:Mode   off
on
on
_:101 50EF 1/3pole:Threshold 1 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 2.500 A
_:102 50EF 1/3pole:Threshold 2 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.150 A to 175.000 A 1.250 A
_:4 50EF 1/3pole:Dropout ratio   0.50 to 0.99 0.95
_:110 50EF 1/3pole:Delay CB open   0.00 s to 60.00 s 0.00 s
_:111 50EF 1/3pole:Operate delay   0.00 s to 60.00 s 0.00 s
_:112 50EF 1/3pole:Minimum operate time   0.00 s to 60.00 s 0.10 s

Logic Diagrams & highlights


End-Fault Protection in the Feeder

End-Fault Protection in the Feeder

Protection with Faults in the Bus Coupler (Dead Zone)

Protection with Faults in the Bus Coupler (Dead Zone)

Logic of the End-Fault Protection

Logic of the End-Fault Protection