Siemens / Echo and tripping in the event of weak infeed _ Setting & highlights _ SI5021

Table of Contents

Overview

The “Echo and tripping in the event of weak infeed” is used to support the teleprotection method for distance protection and ground-fault protection. Its use is only advisable, therefore, if you are using an appropriate teleprotection method.

For more detailed information on “Echo and tripping in the event of weak infeed” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Echo and tripping in the event of weak infeed

Function Blocks

Function Blocks

Setting Parameters


Setting parameters for Echo and tripping in the event of weak infeed Function

Addr. Parameter C Setting Options Default Setting
Weak infeed
_:5821:101 Weak infeed:Echo block time after Tx   0.00 s to 60.00 s 0.05 s
_:5821:102 Weak infeed:Echo and operate delay   0.00 s to 60.00 s 0.04 s
_:5821:103 Weak infeed:Echo pulse   0.00 s to 60.00 s 0.05 s
_:5821:104 Weak infeed:Weak infeed action   off
only WI operate
only echo
echo and WI operate
only echo
_:5821:105 Weak infeed:85-21/67N common chan.   no
yes
no
_:5821:106 Weak infeed:Under- voltage threshold   0.300 V to 200.000 V 25.000 V
_:5821:108 Weak infeed:CB closed on I=0   no
yes
no

Logic Diagrams & highlights


Release Logic for the Echo Function with Distance Protection

Release Logic for the Echo Function with Distance Protection

Release Logic for the Echo Function with Ground-Fault Protection

Release Logic for the Echo Function with Ground-Fault Protection

Logic Diagram for the Echo Function

Logic Diagram for the Echo Function

Logic of the 1-Channel Coordinator

Logic of the 1-Channel Coordinator

Detection of Weak Infeed for Phase-to-Ground Voltages (Grounded Systems)

Detection of Weak Infeed for Phase-to-Ground Voltages (Grounded Systems)

Detection of Weak Infeed for Phase-to-Phase Voltages (Isolated or Resonant-Grounded Systems)

Detection of Weak Infeed for Phase-to-Phase Voltages (Isolated or Resonant-Grounded Systems)

Release Logic for Tripping on Weak Infeed

Release Logic for Tripping on Weak Infeed