Overview

The “End fault protection (EFP)” element operates for dead-zone faults; that is, it faults between the CT and an open feeder breaker. Since a bus protection zone terminates on the CTs, faults between the CT and breaker require special consideration.

For more detailed information on “End fault protection (EFP)” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B30, B90 9B86 End of Fault Protection 1 Function 0 to 1 1 F102 0 (Disabled)
" 9B87 End of Fault Protection 1 CT 0 to 23 1 F400 0
" 9B88 End of Fault Protection 1 Pickup 0.02 to 30 pu 0.001 F001 1200
" 9B89 End of Fault Protection 1 Breaker Open 0 to 4294967295 1 F300 0
" 9B8B End of Fault Protection 1 Breaker Delay 0 to 65.535 s 0.001 F001 400
" 9B8C End of Fault Protection 1 Manual Close 0 to 4294967295 1 F300 0
" 9B8E End of Fault Protection 1 Pickup Delay 0 to 65.535 s 0.001 F001 40
" 9B8F End of Fault Protection 1 Block 0 to 4294967295 1 F300 0
" 9B91 End of Fault Protection 1 Target 0 to 2 1 F109 0 (Self-reset)
" 9B92 End of Fault Protection 1 Events 0 to 1 1 F102 0 (Disabled)
" 9B93 …Repeated for EoF Protection 2          
" 9BA0 …Repeated for EoF Protection 3          
" 9BAD …Repeated for EoF Protection 4          
" 9BBA …Repeated for EoF Protection 5          
" 9BC7 …Repeated for EoF Protection 6          
" 9BD4 …Repeated for EoF Protection 7          
" 9BE1 …Repeated for EoF Protection 8          
" 9BEE …Repeated for EoF Protection 9          
" 9BFB …Repeated for EoF Protection 10          
" 9C08 …Repeated for EoF Protection 11          
" 9C15 …Repeated for EoF Protection 12          
" 9C22 …Repeated for EoF Protection 13          
" 9C2F …Repeated for EoF Protection 14          
" 9C3C …Repeated for EoF Protection 15          
" 9C49 …Repeated for EoF Protection 16          
" 9C56 …Repeated for EoF Protection 17          
" 9C63 …Repeated for EoF Protection 18          
" 9C70 …Repeated for EoF Protection 19          
" 9C7D …Repeated for EoF Protection 20          
B90 9C8A …Repeated for EoF Protection 21          
" 9C97 …Repeated for EoF Protection 22          
" 9CA4 …Repeated for EoF Protection 23          
" 9CB1 …Repeated for EoF Protection 24          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F300 0 : Off (This is boolean FALSE value), 1 : On (This is boolean TRUE value)
F400 0: Card 1 Contact 1 to 4, 1: Card 1 Contact 5 to 8, 2: Card 2 Contact 1 to 4, 3: Card 2 Contact 5 to 8, 4: Card 3 Contact 1 to 4, 5: Card 3 Contact 5 to 8

Logics & highlights


Application of end fault protection element

Application of end fault protection element

End fault protection and bypass isolators

End fault protection and bypass isolators

End fault protection logic

End fault protection logic