Overview
Easergy MiCOM P64x series provides fast and complete protection for transformer faults, preserving service life and is designed for two and three winding transformers (including autotransformers).
For more detailed information on “Easergy MiCOM P64x” relays, refer to Schneider protection relays manuals.
To see other supported devices, click here.
This post covers the specific versions of the MiCOM products with:
- Hardware suffix: L (P642) M (P643/P645)
- Software sufix: B6 (P643) & B5 (P642/P643/P645)
Configuration menu
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
CONFIGURATION | 09 | 00 | ||
This column contains CONFIGURATION parameters. | ||||
Restore Defaults | 09 | 01 | No Operation | No operation, All settings, Setting Group 1, Setting Group 2, Setting Group 3, or Setting Group 4 |
Setting to restore a setting group to factory default settings. | ||||
Setting Group | 09 | 02 | Menu | Select from Menu or Select from PSL |
Allows setting group changes to be initiated using 2 DDB signals in the programmable scheme logic or from the Menu settings. | ||||
Active Settings | 09 | 03 | Group 1 | Group 1, Group 2, Group 3 or Group 4 |
Selects the active setting group. | ||||
Save Changes | 09 | 04 | No Operation | No Operation, Save or Abort |
Saves all relay settings. | ||||
Copy From | 09 | 05 | Group 1 | Group 1, Group 2, Group 3 or Group 4 |
Allows displayed settings to be copied from a selected setting group. | ||||
Copy To | 09 | 06 | No Operation | No Operation, Group 1, Group 2, Group 3 or Group 4 |
Allows displayed settings to be copied to a selected setting group. | ||||
Setting Group 1 | 09 | 07 | Enabled | Enabled or Disabled |
Enables or disables Group 1 settings. If the setting group is disabled from the configuration, all associated settings and signals are hidden, with the exception of this setting. | ||||
Setting Group 2 | 09 | 08 | Disabled | Enabled or Disabled |
Setting Group 2 works in the same way as Setting Group 1. | ||||
Setting Group 3 | 09 | 09 | Disbaled | Enabled or Disabled |
Setting Group 3 works in the same way as Setting Group 1. | ||||
Setting Group 4 | 09 | 0A | Disabled | Enabled or Disabled |
Setting Group 4 works in the same way as Setting Group 1. | ||||
Diff Protection | 09 | 0C | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the differential protection. The unit provides bias differential protection with multiple CT inputs. | ||||
REF Protection | 09 | 0E | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Restricted Earth Fault protection. The unit provides a low impedance REF function per transformer winding. | ||||
Over Current | 09 | 10 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the overcurrent protection: ANSI 50/51/67P, 46OC. | ||||
NPS OverCurrent | 09 | 11 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Negative Phase Sequence overcurrent protection: ANSI 50/51/67P, 46OC. | ||||
Thermal Overload | 09 | 12 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Thermal Overload Protection: ANSI 49. | ||||
Earth Fault | 09 | 13 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Earth Fault Protection: ANSI 50N/51N. | ||||
Residual O/V NVD | 09 | 16 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables (activates) or disables (turns off) the Residual Overvoltage (Neutral Voltage Displacement) Protection function: ANSI 59N. |
||||
Overfluxing | 09 | 18 | Disabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Overfluxing protection: ANSI 24. | ||||
Through Fault | 09 | 1B | Disabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Through Fault function. The Through Fault current monitoring function in the P64x gives the fault current level, the duration of the faulty condition, the date and time. | ||||
Volt Protection | 09 | 1D | Disabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Voltage Protection (Under/Overvoltage and NPS Overvoltage) function: ANSI 27/59/47. | ||||
Freq Protection | 09 | 1E | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Frequency Protection (Under/Overfrequency) function: ANSI 81O/U. | ||||
RTD Inputs | 09 | 1F | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the RTD (Resistance Temperature Device) Inputs. | ||||
CB Fail | 09 | 20 | Disabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Circuit Breaker Fail Protection function: ANSI 50BF. | ||||
Supervision | 09 | 21 | Disabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the Supervision (VTS&CTS) functions: ANSI VTS/CTS. | ||||
Input Labels | 09 | 25 | Visible | Invisible or Visible |
Sets the Input Labels menu visible in the relay settings menu. | ||||
Output Labels | 09 | 26 | Visible | Invisible or Visible |
NOT USED. Sets the Output Labels menu to visible in the relay settings menu. |
||||
RTD Lables | 09 | 27 | Visible | Invisible or Visible |
Sets the RTD Labels menu visible in the relay settings menu. | ||||
CT and VT Ratios | 09 | 28 | Visible | Invisible or Visible |
Sets the Current & Voltage Transformer Ratios menu visible in the relay settings menu. | ||||
Record Control | 09 | 29 | Visible | Invisible or Visible |
Sets the Record Control menu visible in the relay settings menu. | ||||
Disturb Recorder | 09 | 2A | Visible | Invisible or Visible |
Sets the Disturbance Recorder menu visible in the relay settings menu. | ||||
Measure’t Setup | 09 | 2B | Visible | Invisible or Visible |
Sets the Measurement Setup menu visible in the relay settings menu. | ||||
Comms Settings | 09 | 2C | Visible | Invisible or Visible |
Sets the Communications Settings menu visible in the relay settings menu. These are the settings associated with the 1st and 2nd rear communications ports. | ||||
Commission Tests | 09 | 2D | Visible | Invisible or Visible |
Sets the Commissioning Tests menu visible in the relay settings menu. | ||||
Setting Values | 09 | 2E | Primary | Primary or Secondary |
This affects all protection settings that are dependent on CT and VT ratios. | ||||
Control Inputs | 09 | 2F | Visible | Invisible or Visible |
Sets the Control Inputs menu visible in the relay setting menu. | ||||
CLIO Inputs | 09 | 30 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the CLIO (Current Loop Input Output) function. | ||||
CLIO Outputs | 09 | 31 | Enabled | Enabled or Disabled |
Enables (activates) or disables (turns off) the CLIO (Current Loop Input Output) Outputs function. | ||||
CLIO status (Hidden) | 09 | 32 | Hidden | False or True |
CLIO status (Hidden). No Courier text. Cell value set to False if CLIO not fitted and Cell value set to True if CLIO is fitted. |
||||
Control I/P Config | 09 | 35 | Visible | Invisible or Visible |
Sets the Control Input Configuration menu visible in the relay setting menu. | ||||
Ctrl I/P Labels | 09 | 36 | Visible | Invisible or Visible |
Sets the Control Input Labels menu visible in the relay setting menu. | ||||
Direct Access | 09 | 39 | Enabled | Enabled, Disabled or Hotkey Only |
Defines what controls are available using the direct access keys – Enabled (Hotkey and CB Control functions) / Hotkey Only (Control Inputs and Setting group selection) / CB Cntrl Only (CB open/close). | ||||
PB CONFIG | 09 | 48 | Visible | Invisible or Visible |
Sets the PB CONFIG menu visible in the relay setting menu. | ||||
IEC GOOSE | 09 | 49 | Visible | Invisible or Visible |
Sets the IEC 61850 GOOSE menu visible in the relay setting menu. | ||||
Function Keys | 09 | 50 | Visible | Invisible or Visible |
Sets the Function Key menu visible in the relay setting menu. | ||||
VIR I/P Labels | 09 | 70 | Invisible | Invisible or Visible |
VIR I/P Labels Visible/Invisible | ||||
VIR O/P Labels | 09 | 80 | Invisible | Invisible or Visible |
VIR O/P Labels Visible/Invisible | ||||
Usr Alarm Labels | 09 | 90 | Invisible | Invisible or Visible |
USR Alarm Labels Visible/Invisible | ||||
RP1 Read Only | 09 | FB | Disabled | Enabled, Disabled |
Visible when comms options are: 1 – Courier 3 – CS103 6 – IEC61850 with 1st Rear Courier, 7 – IEC61850 with 1st Rear CS103. |
||||
RP2 Read Only | 09 | FC | Disabled | Enabled, Disabled |
Visible when comms options are: 1 – Courier, or 3 – CS103; and hardware options are: 7, 8, E or F. |
||||
NIC Read Only | 09 | FD | Disabled | Enabled, Disabled |
Visible when comms options are: 6 – IEC61850 with 1st Rear Courier, 7 – IEC61850 with 1st Rear CS103. | ||||
SettingValueBeh. | 09 | FE | Independent | 0 = Independent or 1 = Locked Mode |
Independent: cell [092E] Setting Values
will be independent in each interface. For example, the Front Port can have
[092E] set to Secondary and a remote port can have [092E] set to
Primary. Locked Mode: cell [092E] Setting Values are locked to the same value for all interfaces. All interfaces have the same value for [092E]. Whichever interface selects Locked Mode will have its setting for [092E] applied to all interfaces. Any interface can then change [092E] and it will apply on all interfaces. |
||||
LCD Contrast | 09 | FF | 11 | 0 to 31 step 1 |
To confirm the LCD contrast press the right and left arrow keys together instead of Enter. This prevents someone selecting a black or blank contrast setting by accident. Note: The contrast can be set through the FP comms port using the MiCOM software. | ||||
System Config
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: SYSTEM CONFIG | 30 | 00 | ||
This column contains GROUP 1 SYSTEM CONFIG parameters | ||||
Winding Config | 30 | 01 | HV+LV+TV | HV+LV or HV+LV+TV |
P643 and P645 only. This setting indicates if the protected transformer is a two or three winding transformer. |
||||
Winding Type | 30 | 02 | Conventional | Conventional or Auto |
The winding type may be configured as Conventional or Auto. This setting is just for information. | ||||
HV CT Terminals | 30 | 03 | 01 (P642) | 01 (P642) |
Each digit corresponds to a terminal. For further detailed connections refer to the installation section. P642 only – from right to left the current inputs are T1, T2. 0 = disabled, 1 = enabled. | ||||
LV CT Terminals | 30 | 04 | 10 (P645) | 10 (P642) |
P642 only. Each digit corresponds to a terminal. From right to left the current inputs are T1, T2. 0 = disabled, 1 = enabled For further detailed connections refer to the installation section. |
||||
TV CT Terminals | 30 | 05 | 010 (P643) | 010 (P643) |
P643 only. Each digit corresponds to a terminal. From right to left the current inputs are T1, T2, T3. 0 = disabled, 1 = enabled For further detailed connections refer to the installation section. |
||||
Sref | 30 | 07 | 100MVA | 0.1MVA to 5000MVA step 0.1MVA |
Reference power. Used by the differential function to calculate the ratio correction factors. Used by the thermal function when the monitored winding is set to biased current. | ||||
HV Connection | 30 | 08 | Y-Wye | Y-Wye, D-Delta or Z-Zigzag |
The HV winding connections can be configured as Wye, Delta, or Zigzag. | ||||
HV Grounding | 30 | 09 | Grounded | Grounded or Ungrounded |
In Simple mode: Grounded = P64x filters zero sequence current on HV side. Ungrounded = no zero sequence filtering is done on HV side. In Advanced mode: Grounding = Information only, and zero sequence filtering depends on Zero seq filt HV setting. |
||||
HV Nominal | 30 | 0A | 220kV | 100V to 1MV step 1V |
Nominal voltage of the HV winding, mid-tap voltage of the on-load tap changer, or no-load tap changer tap voltage. | ||||
HV Rating | 30 | 0B | 100MVA | 0.1MVA to 5000MVA step 0.1MVA |
This rating is used by the thermal overload function if the monitored winding is set to HV. | ||||
% Reactance | 30 | 0C | 0.1 | 1% to 100% step 0.63% |
Transformer leakage reactance. | ||||
LV Vector Group | 30 | 0D | 0 | 0 to 11 step 1 |
This is used to provide vector correction for phase shift between HV and LV windings. | ||||
LV Connection | 30 | 0E | Y-Wye | Y-Wye, D-Delta or Z-Zigzag |
The LV winding connections can be configured as Wye, Delta, or Zigzag. | ||||
LV Grounding | 30 | 0F | Grounded | Grounded or Ungrounded |
When set as grounded, the P64x filters the zero sequence current in the LV side. When set as ungrounded, no zero sequence filtering is done in the LV side. | ||||
LV Nominal | 30 | 10 | 220kV | 100V to 1MV step 1V |
Nominal voltage of the LV winding, mid-tap voltage of the on-load tap changer, or no-load tap changer tap voltage. | ||||
LV Rating | 30 | 11 | 100MVA | 0.1MVA to 5000MVA step 0.1MVA |
This rating is used by the thermal overload function if the monitored winding is set to LV. | ||||
TV Vector Group | 30 | 12 | 0 | 0 to 11 step 1 |
P643 and P645 only. This is used to provide vector correction for phase shift between HV and TV windings. |
||||
TV Connection | 30 | 13 | Y-Wye | Y-Wye,D-Delta or Z-Zigzag |
P643 and P645 only. The winding connections can be configured as Wye, Delta, or Zigzag. |
||||
TV Grounding | 30 | 14 | Grounded | Grounded or Ungrounded |
P643 and P645 only. Simple: Grounded = P64x filters zero sequence current on TV side. Ungrounded = no zero sequence filtering is done on LV side. Advanced: Grounding = Information only, and zero sequence filtering depends on Zero seq filt HV setting. |
||||
TV Nominal | 30 | 15 | 220kV | 100V to 1MV step 1V |
P643 and P645 only. Nominal voltage of the TV winding. |
||||
TV Rating | 30 | 16 | 100MVA | 0.1MVA to 5000MVA step 0.1MVA |
P643 and P645 only. This rating is used by the thermal overload function if the monitored winding is set to TV. |
||||
Match Factor CT1 | 30 | 20 | Set by relay | Set by relay |
CT1 ratio correction factor used by the differential function. | ||||
Match Factor CT2 | 30 | 21 | Set by relay | Set by relay |
CT2 ratio correction factor used by the differential function. | ||||
Match Factor CT3 | 30 | 22 | Set by relay | Set by relay |
P643 and P645 only. CT3 ratio correction factor used by the differential function. |
||||
Match Factor CT4 | 30 | 23 | Set by relay | Set by relay |
P645 only. CT4 ratio correction factor used by the differential function. |
||||
Match Factor CT5 | 30 | 24 | Set by relay | Set by relay |
P645 only. CT5 ratio correction factor used by the differential function. |
||||
MatchFac REF HV | 30 | 25 | Set by relay | Set by relay |
Ratio correction factor used by REF HV protection. | ||||
MatchFac REF LV | 30 | 26 | Set by relay | Set by relay |
Ratio correction factor used by REF LV protection. | ||||
MatchFac REF TV | 30 | 27 | Set by relay | Set by relay |
P643 and P645 only. Ratio correction factor used by REF TV protection. |
||||
MatchFac REFAuto | 30 | 28 | Set by relay | Set by relay |
Ratio correction factor used by REF Auto protection. | ||||
Phase Sequence | 30 | 5E | Standard ABC | Standard ABC or Reverse ACB |
This sets the phase rotation. It affects the positive and negative sequence quantities calculated by the relay. It also affects functions that are dependent on phase quantities. | ||||
VT Reversal | 30 | 5F | No Swap | No Swap, A-B Swap or C-A Swap |
P643 and P645 only. For applications where 2-phase current inputs are swapped. |
||||
CT1 Reversal | 30 | 60 | No Swap | No Swap, A-B Swap or C-A Swap |
For applications where 2-phase current inputs are swapped. | ||||
CT2 Reversal | 30 | 61 | No Swap | No Swap, A-B Swap or C-A Swap |
For applications where 2-phase current inputs are swapped. | ||||
CT3 Reversal | 30 | 62 | No Swap | No Swap, A-B Swap or C-A Swap |
P643 and P645 only. For applications where 2-phase current inputs are swapped. |
||||
CT4 Reversal | 30 | 63 | No Swap | No Swap, A-B Swap or C-A Swap |
P645 only. For applications where 2-phase current inputs are swapped. |
||||
CT5 Reversal | 30 | 64 | No Swap | No Swap, A-B Swap or C-A Swap |
P645 only. For applications where 2-phase current inputs are swapped. |
||||
Differential Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: DIFF PROTECTION |
31 | 00 | ||
This column contains the GROUP 1 DIFF PROTECTION parameters | ||||
Trans Diff | 31 | 01 | Enabled | Enabled or Disabled |
This enables or disables differential protection for setting group1. | ||||
Set Mode | 31 | 02 | Simple | Simple or Advanced |
Defines Simple or Advanced Mode, as per
HV/LV/TV Grounding. Advanced = zero sequence filtering enabled/disabled in Zero seq filt HV/LV/TV. Simple = Is-HS1 calculated as 1/Xt (Xt=transformer reactance); and Zero seq filt HV/LV/TV, Is-HS1 and Is-Hs2 hidden |
||||
Is1 | 31 | 03 | 0.2 | 0.1pu to 2.5pu step 0.01pu |
Minimum differential threshold of the low set differential characteristic | ||||
K1 | 31 | 04 | 0.3 | 0% to 200% step 1% |
First slope setting of the low set differential characteristic | ||||
Is2 | 31 | 05 | 1 | 0.1pu to 20pu step 0.01pu |
Bias current threshold for the second slope of the low set differential characteristic | ||||
K2 | 31 | 06 | 0.8 | 15% to 200% step 1% |
Second slope setting of the low set differential characteristic | ||||
tDiff | 31 | 07 | 0s | 0 to 10s step 10ms |
Differential time delay | ||||
Is-CTS | 31 | 08 | 1.5 | 0.1pu to 2.5pu step 0.01pu |
In restrain mode, the differential protection Is1 setting is increased to Is-CTS setting after CT failure is detected. The Is-CTS setting increases the restrain region of the differential characteristic | ||||
Is-HS1 | 31 | 10 | 1/Xt | 2.00pu to 32pu step 0.1pu |
High set element one. In the simple mode the relay calculates Is-HS1 as 1/Xt. Where Xt is the transformer reactance. This setting is hidden in simple mode. In advance mode Is-HS1 is visible and settable. | ||||
HS2 Status | 31 | 11 | Enabled | Enabled or Disabled |
Enable or Disabled High set element two | ||||
Is-HS2 | 31 | 12 | 32 | 2.00pu to 32pu step 0.1pu |
High Set element two when HS2 Status is enabled. When HS2 Status is enabled, High set element two. In the simple mode the relay calculates Is-HS2 as 1/Xt. Where Xt is the transformer reactance. This setting is hidden in simple mode. In advance mode Is-HS2 is visible and settable. | ||||
Diff calc remove | 31 | 13 | Disabled | Disabled or TV |
P643 and P645 only. Disable means diff protection is same as usual, ‘TV’ means phase currents of the ends which belong to TV are no effect on trans diff protection. This setting is only settable in advance mode. |
||||
Transient Bias | 31 | 14 | Enabled | Enabled or Disabled |
Default setting ‘Enabled’ means trans diff protection is same as version B2A, ‘Disabled ‘ means the transient bias is removed from bias current for all cases. | ||||
Zero seq filt HV | 31 | 20 | Enabled | Enabled or Disabled |
Enables or disables zero sequence filtering on the HV winding. This setting is only visible and settable in advance mode. | ||||
Zero seq filt LV | 31 | 21 | Enabled | Enabled or Disabled |
Enables or disables zero sequence filtering on the LV winding. This setting is only visible and settable in advance mode. | ||||
Zero seq filt TV | 31 | 22 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables zero sequence filtering on the TV winding. This setting is only visible and settable in advance mode. |
||||
2nd harm blocked | 31 | 28 | Enabled | Enabled or Disabled |
2nd harm blocked | ||||
Ih(2)%> | 31 | 29 | 0.2 | 5% to 50% step 1% |
Second harmonic blocking threshold | ||||
Cross blocking | 31 | 2A | Enabled | Enabled or Disabled |
Enables or disables cross blocking | ||||
CTSat and NoGap | 31 | 2B | Enabled | Enabled or Disabled |
Enables or disables CT saturation detection | ||||
5th harm blocked | 31 | 33 | Enabled | Enabled or Disabled |
Enables or disables 5th harmonic blocking | ||||
Ih(5)%> | 31 | 34 | 0.35 | 0% to 100% step 1% |
Fifth harmonic blocking threshold | ||||
Circuitry Fail | 31 | 40 | Disabled | Enabled or Disabled |
Enables or disables the circuitry fail alarm | ||||
Is-cctfail | 31 | 41 | 0.1 | 0.03pu to 1pu step 0.01pu |
Minimum differential threshold of the circuitry fail alarm | ||||
K-cctfail | 31 | 42 | 0.1 | 0% to 50% step 1% |
Slope for the circuitry fail alarm function | ||||
CctFail Delay | 31 | 43 | 5s | 0s to 10s step 0.1s |
Sets the circuitry fail alarm time delay | ||||
Restricted Earth Fault (REF) Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: REF PROTECTION |
32 | 00 | ||
This column contains GROUP1 REF PROTECTION parameters. | ||||
REF HV status | 32 | 01 | LowZ REF | Disabled, LowZ REF or HighZ REF |
Select to be HighZ REF or LowZ REF or disable for the HV winding | ||||
Neutral CT Input | 32 | 02 | TN1 | TN1 |
HV IS1 Set | 32 | 03 | 0.09 | 0.02In to 1In step 0.01In |
Minimum differential threshold of the HV restricted earth fault characteristic | ||||
HV IS2 Set | 32 | 04 | 0.9 | 0.1In to 10In step 0.1In |
Bias current threshold for the second slope of the HV restricted earth fault characteristic | ||||
HV IREF K1 | 32 | 05 | 0 | 0% to 150% step 1% |
First slope setting of the HV REF characteristic. Normally set to 0% to give optimum sensitivity for internal faults | ||||
HV IREF K2 | 32 | 06 | 1.5 | 15% to 150% step 1% |
Second slope setting of the HV REF characteristic. Normally set to 150% to ensure adequate restraint for external faults. | ||||
HV tREF | 32 | 07 | 0s | 0.01s |
Operating time delay for the HV REF element | ||||
HV IREF>Is | 32 | 08 | 0.09 | 0.02In to 1In step 0.01In |
Threshold of the HV HighZ restricted earth fault. | ||||
HV Trans.Bias | 32 | 09 | Enabled | Enabled or Disabled |
Default setting ‘Enabled’ means REF protection is same as version B2A, ‘Disabled ‘ means the transient bias is removed from bias current for all cases. | ||||
REF LV status | 32 | 20 | Disabled | Disabled, LowZ REF or HighZ REF |
Select to be HighZ REF or LowZ REF or disable for the LV winding | ||||
Neutral CT Input | 32 | 21 | TN2 | TN2 |
LV IS1 Set | 32 | 22 | 0.09 | 0.02In to 1In step 0.01In |
Minimum differential threshold of the LV REF characteristic | ||||
LV IS2 Set | 32 | 23 | 0.9 | 0.1In to 10In step 0.1In |
Bias current threshold for the second slope of the LV REF characteristic | ||||
LV IREF K1 | 32 | 24 | 0 | 0% to 150% step 1% |
First slope setting of the LV REF characteristic. Normally set to 0% to give optimum sensitivity for internal faults | ||||
LV IREF K2 | 32 | 25 | 1.5 | 15% to 150% step 1% |
Second slope setting of the LV REF characteristic. Normally set to 150% to ensure adequate restraint for external faults. | ||||
LV tREF | 32 | 26 | 0s | 0s to 10s step 0.01s |
Operating time delay for the LV restricted earth fault element | ||||
LV IREF>Is | 32 | 27 | 0.09 | 0.02In to 1In step 0.01In |
Threshold of the LV HighZ restricted earth fault. | ||||
LV Trans.Bias | 32 | 28 | Enabled | Enabled or Disabled |
Default setting ‘Enabled’ means REF protection is same as version B2A, ‘Disabled ‘ means the transient bias is removed from bias current for all cases. | ||||
REF TV status | 32 | 30 | Disabled | Disabled, LowZ REF or HighZ REF |
P643 and P645 only. Select to be HighZ REF or LowZ REF or disable for the LV winding |
||||
Neutral CT Input | 32 | 31 | TN3 | TN3 |
P643 and P645 only. | ||||
TV IS1 Set | 32 | 32 | 0.09 | 0.02In to 1In step 0.01In |
P643 and P645 only. Minimum differential threshold of the TV REF characteristic |
||||
TV IS2 Set | 32 | 33 | 0.9 | 0.1In to 10In step 0.1In |
P643 and P645 only. Bias current threshold for the second slope of the TV REF characteristic |
||||
TV IREF K1 | 32 | 34 | 0 | 0% to 150% step 1% |
P643 and P645 only. First slope setting of the TV REF characteristic. Normally set to 0% to give optimum sensitivity for internal faults |
||||
TV IREF K2 | 32 | 35 | 1.5 | 15% to 150% step 1% |
P643 and P645 only. Second slope setting of the TV REF characteristic. Normally set to 150% to ensure adequate restraint for external faults |
||||
TV tREF | 32 | 36 | 0s | 0s to 10s step 0.01s |
P643 and P645 only. Operating time delay for the TV restricted earth fault element |
||||
TV IREF>Is | 32 | 37 | 0.09 | 0.02In to 1In step 0.01In |
P643 and P645 only. Threshold of the TV HighZ restricted earth fault. |
||||
TV Trans.Bias | 32 | 38 | Enabled | Enabled or Disabled |
Default setting ‘Enabled’ means REF protection is same as version B2A, ‘Disabled ‘ means the transient bias is removed from bias current for all cases. | ||||
REF Auto status | 32 | 40 | LowZ REF | Disabled, LowZ REF or HighZ REF |
Enables or disables restricted earth fault protection for the Auto | ||||
Neutral CT Input | 32 | 41 | TN1 | TN1 |
Indicates which single phase CT is used for Auto REF calculation. | ||||
Auto IS1 Set | 32 | 42 | 0.09 | 0.02In to 1In step 0.01In |
Minimum differential threshold of the Auto REF characteristic | ||||
Auto IS2 Set | 32 | 43 | 0.9 | 0.1In to 10In step 0.1In |
Bias current threshold for the second slope of the Auto REF characteristic | ||||
Auto IREF K1 | 32 | 44 | 0 | 0% to 150% step 1% |
First slope setting of the Auto REF characteristic. Normally set to 0% to give optimum sensitivity for internal faults | ||||
Auto IREF K2 | 32 | 45 | 1.5 | 15% to 150% step 1% |
Second slope setting of the Auto REF characteristic. Normally set to 150% to ensure adequate restraint for external faults | ||||
Auto tREF | 32 | 46 | 0s | 0s to 10s step 0.01s |
Operating time delay for the Auto restricted earth fault element | ||||
Auto IS1 Set | 32 | 47 | 0.09 | 0.02In to 1In step 0.01In |
Threshold of the Auto HighZ restricted earth fault. | ||||
Auto Trans.Bias | 32 | 48 | Enabled | Enabled or Disabled |
Default setting ‘Enabled’ means REF protection is same as
version B2A, ‘Disabled ‘ means the transient bias is removed from bias current for all cases. |
||||
NPS Overcurrent Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: NPS OVER ENT |
34 | 00 | ||
This column contains GROUP 1: NPS OVERCURRENT parameters | ||||
NPS O/C 1 | 34 | 01 | T1 | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Negative Sequence Overcurrent 1 | ||||
I2>1 Status | 34 | 02 | Disabled | Enabled or Disabled |
Enables or disables stage 1 of NPS OC 1 | ||||
I2>1 Char | 34 | 03 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Slelect the stage 1 of NPSOC element 1 time characteristic | ||||
I2>1 Direction | 34 | 04 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>1 Current Set | 34 | 05 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 1 NPS element 1 | ||||
I2>1 Time Delay | 34 | 06 | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 1 NPS overcurrent element 1 | ||||
I2>1 TMS | 34 | 07 | 1 | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic | ||||
I2>1 Time Dial | 34 | 08 | 1 | 0.01 to 100 step 0.01 |
Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic | ||||
I2>1 K(RI) | 34 | 09 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic | ||||
I2>1 Reset Char | 34 | 0A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I2>1 tReset | 34 | 0B | 0s | 0s to 100s step 0.01s |
Setting that determine the reset/release time for definite time reset characteristic | ||||
I2>2 Status | 34 | 12 | Disabled | Enabled or Disabled |
Enables or disables stage 2 of NPS OC 1 | ||||
I2>2 Char | 34 | 13 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Slelect stage 2 of NPSOC element 1 time characteristic | ||||
I2>2 Direction | 34 | 14 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>2 Current Set | 34 | 15 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 2 NPS element 1 | ||||
I2>2 Time Delay | 34 | 16 | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 2 NPS overcurrent element 1 | ||||
I2>2 TMS | 34 | 17 | 1s | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic | ||||
I2>2 Time Dial | 34 | 18 | 1 | 0.01 to 100 step 0.01 |
Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic | ||||
I2>2 K(RI) | 34 | 19 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic | ||||
I2>2 Reset Char | 34 | 1A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I2>2 tReset | 34 | 1B | 0s | 0s to 100s step 0.01s |
Setting that determine the reset/release time for definite time reset characteristic | ||||
I2>3 Status | 34 | 21 | Disabled | Enabled or Disabled |
Enables or disables stage 3 NPS definite time element 1 | ||||
I2>3 Direction | 34 | 22 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>3 Current Set | 34 | 23 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 3 NPS element 1 | ||||
I2>3 Time Delay | 34 | 24 | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 3 NPS overcurrent element 1 | ||||
I2>4 Status | 34 | 27 | Disabled | Enabled or Disabled |
Enables or disables stage 4 NPS definite time element 1 | ||||
I2>4 Direction | 34 | 28 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>4 Current Set | 34 | 29 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 4 NPS element 1 | ||||
I2>4 Time Delay | 34 | 2A | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 4 NPS overcurrent element 1 | ||||
I2> VTS Block | 34 | 2D | 15 | 4-bit binary setting |
Logic settings that determine whether VT supervision will block selected negative sequence overcurrent stages. VTS Block only affects directional overcurrent protection. Setting 0 allows continued non-directional operation | ||||
I2> V2pol Set | 34 | 2E | 5*V1 | 0.5*V1 to 25*V1 step 0.5*V1 |
The minimum threshold above which the relay must detect a polarizing voltage for the negative phase sequence directional elements to operate | ||||
I2> Char Angle | 34 | 2F | -60° | -95° to 95° step 1°’ |
Characteristic angle for directionalized NPS fault protection | ||||
NPS O/C 2 | 34 | 31 | P642: T2 P643: T3 P645: T5 | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Negative Sequence Overcurrent 2 | ||||
I2>1 Status | 34 | 32 | Disabled | Enabled or Disabled |
Enables or disables stage 1 of NPS OC 2 | ||||
I2>1 Char | 34 | 33 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Slelect stage 1 of NPSOC element 2 time characteristic | ||||
I2>1 Direction | 34 | 34 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>1 Current Set | 34 | 35 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 1 NPS element 2 | ||||
I2>1 Time Delay | 34 | 36 | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 1 NPS overcurrent element 2 | ||||
I2>1 TMS | 34 | 37 | 1s | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic | ||||
I2>1 Time Dial | 34 | 38 | 1 | 0.01 to 100 step 0.01 |
Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic | ||||
I2>1 K(RI) | 34 | 39 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic | ||||
I2>1 Reset Char | 34 | 3A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I2>1 tReset | 34 | 3B | 0s | 0s to 100s step 0.01s |
Setting that determine the reset/release time for definite time reset characteristic | ||||
I2>2 Status | 34 | 42 | Disabled | Enabled or Disabled |
Enables or disables stage 2 NPS OC 2 | ||||
I2>2 Char | 34 | 43 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Slelect stage 2 of NPSOC element 2 time characteristic | ||||
I2>2 Direction | 34 | 44 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>2 Current Set | 34 | 45 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 2 NPS element 2 | ||||
I2>2 Time Delay | 34 | 46 | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 2 NPS overcurrent element 2 | ||||
I2>2 TMS | 34 | 47 | 1s | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic | ||||
I2>2 Time Dial | 34 | 48 | 1 | 0.01 to 100 step 0.01 |
Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic | ||||
I2>2 K(RI) | 34 | 49 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic | ||||
I2>2 Reset Char | 34 | 4A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I2>2 tReset | 34 | 4B | 0s | 0s to 100s step 0.01s |
Setting that determine the reset/release time for definite time reset characteristic | ||||
I2>3 Status | 34 | 51 | Disabled | Enabled or Disabled |
Enables or disables stage 3 NPS OC 2 | ||||
I2>3 Direction | 34 | 52 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>3 Current Set | 34 | 53 | 0.2 | 24A to 1200A step 3A |
Current pick-up setting for the stage 3 NPS OC 2 | ||||
I2>3 Time Delay | 34 | 54 | 10 | 0s to 100s step 0.01s |
Operating time delay for the stage 3 NPS OC 2 | ||||
I2>4 Status | 34 | 57 | Disabled | Enabled or Disabled |
Enables or disables stage 4 NPS OC 2 | ||||
I2>4 Direction | 34 | 58 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Determines the direction of measurement for this element | ||||
I2>4 Current Set | 34 | 59 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
Current pick-up setting for the stage 4 OC 2 | ||||
I2>4 Time Delay | 34 | 5A | 10s | 0s to 100s step 0.01s |
Operating time delay for the stage 4 NPS OC2 | ||||
I2> VTS Block | 34 | 5D | 15 | 4-bit binary setting |
Logic settings that determine whether VT supervision will block selected negative sequence overcurrent stages. VTS Block only affects directional overcurrent protection. Setting 0 allows continued non-directional operation | ||||
I2> V2pol Set | 34 | 5E | 5*V1 | 0.5*V1 to 25*V1 step 0.5*V1 |
The minimum threshold above which the relay must detect a polarizing voltage for the negative phase sequence directional elements to operate | ||||
I2> Char Angle | 34 | 5F | -60° | -95° to 95° step 1° |
Characteristic angle for directionalized NPS fault protection | ||||
NPS O/C 3 | 34 | 61 | P643: T2 P645: T3 | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
P643 and P645 only. Negetive Sequence Overcurrent 3 |
||||
I2>1 Status | 34 | 62 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables stage 1 of NPS OC 3 |
||||
I2>1 Char | 34 | 63 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Slelect stage 1 of NPSOC element 3 time characteristic |
||||
I2>1 Direction | 34 | 64 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Determines the direction of measurement for this element |
||||
I2>1 Current Set | 34 | 65 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
P643 and P645 only. Current pick-up setting for the stage 1 NPS element 3 |
||||
I2>1 Time Delay | 34 | 66 | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Operating time delay for the stage 1 NPS overcurrent element 3 |
||||
I2>1 TMS | 34 | 67 | 1s | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic |
||||
I2>1 Time Dial | 34 | 68 | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic |
||||
I2>1 K(RI) | 34 | 69 | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic |
||||
I2>1 Reset Char | 34 | 6A | DT | DT or Inverse |
P643 and P645 only. Setting to determine the type of reset/release characteristic of the IEEE/US curves |
||||
I2>1 tReset | 34 | 6B | 0s | 0s to 100s step 0.01s |
P643 and P645 only. Setting that determine the reset/release time for definite time reset characteristic |
||||
I2>2 Status | 34 | 72 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables stage 2 of NPS OC 3 |
||||
I2>2 Char | 34 | 73 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Slelect stage 2 of NPSOC element 3 time characteristic |
||||
I2>2 Direction | 34 | 74 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Determines the direction of measurement for this element |
||||
I2>2 Current Set | 34 | 75 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
P643 and P645 only. Current pick-up setting for the stage 2 NPS element 3 |
||||
I2>2 Time Delay | 34 | 76 | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Operating time delay for the stage 2 NPS overcurrent element 3 |
||||
I2>2 TMS | 34 | 77 | 1s | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of IEC IDMT characteristic |
||||
I2>2 Time Dial | 34 | 78 | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Setting for the time dial setting to adjust the operating time of IEEE/US IDMT characteristic |
||||
I2>2 K(RI) | 34 | 79 | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Setting for the time multiplier setting to adjust the oprating time for the RI IDMT characteristic |
||||
I2>2 Reset Char | 34 | 7A | DT | DT or Inverse |
P643 and P645 only. Setting to determine the type of reset/release characteristic of the IEEE/US curves |
||||
I2>2 tReset | 34 | 7B | 0s | 0s to 100s step 0.01s |
P643 and P645 only. Setting that determine the reset/release time for definite time reset characteristic |
||||
I2>3 Status | 34 | 81 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables stage 3 NPS OC 3 |
||||
I2>3 Direction | 34 | 82 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Determines the direction of measurement for this element |
||||
I2>3 Current Set | 34 | 83 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
P643 and P645 only. Current pick-up setting for the stage 3 NPS OC 3 |
||||
I2>3 Time Delay | 34 | 84 | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Operating time delay for the stage 3 NPS OC 3 |
||||
I2>4 Status | 34 | 87 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables stage 4 NPS OC 3 |
||||
I2>4 Direction | 34 | 88 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Determines the direction of measurement for this element |
||||
I2>4 Current Set | 34 | 89 | 0.2*I1 | 0.08*I1 to 4*I1 step 0.01*I1 |
P643 and P645 only. Current pick-up setting for the stage 4 NPS OC 3 |
||||
I2>4 Time Delay | 34 | 8A | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Operating time delay for the stage 4 NPS OC 3 |
||||
I2> VTS Block | 34 | 8D | 15 | 4-bit binary setting |
P643 and P645 only. Logic settings that determine whether VT supervision will block selected negative sequence overcurrent stages. VTS Block only affects directional overcurrent protection. Setting 0 allows continued non-directional operation |
||||
I2> V2pol Set | 34 | 8E | 5*V1 | 0.5*V1 to 25*V1 step 0.5*V1 |
P643 and P645 only. The minimum threshold above which the relay must detect a polarizing voltage for the negative phase sequence directional elements to operate |
||||
I2> Char Angle | 34 | 8F | -60° | -95° to 95° step 1° |
P643 and P645 only. Characteristic angle for directionalized NPS fault protection |
||||
Overcurrent Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: OVERCUR 1 |
35 | 00 | ||
This column contains GROUP 1: OVERCURRENT 1 parameters | ||||
Overcurrent 1 | 35 | 01 | T1 | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Overcurrent 1 | ||||
I>1 Status | 35 | 02 | Disabled | Enabled or Disabled |
Setting to enable or disable the first stage overcurrent element | ||||
I>1 Char | 35 | 03 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the first stage overcurrent element | ||||
I>1 Direction | 35 | 04 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the first stage element | ||||
I>1 Current Set | 35 | 05 | 1 | 24A to 1200A step 3A |
Pick-up setting for the first stage overcurrent element | ||||
I>1 Time Delay | 35 | 06 | 1s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the first stage element | ||||
I>1 TMS | 35 | 07 | 1 | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
I>1 Time Dial | 35 | 08 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
I>1 K (RI) | 35 | 09 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
I>1 Reset Char | 35 | 0A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I>1 tRESET | 35 | 0B | 0 | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
I>2 Status | 35 | 12 | Disabled | Enabled or Disabled |
Setting to enable or disable the first stage overcurrent element | ||||
I>2 Char | 35 | 13 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the second stage overcurrent element | ||||
I>2 Direction | 35 | 14 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the second stage element | ||||
I>2 Current Set | 35 | 15 | 1 | 24A to 1200A step 3A |
Pick-up setting for the second stage overcurrent element | ||||
I>2 Time Delay | 35 | 16 | 1s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the second stage element. | ||||
I>2 TMS | 35 | 17 | 1s | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
I>2 Time Dial | 35 | 18 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
I>2 K (RI) | 35 | 19 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
I>2 Reset Char | 35 | 1A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I>2 tRESET | 35 | 1B | 0s | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
I>3 Status | 35 | 21 | Disabled | Enabled or Disabled |
Setting to enable or disable the third stage overcurrent element | ||||
I>3 Direction | 35 | 22 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the third stage element | ||||
I>3 Current Set | 35 | 23 | 10A | 24A to 3840A step 3A |
Pick-up setting for the third stage overcurrent element | ||||
I>3 Time Delay | 35 | 24 | 0s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the third stage element | ||||
I>4 Status | 35 | 27 | Disabled | Enabled or Disabled |
Setting to enable or disable the fourth stage overcurrent element | ||||
I>4 Direction | 35 | 28 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the fourth stage element | ||||
I>4 Current Set | 35 | 29 | 10 | 24A to 3840A step 3A |
Pick-up setting for the fourth stage overcurrent element | ||||
I>4 Time Delay | 35 | 2A | 0s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the fourth stage element. | ||||
I> Char Angle | 35 | 2D | 30° | -95°’ to 95° step ‘1°’ |
Setting for the relay characteristic angle used for the directional decision | ||||
I> Function Link | 35 | 2E | 15 | 4-bit binary setting |
Logic Settings that determine whether blocking signals from VT supervision affect certain overcurrent stages | ||||
Overcurrent 2 | 35 | 31 | P642: T2 P643: T3 P645: T5 | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Overcurrent 2 | ||||
I>1 Status | 35 | 32 | Disabled | Enabled or Disabled |
Setting to enable or disable the first stage overcurrent element | ||||
I>1 Char | 35 | 33 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the first stage overcurrent element | ||||
I>1 Direction | 35 | 34 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the first stage element | ||||
I>1 Current Set | 35 | 35 | 1 | 24A to 1200A step 3A |
Pick-up setting for the first stage overcurrent element | ||||
I>1 Time Delay | 35 | 36 | 1s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the first stage element | ||||
I>1 TMS | 35 | 37 | 1 | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
I>1 Time Dial | 35 | 38 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
I>1 K (RI) | 35 | 39 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
I>1 Reset Char | 35 | 3A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I>1 tRESET | 35 | 3B | 0s | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
I>2 Status | 35 | 42 | Disabled | Enabled or Disabled |
Setting to enable or disable the second stage overcurrent element | ||||
I>2 Char | 35 | 43 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the first stage overcurrent element | ||||
I>2 Direction | 35 | 44 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the second stage element | ||||
I>2 Current Set | 35 | 45 | 1 | 24A to 1200A step 3A |
Pick-up setting for the second stage overcurrent element | ||||
I>2 Time Delay | 35 | 46 | 1 | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the second stage element. | ||||
I>2 TMS | 35 | 47 | 1 | 0.025 to 1.2 step 0.005 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
I>2 Time Dial | 35 | 48 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
I>2 K (RI) | 35 | 49 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
I>2 Reset Char | 35 | 4A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
I>2 tRESET | 35 | 4B | 0 | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
I>3 Status | 35 | 51 | Disabled | Enabled or Disabled |
Setting to enable or disable the third stage overcurrent element | ||||
I>3 Direction | 35 | 52 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the third stage element | ||||
I>3 Current Set | 35 | 53 | 10 | 24A to 3840A step 3A |
Pick-up setting for the third stage overcurrent element | ||||
I>3 Time Delay | 35 | 54 | 0 | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the third stage element | ||||
I>4 Status | 35 | 57 | Disabled | Enabled or Disabled |
Setting to enable or disable the fourth stage overcurrent element | ||||
I>4 Direction | 35 | 58 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the fourth stage element | ||||
I>4 Current Set | 35 | 59 | 10 | 24A to 3840A step 3A |
Pick-up setting for the fourth stage overcurrent element | ||||
I>4 Time Delay | 35 | 5A | 0s | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the fourth stage element. | ||||
I> Char Angle | 35 | 5D | 30° | -95° to 95° step 1° |
Setting for the relay characteristic angle used for the directional decision | ||||
I> Function Link | 35 | 5E | 15 | 4-bit binary setting |
Logic Settings that determine whether blocking signals from VT supervision affect certain overcurrent stages | ||||
Overcurrent 3 | 35 | 61 | P643: T2 P645: T3 | P643 and P645 only. Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
P643 and P645 only. Overcurrent 3 | ||||
I>1 Status | 35 | 62 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the first stage overcurrent element |
||||
I>1 Char | 35 | 63 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Setting for the tripping characteristic for the first stage overcurrent element |
||||
I>1 Direction | 35 | 64 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. This setting determines the direction of measurement for the first stage element |
||||
I>1 Current Set | 35 | 65 | 1 | 24A to 1200A step 3A |
P643 and P645 only. Pick-up setting for the first stage overcurrent element |
||||
I>1 Time Delay | 35 | 66 | 1 | 0s to 100s step 0.01s |
P643 and P645 only. Setting for the time delay for the definite time setting if selected for the first stage element |
||||
I>1 TMS | 35 | 67 | 1 | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic |
||||
I>1 Time Dial | 35 | 68 | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves |
||||
I>1 K (RI) | 35 | 69 | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Setting for the time multiplier to adjust the operating time for the RI curve |
||||
I>1 Reset Char | 35 | 6A | DT | DT or Inverse |
P643 and P645 only. Setting to determine the type of reset/release characteristic of the IEEE/US curves |
||||
I>1 tRESET | 35 | 6B | 0 | 0s to 100s step 0.01s |
P643 and P645 only. Setting that determines the reset/release time for definite time reset characteristic |
||||
I>2 Status | 35 | 72 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the second stage overcurrent element |
||||
I>2 Char | 35 | 73 | DT (DT) | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Setting for the tripping characteristic for the second stage overcurrent element |
||||
I>2 Direction | 35 | 74 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. This setting determines the direction of measurement for the second stage element |
||||
I>2 Current Set | 35 | 75 | 1 | 24A to 1200A step 3A |
P643 and P645 only. Pick-up setting for the second stage overcurrent element |
||||
I>2 Time Delay | 35 | 76 | 1 | 0s to 100s step 0.01s |
P643 and P645 only. Setting for the time delay for the definite time setting if selected for the second stage element. |
||||
I>2 TMS | 35 | 77 | 1 | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic |
||||
I>2 Time Dial | 35 | 78 | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves |
||||
I>2 K (RI) | 35 | 79 | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Setting for the time multiplier to adjust the operating time for the RI curve |
||||
I>2 Reset Char | 35 | 7A | DT | DT or Inverse |
P643 and P645 only. Setting to determine the type of reset/release characteristic of the IEEE/US curves |
||||
I>2 tRESET | 35 | 7B | 0 | 0s to 100s step 0.01s |
P643 and P645 only. Setting that determines the reset/release time for definite time reset characteristic |
||||
I>3 Status | 35 | 81 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the third stage overcurrent element |
||||
I>3 Direction | 35 | 82 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. This setting determines the direction of measurement for the third stage element |
||||
I>3 Current Set | 35 | 83 | 10 | 24A to 3840A step 3A |
P643 and P645 only. Pick-up setting for the third stage overcurrent element |
||||
I>3 Time Delay | 35 | 84 | 0 | 0s to 100s step 0.01s |
P643 and P645 only. Setting for the time delay for the definite time setting if selected for the third stage element |
||||
I>4 Status | 35 | 87 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the fourth stage overcurrent element |
||||
I>4 Direction | 35 | 88 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. This setting determines the direction of measurement for the fourth stage element |
||||
I>4 Current Set | 35 | 89 | 10 | 24A to 3840A step 3A |
P643 and P645 only. Pick-up setting for the fourth stage overcurrent element |
||||
I>4 Time Delay | 35 | 8A | 0s | 0s to 100s step 0.01s |
P643 and P645 only. Setting for the time delay for the definite time setting if selected for the fourth stage element. |
||||
I> Char Angle | 35 | 8D | 30° | -95° to 95° step 1° |
P643 and P645 only. Setting for the relay characteristic angle used for the directional decision |
||||
I> Function Link | 35 | 8E | 15 | 4-bit binary setting |
P643 and P645 only. Logic Settings that determine whether blocking signals from VT supervision affect certain overcurrent stages |
||||
V DEPENDANT O/C | 35 | 90 | Sub-Heading | Sub-Heading |
Sub-Heading for voltage dependant over current | ||||
V Dep OC>1 Mode | 35 | 91 | VCO | 0 = VCO, 1 = VRO |
Voltage dependant overcurrent stage 1 mode | ||||
V OC>1 | 35 | 92 | Disabled | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Enable or disable Voltage dependant overcurrent stage 1 | ||||
V OC>1 Char | 35 | 93 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the first stage voltage dependant overcurrent element | ||||
V OC>1 Direction | 35 | 94 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the first stage element | ||||
V OC>1 Curr’ Set | 35 | 95 | 1 | 24A to 1200A step 3A |
Current pick-up setting for first stage the voltage dependant over current | ||||
V OC>1 T Delay | 35 | 96 | 1 | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the first stage element | ||||
V OC>1 TMS | 35 | 97 | 1 | 0.025 to 1.2 step 0.025 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
V OC>1 Time Dial | 35 | 98 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
V OC>1 k (RI) | 35 | 99 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
V OC>1 Rst Char | 35 | 9A | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
V OC>1 tRESET | 35 | 9B | 0s | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
V OC>1 Angle | 35 | 9C | 30° | -95° to 95° step 1° |
Setting for the relay characteristic angle used for the directional decision | ||||
V OC>1 V<1 Set | 35 | 9D | 80 | 5V to 120V step 1V |
Sets the voltage V1 threshold at which the current setting of the overcurrent stage/stages becomes reduced, noting that this occurs on a per phase basis. | ||||
V OC>1 K Set | 35 | 9E | 0.25 | 0.1 to 1 step 0.25 |
Sets to determine the overcurrent multiplier factor used to reduce the pick-up overcurrent setting. | ||||
V OC>1 V<2 Set | 35 | 9F | 60 | 5V to 120V step 1V |
Sets the voltage V2 threshold at which the current setting of the overcurrent stage/stages becomes reduced, noting that this occurs on a per phase basis. | ||||
V Dep OC>2 Mode | 35 | A1 | VCO | 0 = VCO, 1 = VRO |
Allows selection of whether voltage control or voltage restrained should be applied. | ||||
V OC>2 | 35 | A2 | Disabled | Disabled, HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
Enable or disable Voltage dependant overcurrent stage 2 | ||||
V OC>2 Char | 35 | A3 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Setting for the tripping characteristic for the second stage voltage dependant overcurrent element | ||||
V OC>2 Direction | 35 | A4 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
This setting determines the direction of measurement for the second stage element | ||||
V OC>2 Curr’ Set | 35 | A5 | 1 | 24A to 1200A step 3A |
Current pick-up setting for second stage the voltage dependant over current | ||||
V OC>2 T Delay | 35 | A6 | 1 | 0s to 100s step 0.01s |
Setting for the time delay for the definite time setting if selected for the second stage element | ||||
V OC>2 TMS | 35 | A7 | 1 | 0.025 to 1.2 step 0.025 |
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
V OC>2 Time Dial | 35 | A8 | 1 | 0.01 to 100 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
V OC>2 k (RI) | 35 | A9 | 1 | 0.1 to 10 step 0.05 |
Setting for the time multiplier to adjust the operating time for the RI curve | ||||
V OC>2 Rst Char | 35 | AA | DT | DT or Inverse |
Setting to determine the type of reset/release characteristic of the IEEE/US curves | ||||
V OC>2 tRESET | 35 | AB | 0s | 0s to 100s step 0.01s |
Setting that determines the reset/release time for definite time reset characteristic | ||||
V OC>2 Angle | 35 | AC | 30° | -95° to 95° step 1° |
Setting for the relay characteristic angle used for the directional decision | ||||
V OC>2 V<1 Set | 35 | AD | 80 | 5V to 120V step 1V |
Sets the voltage V1 threshold at which the current setting of the overcurrent stage/stages becomes reduced, noting that this occurs on a per phase basis. | ||||
V OC>2 K Set | 35 | AE | 0.25 | 0.1 to 1 step 0.25 |
Sets to determine the overcurrent multiplier factor used to reduce the pick-up overcurrent setting. | ||||
V OC>2 V<2 Set | 35 | AF | 60 | 5V to 120V step 1V |
Sets the voltage V2 threshold at which the current setting of
the overcurrent stage/stages becomes reduced, noting that this occurs on a per phase basis. |
||||
Thermal Overload Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: THERMAL OVERLOAD | 37 | 00 | ||
This column contains GROUP1: THERMAL OVERLOAD parameters | ||||
Monit’d winding | 37 | 11 | HV | HV, LV, TV or Biased Current |
An overall through loading picture of the transformer is provided when the monitor winding is set to Biased Current | ||||
Ambient T | 37 | 12 | AVERAGE | RTD 1 to 10, CLIO 1 to 4 or Average |
Ambient temperature | ||||
CLI Input Type | 37 | 15 | 4-20mA | 0-1 mA, 0-10m/a, 0-20mA or 4-20mA |
This setting is available when Ambient T is set to CLIOx | ||||
CLI Minimum | 37 | 16 | 0 | -9999 to 9999 step 0.1 |
This setting is available when Ambient T is set to CLIOx | ||||
CLI Maximum | 37 | 17 | 100 | -9999 to 9999 step 0.1 |
This setting is available when Ambient T is set to CLIOx | ||||
Average Amb T | 37 | 18 | 25 | -25°C to 75°C step 0.1°C |
This setting is available when Ambient T is set to Average | ||||
Top Oil Temp | 37 | 21 | CALCULATED | RTD 1 to 10, CLIO 1 to 4 or Calculated |
The top oil temperature may be calculated by the relay, or it may be measured using RTD or CLIO inputs | ||||
CLI Input Type | 37 | 24 | 4-20mA | 0 to 3 step 1 |
This setting is available when Top Oil T is set to CLIOx | ||||
CLI Minimum | 37 | 25 | 0 | -9999 to 9999 step 0.1 |
This setting is available when Top Oil T is set to CLIOx | ||||
CLI Maximum | 37 | 26 | 100 | -9999 to 9999 step 0.1 |
This setting is available when Top Oil T is set to CLIOx | ||||
IB | 37 | 29 | 1 | 0.1pu to 4pu step 0.01pu |
The relay uses this setting to calculate the ratio of ultimate load to rated load | ||||
Rated NoLoadLoss | 37 | 2A | 3 | 0.1 to 100 step 0.1 |
Ratio of load loss at rated load to no-load loss (iron loss). The transformer manufacturer should provide this parameter | ||||
Hot Spot Overtop | 37 | 2B | 25 | 0.1°C to 200°C step 0.1°C |
Hottest spot temperature over top oil temperature setting. The transformer manufacturer should provide this parameter | ||||
Top Oil Overamb | 37 | 2C | 55 | 0.1°C to 200°C step 0.1°C |
Top oil temperature over ambient temperature setting. The transformer manufacturer should provide this parameter | ||||
Cooling Mode | 37 | 2D | Cooling Mode 1 | Cooling Mode 1, Cooling Mode 2, Cooling Mode 3, Cooling Mode 4 or Select via PSL |
This setting is uesed to select the cooling Mode | ||||
Cooling Mode 1 | 37 | 2F | Sub-Heading | Sub-Heading |
This is the Sub-Heading for cooling mode 1. It is visible when cooling mode is selected to be cooling mode 1 or to be select from PSL | ||||
Winding exp m | 37 | 30 | 0.8 | 0.01 to 2 step 0.01 |
Winding exponient m for cooling mode 1, available when cooling mode is selected to be cooling mode 1 or select from PSL | ||||
Oil exp n | 37 | 31 | 0.8 | 0.01 to 2 step 0.01 |
oil exponient n for cooling mode 1, available when cooling mode is selected to be cooling mode 1 or select from PSL | ||||
Cooling Mode 2 | 37 | 32 | Sub-Heading | Sub-Heading |
This is the Sub-Heading for cooling mode 2. It is visible when cooling mode is selected to be cooling mode 2 or to be select from PSL | ||||
Winding exp m | 37 | 33 | 0.8 | 0.01 to 2 step 0.01 |
Winding exponient m for cooling mode 2, available when cooling mode is selected to be cooling mode 2 or select from PSL | ||||
Oil exp n | 37 | 34 | 0.8 | 0.01 to 2 step 0.01 |
oil exponient n for cooling mode 2, available when cooling mode is selected to be cooling mode 2 or select from PSL | ||||
Cooling Mode 3 | 37 | 35 | Sub-Heading | Sub-Heading |
This is the Sub-Heading for cooling mode 3. It is visible when cooling mode is selected to be cooling mode 3 or to be select from PSL | ||||
Winding exp m | 37 | 36 | 0.8 | 0.01 to 2 step 0.01 |
Winding exponient m for cooling mode 3, available when cooling mode is selected to be cooling mode 3 or select from PSL | ||||
Oil exp n | 37 | 37 | 0.8 | 0.01 to 2 step 0.01 |
oil exponient n for cooling mode 3, available when cooling mode is selected to be cooling mode 3 or select from PSL | ||||
Cooling Mode 4 | 37 | 38 | Sub-Heading | Sub-Heading |
This is the Sub-Heading for cooling mode 4. It is visible when cooling mode is selected to be cooling mode 4 or to be select from PSL | ||||
Winding exp m | 37 | 39 | 0.8 | 0.01 to 2 step 0.01 |
Winding exponient m for cooling mode 4, available when cooling mode is selected to be cooling mode 4 or select from PSL | ||||
Oil exp n | 37 | 3A | 0.8 | 0.01 to 2 step 0.01 |
oil exponient n for cooling mode 4, available when cooling mode is selected to be cooling mode 4 or select from PSL | ||||
Hot spot rise co | 37 | 3B | 1 | 0.01 min to 20 min step 0.01 min |
Hot spot rise co parameters used to calculate the hot spot temperature | ||||
Top oil rise co | 37 | 3C | 120 | 1 min to 1000 min step 1 min |
Top oil reis co parameters used to calculate the top oil temperature | ||||
Tol Status | 37 | 40 | Enabled | Enabled or Disabled |
This setting enables or disables the three hot spot and the three top oil thermal stages | ||||
Hot Spot>1 Set | 37 | 5E | 110 deg C | 1°C to 300°C step 0.1°C |
Hot spot first stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 may be used to set it. See the application chapter for suggested values | ||||
tHot Spot>1 Set | 37 | 5F | 10 mins | 0 min to 60000 min step 1 min |
Hot spot first stage time delay setting | ||||
Hot Spot>2 Set | 37 | 60 | 130 deg C | 1°C to 300°C step 0.1°C |
Hot spot second stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 may be used to set it. See the application chapter for suggested values | ||||
tHot Spot>2 Set | 37 | 61 | 10 mins | 0 min to 60000 min step 0.1 min |
Hot spot second stage time delay setting | ||||
Hot Spot>3 Set | 37 | 62 | 150 deg C | 1°C to 300°C step 0.1°C |
Hot spot third stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 may be used to set it. See the application chapter for suggested values | ||||
tHot Spot>3 Set | 37 | 63 | 10 mins | 0 min to 60000 min step 1 min |
Hot spot third stage time delay setting | ||||
Top Oil>1 Set | 37 | 64 | 70 deg C | 1°C to 300°C step 0.1°C |
Top oil first stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 may be used to set it. See the application chapter for suggested values. | ||||
tTop Oil>1 Set | 37 | 65 | 10 mins | 0 min to 60000 min step 1 min |
Top oil second stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 (may be used to set it. See the application chapter for suggested values | ||||
Top Oil>2 Set | 37 | 66 | 80 deg C | 1°C to 300°C step 0.1°C |
Top oil second stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 (may be used to set it. See the application chapter for suggested values | ||||
tTop Oil>2 Set | 37 | 67 | 10 mins | 0 min to 60000 min step 1 min |
Top oil second stage time delay setting | ||||
Top Oil>3 Set | 37 | 68 | 90 deg C | 1°C to 300°C step 0.1°C |
Top oil third stage setting. The suggested temperature limits given by IEEE Std. C57.91-1995 may be used to set it. See the application chapter for suggested values | ||||
tTop Oil>3 Set | 37 | 69 | 10 mins | 0 min to 60000 min step 1 min |
Top oil third stage time delay setting | ||||
tPre-trip Set | 37 | 6A | 5 mins | 0 min to 60000 min step 1 min |
After the tpre-trip timer has expired, a pre-trip alarm is given. This alarm indicates that if the load remains unchanged a thermal trip will be asserted after the stage timer has expired | ||||
LOL Status | 37 | 80 | Enable | Enabled or Disabled |
Enables or disables the loss of life function | ||||
Life Hours at HS | 37 | 81 | 180000 hrs | 1 hr to 300000 hrs step 1hr |
Life hours at the reference hottest spot temperature. Advice from the transformer manufacturer may be required | ||||
Designed HS temp | 37 | 82 | 110 deg C | 1°C to 200°C step 0.1°C |
The designed hottest spot temperature is 110°C for a transformer rated 65°C average winding rise, and 95°C for a transformer rated 55°C average winding rise | ||||
Constant B Set | 37 | 83 | 15000 | 1 to 100000 step 1 |
Constant B is associated to the life expectancy curve. It is based on modern experimental data, and it may be set to 15000 as suggested by IEEE Std. C57.91-1995 | ||||
FAA> Set | 37 | 84 | 2 | 0.1 to 30 step 0.01 |
Aging acceleration factor setting. If the aging acceleration factor calculated by the relay is above this setting and tFAA has expired, an FAA alarm would be asserted. FAA calculation depends on constant B and the hottest temperature calculated by the thermal element | ||||
tFAA> Set | 37 | 85 | 10 mins | 0 min to 60000 min step 1 min |
Aging acceleration factor timer | ||||
LOL>1 Set | 37 | 86 | 135000 hrs | 1 hr to 300000 hrs step 1hr |
Transformer loss of life setting. If the life already lost by the transformer is above this threshold, an LOL alarm would be asserted after tLOL has expired. LOL calculation depends on the life hours at design hot spot temperature and the calculated residual life | ||||
tLOL> Set | 37 | 87 | 10 mins | 0 min to 60000 min step 1 min |
Loss of life timer | ||||
Reset Life Hours | 37 | 88 | 0 hr | 1 hr to 300000 hrs step 1hr |
Resets the LOL status parameter to the set value when the loss
of life reset command is executed. For new transformers Reset Life Hours is zero, so that when the commissioning of the thermal element is over, the loss of life statistics calculations are reset to zero. For old transformers this setting should indicate how much life the transformer has already lost; therefore, it should be set to the transformer loss of life |
||||
Earth Fault Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: EARTH FAULT | 38 | 00 | ||
This colunm contains GROUP1 : EARTH FAULT parameters | ||||
Earth Fault 1 | 38 | 01 | Enabled | Enabled or Disabled |
Enable or Disable Earth Fault 1 | ||||
EF 1 Input | 38 | 02 | Measured | Measured or Derived |
Selects measured neutral current or derived neutral current | ||||
EF 1 Derived | 38 | 03 | T1 | HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
This is available when earth fault is selected to be derived for stage 1 to detemine the derived current source | ||||
EF 1 Measured | 38 | 04 | TN1 | TN1, TN2 or TN3 |
This is available when earth fault is selected to be measured for stage 1 to determine the measured current source | ||||
IN>1 Status | 38 | 05 | Enabled | Enabled or Disabled |
Setting to enable or disable the first stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>1 Char | 38 | 06 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Tripping characteristic for the first stage earth fault element 1 | ||||
IN>1 Direction | 38 | 07 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the first stage earth fault protection 1 | ||||
IN>1 Current | 38 | 08 | 0.2*In | 24A to 1200A step 3A |
Pick-up setting for the first stage earth fault element 1 | ||||
IN>1 IDG Is | 38 | 09 | 1.5 | 1 to 4 step 0.1 |
Multiple of IN>1 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts | ||||
IN>1 Time Delay | 38 | 0A | 1 | 0s to 200s step 0.01s |
Operating time delay setting for the first stage definite time element | ||||
IN>1 TMS | 38 | 0B | 1 | 0.025 to 1.2 step 0.005 |
Time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
IN>1 Time Dial | 38 | 0C | 1 | 0.01 to 100 step 0.01 |
Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
IN>1 K (RI) | 38 | 0D | 1 | 0.1 to 10 step 0.05 |
Time multiplier to adjust the operating time for the RI curve | ||||
IN>1 IDG Time | 38 | 0E | 1.2 | 1 to 2 step 0.01 |
Minimum operating time at high levels of fault current for the IDG curve | ||||
IN>1 Reset Char | 38 | 0F | DT | DT or Inverse |
Type of reset/release characteristic of the IEEE/US curves | ||||
IN>1 tRESET | 38 | 10 | 0 | 0s to 100s step 0.01s |
Reset/release time setting for definite time reset characteristic | ||||
IN>2 Status | 38 | 15 | Disabled | Enabled or Disabled |
Setting to enable or disable the second stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>2 Char | 38 | 16 | DT | Disabled, DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Tripping characteristic for the second stage earth fault protection 1 | ||||
IN>2 Direction | 38 | 17 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the second stage earth fault protection 1 | ||||
IN>2 Current | 38 | 18 | 0.2 | 24A to 1200A step 3A |
Pick-up setting for the second stage earth fault element 1 | ||||
IN>2 IDG Is | 38 | 19 | 1.5 | 1 to 4 step 0.1 |
Multiple of IN>2 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts | ||||
IN>2 Time Delay | 38 | 1A | 1 | 0s to 200s step 0.01s |
Operating time delay setting for the second stage definite time element | ||||
IN>2 TMS | 38 | 1B | 1 | 0.025 to 1.2 step 0.005 |
Time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
IN>2 Time Dial | 38 | 1C | 1 | 0.01 to 100 step 0.01 |
Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
IN>2 K (RI) | 38 | 1D | 1 | 0.1 to 10 step 0.05 |
Time multiplier to adjust the operating time for the RI curve | ||||
IN>2 IDG Time | 38 | 1E | 1.2 | 1s to 2s step 0.01s |
Minimum operating time at high levels of fault current for the IDG curve | ||||
IN>2 Reset Char | 38 | 1F | DT | DT or Inverse |
Type of reset/release characteristic of the IEEE/US curves | ||||
IN>2 tRESET | 38 | 20 | 0 | 0s to 100s step 0.01s |
Reset/release time setting for definite time reset characteristic | ||||
IN>3 Status | 38 | 25 | Disabled | Enabled or Disabled |
Setting to enable or disable the third stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>3 Direction | 38 | 26 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the third stage earth fault protection 1 | ||||
IN>3 Current | 38 | 27 | 0.5 | 24A to 9600A step 3A |
Pick-up setting for the third stage earth fault element 1 | ||||
IN>3 Time Delay | 38 | 28 | 0 | 0s to 200s step 0.01s |
Operating time delay setting for the third stage definite time element | ||||
IN>4 Status | 38 | 2C | Disabled | Enabled or Disabled |
Setting to enable or disable the fourth stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>4 Direction | 38 | 2D | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the fourth stage earth fault protection 1 | ||||
IN>4 Current | 38 | 2E | 0.5 | 24A to 9600A step 3A |
Pick-up setting for the fourth stage earth fault element 1 | ||||
IN>4 Time Delay | 38 | 2F | 0 | 0s to 200s step 0.01s |
Operating time delay setting for the fourth stage definite time element | ||||
IN> Func Link | 38 | 33 | 15 | 4-bit binary setting |
Settings that determine whether VT supervision logic signals block selected earth fault stages. When set to 1, the VTS operation will block the stage if directionalized. When set to 0, the stage will revert to non-directional on the operation of the VTS | ||||
IN> DIRECTIONAL | 38 | 34 | Sub-Heading | Sub-Heading |
Sub-Heading for IN directional | ||||
IN> Char Angle | 38 | 35 | -60 | -95° to 95° step 1° |
Setting for the relay characteristic angle used for the directional decision | ||||
IN> Pol | 38 | 36 | Zero Sequence | Zero sequence or Neg sequence |
Setting that determines whether the directional function uses zero sequence or negative sequence voltage polarizing | ||||
IN> VNpol Set | 38 | 37 | 5 | 0.5V to 80V step 0.5V |
P643 and P645 only. Setting for the minimum zero sequence voltage polarizing quantity for directional decision |
||||
IN> V2pol Set | 38 | 38 | 5 | 0.5V to 80V step 0.5V |
Setting for the minimum negative sequence voltage polarizing quantity for directional decision | ||||
IN> I2pol Set | 38 | 39 | 0.08 | 24A to 300A step 3A |
Setting for the minimum negative sequence current polarizing quantity for directional decision | ||||
Earth Fault 2 | 38 | 41 | Enabled | Enabled or Disabled |
Enable or Disable Earth Fault 2 | ||||
EF 2 Input | 38 | 42 | Measured | Measured or Derived |
Selects measured neutral current or derived neutral current | ||||
EF 2 Derived | 38 | 43 | P642: T2 P643: T3 P645: T5 | HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
The setting is avaliable when earth fault input is derived to select the derived neural current source | ||||
EF 2 Measured | 38 | 44 | TN2 | TN1, TN2 or TN3 |
The setting is avaliable when earth fault input is measured to select the measured neural curernt source | ||||
IN>1 Status | 38 | 45 | Enabled | Enabled or Disabled |
Setting to enable or disable the first stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>1 Char | 38 | 46 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Tripping characteristic for the first stage earth fault protection 2 | ||||
IN>1 Direction | 38 | 47 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the first stage earth fault protection 2 | ||||
IN>1 Current | 38 | 48 | 0.2*In | 24A to 1200A step 3A |
Pick-up setting for the first stage earth fault element 2 | ||||
IN>1 IDG Is | 38 | 49 | 1.5 | 1 to 4 step 0.1 |
Multiple of IN>1 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts | ||||
IN>1 Time Delay | 38 | 4A | 1 | 0s to 200s step 0.01s |
Operating time delay setting for the first stage definite time element | ||||
IN>1 TMS | 38 | 4B | 1 | 0.025 to 1.2 step 0.005 |
Time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
IN>1 Time Dial | 38 | 4C | 1 | 0.01 to 100 step 0.01 |
Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
IN>1 K (RI) | 38 | 4D | 1 | 0.1 to 10 step 0.05 |
Time multiplier setting to adjust the operating time for the RI curve | ||||
IN>1 IDG Time | 38 | 4E | 1.2 | 1s to 2s step 0.01s |
Minimum operating time at high levels of fault current for the IDG curve | ||||
IN>1 Reset Char | 38 | 4F | DT | DT or Inverse |
Type of reset/release characteristic of the IEEE/US curves | ||||
IN>1 tRESET | 38 | 50 | 0 | 0s to 100s step 0.01s |
Reset/release time setting for definite time reset characteristic | ||||
IN>2 Status | 38 | 55 | Disabled | Enabled or Disabled |
Setting to enable or disable the second stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>2 Char | 38 | 56 | DT | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
Tripping characteristic for the second stage earth fault protection 2 | ||||
IN>2 Direction | 38 | 57 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the second stage earth fault protection 2 | ||||
IN>2 Current | 38 | 58 | 0.2 | 24A to 1200A step 3A |
Pick-up setting for the second stage earth fault element 2 | ||||
IN>2 IDG Is | 38 | 59 | 1.5 | 1 to 4 step 0.1 |
Multiple of IN>2 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts | ||||
IN>2 Time Delay | 38 | 5A | 1 | 0s to 200s step 0.01s |
Operating time delay setting for the second stage definite time element | ||||
IN>2 TMS | 38 | 5B | 1 | 0.025 to 1.2 step 0.005 |
Time multiplier setting to adjust the operating time of the IEC IDMT characteristic | ||||
IN>2 Time Dial | 38 | 5C | 1 | 0.01 to 100 step 0.01 |
Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves | ||||
IN>2 K (RI) | 38 | 5D | 1 | 0.1 to 10 step 0.05 |
Time multiplier to adjust the operating time for the RI curve | ||||
IN>2 IDG Time | 38 | 5E | 1.2 | 1s to 2s step 0.01s |
Minimum operating time at high levels of fault current for the IDG curve | ||||
IN>2 Reset Char | 38 | 5F | DT | DT or Inverse |
Type of reset/release characteristic of the IEEE/US curves | ||||
IN>2 tRESET | 38 | 60 | 0 | 0s to 100s step 0.01s |
Reset/release time setting for definite time reset characteristic | ||||
IN>3 Status | 38 | 65 | Disabled | Enabled or Disabled |
Setting to enable or disable the third stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>3 Direction | 38 | 66 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the third stage earth fault protection 2 | ||||
IN>3 Current | 38 | 67 | 0.5 | 24A to 9600A step 3A |
Pick-up setting for the third stage earth fault element 2 | ||||
IN>3 Time Delay | 38 | 68 | 0 | 0s to 200s step 0.01s |
Operating time delay setting for the third stage definite time element | ||||
IN>4 Status | 38 | 6C | Disabled | Enabled or Disabled |
Setting to enable or disable the fourth stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden | ||||
IN>4 Direction | 38 | 6D | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
Direction setting for the fourth stage earth fault protection 2 | ||||
IN>4 Current | 38 | 6E | 0.5 | 24A to 9600A step 3A |
Pick-up setting for the fourth stage earth fault element 2 | ||||
IN>4 Time Delay | 38 | 6F | 0 | 0s to 200s step 0.01s |
Operating time delay setting for the fourth stage definite time element | ||||
IN> Func Link | 38 | 73 | 15 | 4-bit binary setting |
Settings that determine whether VT supervision logic signals block selected earth fault stages. When set to 1, the VTS operation will block the stage if directionalized. When set to 0, the stage will revert to non-directional on the operation of the VTS | ||||
IN> DIRECTIONAL | 38 | 74 | Sub-Heading | Sub-Heading |
Sub-Heading for IN directional | ||||
IN> Char Angle | 38 | 75 | -60 | -95° to 95° step 1° |
Setting for the relay characteristic angle used for the directional decision | ||||
IN> Pol | 38 | 76 | Zero Sequence | Zero sequence or Neg sequence |
Setting that determines whether the directional function uses zero sequence or negative sequence voltage polarizing | ||||
IN> VNpol Set | 38 | 77 | 5 | 0.5V to 80V step 0.5V |
P643 and P645 only. Setting for the minimum zero sequence voltage polarizing quantity for directional decision |
||||
IN> V2pol Set | 38 | 78 | 5 | 0.5V to 25V step 0.5V |
Setting for the minimum negative sequence voltage polarizing quantity for directional decision | ||||
IN> I2pol Set | 38 | 79 | 0.08 | 24A to 300A step 3A |
Setting for the minimum negative sequence current polarizing quantity for directional Decision | ||||
Earth Fault 3 | 38 | 81 | Enabled | Enabled or Disabled |
P643 and P645 only. Earth Fault 3 | ||||
EF 3 Input | 38 | 82 | Measured | Measured or Derived |
P643 and P645 only. Selects measured neutral current or derived neutral current |
||||
EF 3 Derived | 38 | 83 | P643: T2 P645: T3 | HV Winding, LV Winding, TV Winding, T1, T2, T3, T4 or T5 |
P643 and P645 only. | ||||
EF 3 Measured | 38 | 84 | TN3 | TN1, TN2 or TN3 |
P643 and P645 only. | ||||
IN>1 Status | 38 | 85 | Enabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the first stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden |
||||
IN>1 Char | 38 | 86 | IEC S Inverse | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Tripping characteristic for the first stage earth fault protection |
||||
IN>1 Direction | 38 | 87 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Direction setting for the first stage earth fault protection 3 |
||||
IN>1 Current | 38 | 88 | 0.2*In | 24A to 1200A step 3A |
P643 and P645 only. Pick-up setting for the first stage earth fault element 3 |
||||
IN>1 IDG Is | 38 | 89 | 1.5 | 1 to 4 step 0.1 |
P643 and P645 only. Multiple of IN>1 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts |
||||
IN>1 Time Delay | 38 | 8A | 1 | 0s to 200s step 0.01s |
P643 and P645 only. Operating time delay setting for the first stage definite time element |
||||
IN>1 TMS | 38 | 8B | 1 | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Time multiplier setting to adjust the operating time of the IEC IDMT characteristic |
||||
IN>1 Time Dial | 38 | 8C | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves |
||||
IN>1 K (RI) | 38 | 8D | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Time multiplier to adjust the operating time for the RI curve |
||||
IN>1 IDG Time | 38 | 8E | 1.2 | 1s to 2s step 0.01s |
P643 and P645 only. Minimum operating time at high levels of fault current for the IDG curve |
||||
IN>1 Reset Char | 38 | 8F | DT | DT or Inverse |
P643 and P645 only. Type of reset/release characteristic of the IEEE/US curves |
||||
IN>1 tRESET | 38 | 90 | 0 | 0s to 100s step 0.01s |
P643 and P645 only. Reset/release time setting for definite time reset characteristic |
||||
IN>2 Status | 38 | 95 | Disabled | Enabled or Disabled |
d P645 only. e or disable the second stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden |
||||
IN>2 Char | 38 | 96 | DT | DT (DT), IEC S Inverse (TMS), IEC V Inverse (TMS), IEC E Inverse (TMS), UK LT Inverse (TMS), Rectifier (TMS), RI (K), IEEE M Inverse (TD), IEEE V Inverse (TD), IEEE E Inverse (TD), US Inverse (TD) or US ST Inverse (TD) |
P643 and P645 only. Tripping characteristic for the second stage earth fault protection |
||||
IN>2 Direction | 38 | 97 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Direction setting for the second stage earth fault protection 2 |
||||
IN>2 Current | 38 | 98 | 0.2 | 24A to 1200A step 3A |
P643 and P645 only. Pick-up setting for the second stage earth fault element 2 |
||||
IN>2 IDG Is | 38 | 99 | 1.5 | 1 to 4 step 0.1 |
P643 and P645 only. Multiple of IN>2 setting for the IDG curve (Scandinavia), determines the actual relay current threshold at which the element starts |
||||
IN>2 Time Delay | 38 | 9A | 1 | 0s to 200s step 0.01s |
P643 and P645 only. Operating time delay setting for the second stage definite time element |
||||
IN>2 TMS | 38 | 9B | 1 | 0.025 to 1.2 step 0.005 |
P643 and P645 only. Time multiplier setting to adjust the operating time of the IEC IDMT characteristic |
||||
IN>2 Time Dial | 38 | 9C | 1 | 0.01 to 100 step 0.01 |
P643 and P645 only. Time multiplier setting to adjust the operating time of the IEEE/US IDMT curves |
||||
IN>2 K (RI) | 38 | 9D | 1 | 0.1 to 10 step 0.05 |
P643 and P645 only. Time multiplier to adjust the operating time for the RI curve |
||||
IN>2 IDG Time | 38 | 9E | 1.2 | 1s to 2s step 0.01s |
P643 and P645 only. Minimum operating time at high levels of fault current for the IDG curve |
||||
IN>2 Reset Char | 38 | 9F | DT | DT or Inverse |
P643 and P645 only. Type of reset/release characteristic of the IEEE/US curves |
||||
IN>2 tRESET | 38 | A0 | 0 | 0s to 100s step 0.01s |
P643 and P645 only. Reset/release time setting for definite time reset characteristic |
||||
IN>3 Status | 38 | A5 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the third stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden |
||||
IN>3 Direction | 38 | A6 | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Direction setting for the third stage earth fault protection 3 |
||||
IN>3 Current | 38 | A7 | 0.5 | 24A to 9600A step 3A |
P643 and P645 only. Pick-up setting for the third stage earth fault element 3 |
||||
IN>3 Time Delay | 38 | A8 | 0 | 0s to 200s step 0.01s |
P643 and P645 only. Operating time delay setting for the third stage definite time element |
||||
IN>4 Status | 38 | AC | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the fourth stage definite time element. If the function is disabled, all associated settings with the exception of this setting, are hidden |
||||
IN>4 Direction | 38 | AD | Non-Directional | Non-directional, Directional Fwd or Directional Rev |
P643 and P645 only. Direction setting for the fourth stage TV winding earth fault protection |
||||
IN>4 Current | 38 | AE | 0.5 | 24A to 9600A step 3A |
P643 and P645 only. Pick-up setting for the fourth stage earth fault element on the TV winding |
||||
IN>4 Time Delay | 38 | AF | 0 | 0s to 200s step 0.01s |
P643 and P645 only. Operating time delay setting for the fourth stage definite time element |
||||
IN> Func Link | 38 | B3 | 15 | 4-bit binary setting |
P643 and P645 only. Settings that determine whether VT supervision logic signals block selected earth fault stages. When set to 1, the VTS operation will block the stage if directionalized. When set to 0, the stage will revert to non-directional on the o |
||||
IN> DIRECTIONAL | 38 | B4 | Sub-Heading | Sub-Heading |
P643 and P645 only. | ||||
IN> Char Angle | 38 | B5 | -60 | -95° to 95° step 1° |
P643 and P645 only. Setting for the relay characteristic angle used for the directional decision |
||||
IN> Pol | 38 | B6 | Zero Sequence | Zero sequence or Neg sequence |
P643 and P645 only. Setting that determines whether the directional function uses zero sequence or negative sequence voltage polarizing |
||||
IN> VNpol Set | 38 | B7 | 5 | 0.5V to 80V step 0.5V |
P643 and P645 only. Setting for the minimum zero sequence voltage polarizing quantity for directional decision |
||||
IN> V2pol Set | 38 | B8 | 5 | 0.5V to 25V step 0.5V |
P643 and P645 only. Setting for the minimum negative sequence voltage polarizing quantity for directional decision |
||||
IN> I2pol Set | 38 | B9 | 0.08 | 24A to 300A step 3A |
P643 and P645 only. Setting for the minimum negative sequence current polarizing quantity for directional decision |
||||
Through Fault (TF) Monitoring Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: TF MONITORING |
39 | 00 | ||
This column contains GROUP1: THROUGH FAULT parameters | ||||
Through Fault | 39 | 01 | Enabled | Enabled or Disabled |
Enables or disables monitoring of through faults | ||||
Monitored Input | 39 | 02 | HV | HV, LV, TV or Biased Current |
Selects the input winding to be monitored | ||||
TF I> Trigger | 39 | 03 | 3.85pu | 0.08pu to 20pu step 0.01pu |
A through fault event is recorded if any of the phase currents is larger than this setting | ||||
TF I2t> Alarm | 39 | 04 | 100 pu | 0 to 1600pu step 0.1pu |
An alarm is asserted if the maximum cumulative I2t in the three phases exceeds this setting | ||||
Residual Overvoltage (Neutral Voltage Displacement)
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: RESIDUAL O/V NVD | 3B | 00 | ||
P643 and P645 only. This column contains GROUP 1: RESIDUAL O/V NVD parameters |
||||
VN>1 Function | 3B | 14 | DT | Disabled, DT or IDMT |
P643 and P645 only. Setting for the tripping characteristic of the first stage residual overvoltage element |
||||
VN>1 Voltage Set | 3B | 16 | 5*V1 | 1*V1 to 80*V1 step 1*V1 |
P643 and P645 only. Pick-up setting for the first stage residual overvoltage characteristic |
||||
VN>1 Time Delay | 3B | 18 | 5s | 0 to 100s step 0.01s |
P643 and P645 only. Operating time delay setting for the first stage definite time residual overvoltage element |
||||
VN>1 TMS | 3B | 1A | 1 | 0.5 to 100 step 0.5 |
P643 and P645 only. TMS to adjust the operating time of the IDMT characteristic. The characteristic is defined as follows: t = K / ( M – 1) where: K = TMS t = Operating time in seconds M = Derived residual voltage/relay setting voltage (VN> Voltage Set) |
||||
VN>1 tReset | 3B | 1C | 0s | 0 to 100s step 0.01s |
P643 and P645 only. Setting to determine the reset or release definite time for the first stage characteristic |
||||
VN>2 Status | 3B | 20 | Disabled | Enabled or Disabled |
P643 and P645 only. Setting to enable or disable the second stage definite time residual overvoltage element |
||||
VN>2 Voltage Set | 3B | 26 | 10*V1 | 1*V1 to 80*V1 step 1*V1 |
P643 and P645 only. Pick-up setting for the second stage residual overvoltage element |
||||
VN>2 Time Delay | 3B | 28 | 10s | 0 to 100s step 0.01s |
P643 and P645 only. Operating time delay for the second stage residual overvoltage element |
||||
Overfluxing
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: OVERFLUXING | 3D | 00 | ||
This column contains GROUP 1: OVERFLUXING parameters | ||||
Volts/Hz W1 | 3D | 01 | Sub-Heading | Sub-Heading |
Volts/Hz Overfluxing element W1. P643 and P645 only if the optional three-phase VT is available. |
||||
V/HZ Alm Status | 3D | 02 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the V/Hz alarm element |
||||
V/HZ Alm Set | 3D | 03 | 2.31 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
P643 and P645 only. Pick-up setting for the V/Hz element |
||||
V/Hz Alarm Delay | 3D | 04 | 10s | 0s to 6000s step 0.1s |
P643 and P645 only. Operating time delay setting of the V/Hz alarm element |
||||
V/Hz>1 Status | 3D | 10 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the V/Hz first stage trip element |
||||
V/Hz>1 Function | 3D | 13 | DT | DT or IDMT |
P643 and P645 only. Tripping characteristic setting of the V/Hz first stage trip element |
||||
V/Hz>1 Trip Set | 3D | 16 | 2.42 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
P643 and P645 only. Pick-up setting for the V/Hz first stage trip element |
||||
V/Hz>1 Trip TMS | 3D | 19 | 0.1 | 0.01 to 12 step 0.01 |
P643 and P645 only. Setting for the Time Multiplier Setting (TMS) to adjust the operating time of the IDMT characteristic |
||||
V/Hz>1 Delay | 3D | 1A | 60s | 0s to 6000s step 0.1s |
P643 and P645 only. Operating time-delay setting of the V/Hz first stage trip element |
||||
V/Hz>1 tReset | 3D | 1B | 60s | 0s to 6000s step 0.1s |
P643 and P645 only. Reset function so the user can reset overfluxing after injection testing |
||||
V/Hz>2 Status | 3D | 20 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the V/Hz second stage trip element |
||||
V/Hz>2 Trip Set | 3D | 25 | 2.64 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
P643 and P645 only. Pick-up setting for the V/Hz second stage trip element |
||||
V/Hz>2 Delay | 3D | 2A | 3s | 0s to 6000s step 0.1s |
P643 and P645 only. Operating time delay setting of the V/Hz alarm element |
||||
V/Hz>3 Status | 3D | 30 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the V/Hz third stage trip element |
||||
V/Hz>3 Trip Set | 3D | 35 | 2.86 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
P643 and P645 only. Pick-up setting for the V/Hz third stage trip element |
||||
V/Hz>3 Delay | 3D | 3A | 2.00s | 0s to 6000s step 0.1s |
P643 and P645 only. Operating time delay setting of the V/Hz alarm element |
||||
V/Hz>4 Status | 3D | 40 | Enabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the V/Hz fourth stage trip element |
||||
V/Hz>4 Trip Set | 3D | 45 | 3.08 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
P643 and P645 only. Pick-up setting for the V/Hz fourth stage trip element |
||||
V/Hz>4 Delay | 3D | 4A | 1.00s | 0s to 6000s step 0.1s |
P643 and P645 only. Operating time delay setting of the V/Hz alarm element |
||||
TPre-trip Alarm | 3D | 4F | 200s | 0s to 6000s step 0.1s |
P643 and P645 only. Pre-trip alarm time delay | ||||
Volts/Hz W2 | 3D | 50 | ||
Volts/Hz Overfluxing element W2. | ||||
V/HZ Alm Status | 3D | 51 | Enabled | Enabled or Disabled |
Enables or disables the V/Hz alarm element | ||||
V/HZ Alm Set | 3D | 52 | 2.31 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
Pick-up setting for the V/Hz element | ||||
V/Hz Alarm Delay | 3D | 53 | 10s | 0s to 6000s step 0.1s |
Operating time delay setting of the V/Hz alarm element | ||||
V/Hz>1 Status | 3D | 60 | Enabled | Enabled or Disabled |
Enables or disables the V/Hz first stage trip element | ||||
V/Hz>1 Function | 3D | 63 | DT | DT or IDMT |
Tripping characteristic setting of the V/Hz first stage trip element | ||||
V/Hz>1 Trip Set | 3D | 66 | 2.42 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
Pick-up setting for the V/Hz first stage trip element | ||||
V/Hz>1 Trip TMS | 3D | 69 | 0.1 s | 0.01 to 12 step 0.01 |
Setting for the time multiplier setting to adjust the operating time of the IDMT characteristic. | ||||
V/Hz>1 Delay | 3D | 6A | 60s | 0s to 6000s step 0.1s |
Operating time delay setting of the V/Hz alarm element | ||||
V/Hz>1 tReset | 3D | 6B | 0s | 0s to 6000s step 0.1s |
Reset function so the user can reset overfluxing after injection testing | ||||
V/Hz>2 Status | 3D | 70 | Enabled | Enabled or Disabled |
Enables or disables the V/Hz second stage trip element | ||||
V/Hz>2 Trip Set | 3D | 75 | 2.64 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
Pick-up setting for the V/Hz second stage trip element | ||||
V/Hz>2 Delay | 3D | 7A | 3s | 0s to 6000s step 0.1s |
Operating time delay setting of the V/Hz alarm element | ||||
V/Hz>3 Status | 3D | 80 | Enabled | Enabled or Disabled |
Enables or disables the V/Hz third stage trip element | ||||
V/Hz>3 Trip Set | 3D | 85 | 2.86 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
Pick-up setting for the V/Hz third stage trip element | ||||
V/Hz>3 Delay | 3D | 8A | 2.00s | 0s to 6000s step 0.1s |
Operating time delay setting of the V/Hz alarm element | ||||
V/Hz>4 Status | 3D | 90 | Enabled | Enabled or Disabled |
Enables or disables the V/Hz fourth stage trip element | ||||
V/Hz>4 Trip Set | 3D | 95 | 3.08 V/HZ | 1.5V/Hz to 3.5V/Hz step 0.01V/Hz |
Pick-up setting for the V/Hz fourth stage trip element | ||||
V/Hz>4 Delay | 3D | 9A | 1.00s | 0s to 6000s step 0.1s |
Operating time delay setting of the V/Hz alarm element | ||||
TPre-trip alarm | 3D | 9F | 200s | 0s to 6000s step 0.1s |
Pre-trip alarm time delay | ||||
Voltage Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: VOLT PROTECTION |
42 | 00 | ||
This column contains GROUP 1: VOLT PROTECTION parameters | ||||
UNDER VOLTAGE | 42 | 01 | Sub-Heading | Sub-Heading |
P643 and P645 only. UNDER VOLTAGE | ||||
V< Measur’t Mode | 42 | 02 | Phase-Neutral | Phase-Phase or Phase-Neutral |
P643 and P645 only. Sets the measured input voltage used for the undervoltage elements |
||||
V< Operate Mode | 42 | 03 | Any Phase | Any-Phase or Three-phase |
P643 and P645 only. Determines whether any phase or all three phases must satisfy the undervoltage criteria before a decision is made |
||||
V<1 Function | 42 | 04 | DT | IDMT or DT or Disabled |
P643 and P645 only. Tripping characteristic for the first stage undervoltage function. The characteristic is defined by: t = K / (1 – M) Where: K = TMS t = Operating time in seconds M = Measured voltage/relay setting voltage (V< Voltage Set) |
||||
V<1 Voltage Set | 42 | 05 | 50V | 10V to 120V step 1V |
P643 and P645 only. Sets the pick-up setting for the first stage undervoltage element |
||||
V<1 Time Delay | 42 | 06 | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Sets the operating time-delay for the first stage definite time undervoltage element |
||||
V<1 TMS | 42 | 07 | 1 | 0.05 to 100 step 0.05 |
P643 and P645 only. Sets the time multiplier setting to adjust the operating time of the IEC IDMT characteristic |
||||
V<1 Poledead Inh | 42 | 08 | Enabled | Enabled or Disabled |
P643 and P645 only. If the setting is enabled, the relevant stage is inhibited by the pole dead logic. This logic produces an output when it detects either an open circuit breaker through auxiliary contacts feeding the relay opto inputs, or it detects a combination of both undercurrent and undervoltage on any one phase. It allows the undervoltage protection to reset when the circuit breaker opens to cater for line or bus side VT applications. |
||||
V<2 Status | 42 | 09 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the second stage undervoltage element |
||||
V<2 Voltage Set | 42 | 0A | 38V | 10V to 120V step 1V |
P643 and P645 only. Sets the pick-up setting for the second stage undervoltage element |
||||
V<2 Time Delay | 42 | 0B | 5s | 0s to 100s step 0.01s |
P643 and P645 only. Sets the operating time-delay for the second stage definite time undervoltage element |
||||
V<2 Poledead Inh | 42 | 0C | Enabled | Enabled or Disabled |
P643 and P645 only. This works in the same way as V<1 Poledead Inh but for V<2 Poledead Inh instead. |
||||
OVERVOLTAGE | 42 | 20 | Sub-Heading | Sub-Heading |
P643 and P645 only. OVERVOLTAGE | ||||
V> Measur’t Mode | 42 | 21 | Phase-Phase | Phase-Phase or Phase-Neutral |
P643 and P645 only. Sets the measured input voltage used for the overvoltage elements |
||||
V> Operate Mode | 42 | 22 | Any Phase | Any-Phase or Three-phase |
P643 and P645 only. Determines whether any phase or all three phases must satisfy the overvoltage criteria before a decision is made |
||||
V>1 Function | 42 | 23 | DT | IDMT or DT or Disabled |
P643 and P645 only. Tripping characteristic for the first stage overvoltage function. The characteristic is defined by: t = K / (M – 1) Where: K = TMS t = Operating time in seconds M = Measured voltage/relay setting voltage (V<> Voltage Set) |
||||
V>1 Voltage Set | 42 | 24 | 130V | 60V to 185V step 1V |
P643 and P645 only. Sets the pick-up setting for the first stage overvoltage element |
||||
V>1 Time Delay | 42 | 25 | 10s | 0s to 100s step 0.01s |
P643 and P645 only. Sets the operating time-delay for the first stage definite time overvoltage element |
||||
V>1 TMS | 42 | 26 | 1 | 0.05 to 100 step 0.05 |
P643 and P645 only. Sets the time multiplier to adjust the operating time of the IEC IDMT characteristic |
||||
V>2 Status | 42 | 27 | Disabled | Enabled or Disabled |
P643 and P645 only. Enables or disables the second stage overvoltage element |
||||
V>2 Voltage Set | 42 | 28 | 150V | 60V to 185V step 1V |
P643 and P645 only. Sets the pick-up setting for the second stage overvoltage element |
||||
V>2 Time Delay | 42 | 29 | 0.5 | 0s to 100s step 0.01s |
P643 and P645 only. Sets the operating time-delay for the second stage definite time overvoltage element |
||||
NPS O/V | 42 | 40 | Sub-Heading | Sub-Heading |
Negative phase sequence over voltage | ||||
V2> Status | 42 | 41 | Disabled | Enabled or Disabled |
Enable or disable the NPS OV | ||||
V2> Voltage Set | 42 | 42 | 15V | 1V to 110V step 1V |
Set up the pick up setting for Negative phase sequence over voltage | ||||
V2> Time Delay | 42 | 43 | 5s | 0s to 100s step 0.01s |
Set the operating time delay for the definite time stage | ||||
Frequency Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: FREQ PROTECTION |
43 | 00 | ||
This column contains GROUP 1: FREQ PROTECTION parameters | ||||
UNDER FREQUENCY | 43 | 01 | Sub-Heading | Sub-Heading |
UNDER FREQUENCY | ||||
F<1 Status | 43 | 02 | Enabled | Enabled or Disabled |
Enables or disables the first stage underfrequency element | ||||
F<1 Setting | 43 | 03 | 49.5Hz | 46Hz to 65Hz step 0.01Hz |
Determines the pick-up threshold for the first stage underfrequency element | ||||
F<1 Time Delay | 43 | 04 | 4s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the first stage underfrequency element | ||||
F<2 Status | 43 | 05 | Disabled | Enabled or Disabled |
Enables or disables the second stage underfrequency element | ||||
F<2 Setting | 43 | 06 | 49Hz | 46Hz to 65Hz step 0.01Hz |
Determines the pick-up threshold for the second stage underfrequency element | ||||
F<2 Time Delay | 43 | 07 | 3s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the second stage underfrequency element | ||||
F<3 Status | 43 | 08 | Disabled | Enabled or Disabled |
Enables or disables the third stage underfrequency element | ||||
F<3 Setting | 43 | 09 | 48.5Hz | 46Hz to 65Hz step 0.01Hz |
Determines the pick-up threshold for the third stage underfrequency element | ||||
F<3 Time Delay | 43 | 0A | 2s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the third stage underfrequency element | ||||
F<4 Status | 43 | 0B | Disabled | Enabled or Disabled |
Determines the pick-up threshold for the fourth stage underfrequency element | ||||
F<4 Setting | 43 | 0C | 48Hz | 46Hz to 65Hz step 0.01Hz |
Enables or disables the fourth stage underfrequency element | ||||
F<4 Time Delay | 43 | 0D | 1s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the fourth stage underfrequency element | ||||
OVER FREQUENCY | 43 | 0F | Sub-Heading | Sub-Heading |
OVER FREQUENCY | ||||
F>1 Status | 43 | 10 | Enabled | Enabled or Disabled |
Enables or disables the first stage overfrequency element | ||||
F>1 Setting | 43 | 11 | 50.5Hz | 46Hz to 65Hz step 0.01Hz |
Determines the pick-up threshold for the first stage overfrequency element | ||||
F>1 Time Delay | 43 | 12 | 2s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the first stage overfrequency element | ||||
F>2 Status | 43 | 13 | Disabled | Enabled or Disabled |
Enables or disables the second stage overfrequency element | ||||
F>2 Setting | 43 | 14 | 51Hz | 46Hz to 65Hz step 0.01Hz |
Determines the pick-up threshold for the second stage overfrequency element | ||||
F>2 Time Delay | 43 | 15 | 1s | 0s to 600s step 0.01s |
Determines the minimum operating time-delay for the second stage overfrequency element | ||||
Resistor Temperature Device (RTD) Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: RTD PROT ON |
44 | 00 | ||
This column contains GROUP 1: RTD PROTECTION parameters | ||||
Select RTD | 44 | 01 | 0 | 10-bit binary setting: Bit 0 – Select RTD 1, Bit 1 – Select RTD 2, Bit 2 – Select RTD 3 through to Bit 9 – Select RTD 10 |
10-bit setting to enable or disable the 10 RTDs. For each bit 1 = Enabled, 0 = Disabled | ||||
RTD1 PROTECTION | 44 | 02 | Sub-Heading | Sub-Heading |
RTD1 PROTECTION | ||||
RTD Alarm Set | 44 | 03 | 80°C | 0° to 200°C step 1°C |
Temperature setting for the RTD 1 alarm element | ||||
RTD Alarm Dly | 44 | 04 | 10 s | 0s to 100s step 1s |
Operating time delay setting for the RTD 1 alarm element | ||||
RTD Trip Set | 44 | 05 | 85°C | 0° to 200°C step 1°C |
Operating time delay setting for the RTD 1 alarm element | ||||
RTD Trip Dly | 44 | 06 | 1 s | 0s to 100s step 1s |
Operating time delay setting for the RTD 1 alarm element | ||||
RTD2 PROTECTION | 44 | 07 | Sub-Heading | Sub-Heading |
RTD2 PROTECTION | ||||
RTD Alarm Set | 44 | 08 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 09 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 0A | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 0B | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD3 PROTECTION | 44 | 0C | Sub-Heading | Sub-Heading |
RTD3 PROTECTION | ||||
RTD Alarm Set | 44 | 0D | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 0E | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 0F | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 10 | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD4 PROTECTION | 44 | 11 | Sub-Heading | Sub-Heading |
RTD4 PROTECTION | ||||
RTD Alarm Set | 44 | 12 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 13 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 14 | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 15 | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD5 PROTECTION | 44 | 16 | Sub-Heading | Sub-Heading |
RTD5 PROTECTION | ||||
RTD Alarm Set | 44 | 17 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 18 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 19 | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 1A | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD6 PROTECTION | 44 | 1B | Sub-Heading | Sub-Heading |
RTD6 PROTECTION | ||||
RTD Alarm Set | 44 | 1C | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 1D | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 1E | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 1F | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD7 PROTECTION | 44 | 20 | Sub-Heading | Sub-Heading |
RTD7 PROTECTION | ||||
RTD Alarm Set | 44 | 21 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 22 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 23 | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 24 | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD8 PROTECTION | 44 | 25 | Sub-Heading | Sub-Heading |
RTD8 PROTECTION | ||||
RTD Alarm Set | 44 | 26 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 27 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 28 | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 29 | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD9 PROTECTION | 44 | 2A | Sub-Heading | Sub-Heading |
RTD9 PROTECTION | ||||
RTD Alarm Set | 44 | 2B | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 2C | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 2D | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 2E | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD 10 PROTECTION | 44 | 2F | Sub-Heading | Sub-Heading |
RTD 10 PROTECTION | ||||
RTD Alarm Set | 44 | 30 | 80°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Alarm Dly | 44 | 31 | 10 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Set | 44 | 32 | 85°C | 0° to 200°C step 1°C |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
RTD Trip Dly | 44 | 33 | 1 s | 0s to 100s step 1s |
This setting works in the same way as the RTD 1 alarm element, but for RTD 2 instead | ||||
Circuit Breaker (CB) Failure
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: CB FAIL | 45 | 00 | ||
GROUP 1: CB FAIL | ||||
T1 CBF | 45 | 01 | Disabled | Enabled or Disabled |
BREAKER FAIL for CT1 | ||||
I< Current Set | 45 | 02 | 0.1 | 5% to 400% step 1% |
Set the CT1 under current setting | ||||
IN< Status | 45 | 03 | Disabled | Enabled or Disabled |
Enable or Disabel the IN< | ||||
IN< Input | 45 | 04 | Measured | Measured or Derived |
Set the IN input, derived or measured | ||||
IN< Terminal | 45 | 05 | TN1 | TN1, TN2 or TN3 |
If for IN is measured, set the measured netrual current source | ||||
IN< Current Set | 45 | 06 | 0.1 | 5% to 400% step 1% |
Set IN under current setting | ||||
CB Fail 1 Status | 45 | 07 | Disabled | Enabled or Disabled |
Enables or disables the first stage of the circuit breaker function | ||||
CB Fail 1 Timer | 45 | 08 | 0.05s | 0s to 10s step 0.001s |
Circuit breaker fail timer setting for stage 1, for which the initiating condition must be valid | ||||
CB Fail 2 Status | 45 | 09 | Enabled | Enabled or Disabled |
Enables or disables the second stage of the circuit breaker function | ||||
CB Fail 2 Timer | 45 | 0A | 0.2s | 0s to 10s step 0.001s |
Circuit breaker fail timer setting for stage 2, for which the initiating condition must be valid | ||||
CBF Non I Reset | 45 | 0C | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
Setting which determines the elements that reset the circuit breaker fail time for non current-based protection functions (such as voltage and frequency) initiating circuit breaker fail conditions | ||||
CBF Ext Reset | 45 | 0D | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
Setting which determines the elements that reset the circuit breaker fail time for external protection functions initiating circuit breaker fail conditions | ||||
T2 CBF | 45 | 11 | Disabled | Enabled or Disabled |
I< Current Set | 45 | 12 | 0.1 | 5% to 400% step 1% |
IN< Status | 45 | 13 | Disabled | Enabled or Disabled |
IN< Input | 45 | 14 | Measured | Measured or Derived |
IN< Terminal | 45 | 15 | TN1 | TN1, TN2 or TN3 |
IN< Current Set | 45 | 16 | 0.1 | 5% to 400% step 1% |
CB Fail 1 Status | 45 | 17 | Disabled | Enabled or Disabled |
CB Fail 1 Timer | 45 | 18 | 0.05s | 0s to 10s step 0.001s |
CB Fail 2 Status | 45 | 19 | Enabled | Enabled or Disabled |
CB Fail 2 Timer | 45 | 1A | 0.2s | 0s to 10s step 0.001s |
CBF Non I Reset | 45 | 1C | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
CBF Ext Reset | 45 | 1D | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
T3 CBF | 45 | 21 | Disabled | Enabled or Disabled |
P643 and P645 only. | ||||
I< Current Set | 45 | 22 | 0.1 | 5% to 400% step 1% |
P643 and P645 only. | ||||
IN< Status | 45 | 23 | Disabled | Enabled or Disabled |
P643 and P645 only. | ||||
IN< Input | 45 | 24 | Measured | Measured or Derived |
P643 and P645 only. | ||||
IN< Terminal | 45 | 25 | TN1 | TN1, TN2 or TN3 |
P643 and P645 only. | ||||
IN< Current Set | 45 | 26 | 0.1 | 5% to 400% step 1% |
P643 and P645 only. | ||||
CB Fail 1 Status | 45 | 27 | Disabled | Enabled or Disabled |
P643 and P645 only. | ||||
CB Fail 1 Timer | 45 | 28 | 0.05s | 0s to 10s step 0.001s |
P643 and P645 only. | ||||
CB Fail 2 Status | 45 | 29 | Enabled | Enabled or Disabled |
P643 and P645 only. | ||||
CB Fail 2 Timer | 45 | 2A | 0.2s | 0s to 10s step 0.001s |
P643 and P645 only. | ||||
CBF Non I Reset | 45 | 2C | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P643 and P645 only. | ||||
CBF Ext Reset | 45 | 2D | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P643 and P645 only. | ||||
T4 CBF | 45 | 31 | Disabled | Enabled or Disabled |
P645 only. | ||||
I< Current Set | 45 | 32 | 0.1 | 5% to 400% step 1% |
P645 only. | ||||
IN< Status | 45 | 33 | Disabled | Enabled or Disabled |
P645 only. | ||||
IN< Input | 45 | 34 | Measured | Measured or Derived |
P645 only. | ||||
IN< Terminal | 45 | 35 | TN1 | TN1, TN2 or TN3 |
P645 only. | ||||
IN< Current Set | 45 | 36 | 0.1 | 5% to 400% step 1% |
P645 only. | ||||
CB Fail 1 Status | 45 | 37 | Disabled | Enabled or Disabled |
P645 only. | ||||
CB Fail 1 Timer | 45 | 38 | 0.05s | 0s to 10s step 0.001s |
P645 only. | ||||
CB Fail 2 Status | 45 | 39 | Enabled | Enabled or Disabled |
P645 only. | ||||
CB Fail 2 Timer | 45 | 3A | 0.2s | 0s to 10s step 0.001s |
P645 only. | ||||
CBF Non I Reset | 45 | 3C | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P645 only. | ||||
CBF Ext Reset | 45 | 3D | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P645 only. | ||||
T5 CBF | 45 | 41 | Disabled | Enabled or Disabled |
P645 only. | ||||
I< Current Set | 45 | 42 | 0.1 | 5% to 400% step 1% |
P645 only. | ||||
IN< Status | 45 | 43 | Disabled | Enabled or Disabled |
P645 only. | ||||
IN< Input | 45 | 44 | Measured | Measured or Derived |
P645 only. | ||||
IN< Terminal | 45 | 45 | TN1 | TN1, TN2 or TN3 |
P645 only. | ||||
IN< Current Set | 45 | 46 | 0.1 | 5% to 400% step 1% |
P645 only. | ||||
CB Fail 1 Status | 45 | 47 | Disabled | Enabled or Disabled |
P645 only. | ||||
CB Fail 1 Timer | 45 | 48 | 0.05s | 0s to 10s step 0.001s |
P645 only. | ||||
CB Fail 2 Status | 45 | 49 | Enabled | Enabled or Disabled |
P645 only. | ||||
CB Fail 2 Timer | 45 | 4A | 0.2s | 0s to 10s step 0.001s |
P645 only. | ||||
CBF Non I Reset | 45 | 4C | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P645 only. | ||||
CBF Ext Reset | 45 | 4D | CB Open & I< | I< Only, CB Open & I< or Prot Reset & I |
P645 only. | ||||
VT and CT Supervision
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: SUPERVIS | 46 | 00 | ||
This column contains GROUP 1: SUPERVISION parameters | ||||
VT SUPERVISION | 46 | 01 | Sub-Heading | Sub-Heading |
VT Supervision does not apply to P642 when the optional three-phase VT input is available. Only visible if Main VT is fitted or P642 model with 2 VT inputs. | ||||
VTS Status | 46 | 02 | Indication | Blocking or Indication or Disabled |
Determines whether on detection of
VTS. • VTS logic is Disabled. • VTS alarm is Indication only. • Voltage-dependent protection elements are Blocked. Optional conversion of directional overcurrent to non-directional protection (blocking mode only). |
||||
VTS Reset Mode | 46 | 03 | Manual | Manual or Auto |
VTS block is latched after
user-settable VTS Time Delay. Once latched, the reset methods are: Manual
using the front panel interface (or remote communications). Auto provided VTS condition has been removed and 3-phase voltages have been restored above ph |
||||
VTS Time Delay | 46 | 04 | 5s | 1s to 10s step 0.1s |
Operating time delay setting of the VTS element on detection of a voltage supervision condition. | ||||
VTS I> Inhibit | 46 | 05 | 10 | 0.08pu to 32pu step 0.01pu |
The overcurrent setting inhibits VT
supervision if all 3-phase voltages are lost, due to a close-up 3-phase fault
after CB is closed. In P643, CT1/CT2/CT3 if the VT is in the HV, TV or LV. In P645, CT1/CT3/CT5 if the VT is in HV, TV or LV. |
||||
VTS I2> Inhibit | 46 | 06 | 0.05 | 0.05pu to 0.5pu step 0.01pu |
NPS overcurrent setting inhibits VT
supervision if a fault occurs with excess negative sequence current. In P643,
always referred to CT1/CT2/CT3 if the VT is in the HV, TV or LV. In P645, always referred to CT1/CT3/CT5 if the VT is in HV, TV or LV. |
||||
CT SUPERVISION | 46 | 20 | Sub-Heading | Sub-Heading |
CT Supervision applies to P642, P643, P645 and P746 when the optional CT input is available. | ||||
Diff CTS | 46 | 21 | Enable | Enabled or Disabled |
Enables or disables the CTS function | ||||
CTS Status | 46 | 22 | Restrain | Indication or Restrain |
In Indication mode, the CTS alarm is issued without delay when a CT failure is detected. In restrain mode, the differential protection is desensitised to the Is-CTS setting | ||||
CTS Tdelay | 46 | 23 | 2s | 0s to 10s step 0.1s |
Determines the operating time delay of the element on detection of a current transformer supervision condition | ||||
CTS I1 | 46 | 24 | 0.1 | 5% to 100% step 1% |
Set release threshold | ||||
CTS I2/I1>1 | 46 | 25 | 0.05 | 5% to 100% step 1% |
Low set ratio of negative to positive sequence current | ||||
CTS I2/I1>2 | 46 | 26 | 0.4 | 5% to 100% step 1% |
High set ratio of negative to positive sequence current | ||||
Input Labels
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: INPUT LABELS | 4A | 00 | ||
This column contains GROUP 1: INPUT LABELS parameters | ||||
Opto Input 1 | 4A | 01 | Input L1 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 2 | 4A | 02 | Input L2 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 3 | 4A | 03 | Input L3 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 4 | 4A | 04 | Input L4 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 5 | 4A | 05 | Input L5 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 6 | 4A | 06 | Input L6 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 7 | 4A | 07 | Input L7 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 8 | 4A | 08 | Input L8 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 9 | 4A | 09 | Input L9 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 10 | 4A | 0A | Input L10 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 11 | 4A | 0B | Input L11 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 12 | 4A | 0C | Input L12 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 13 | 4A | 0D | Input L13 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 14 | 4A | 0E | Input L14 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 15 | 4A | 0F | Input L15 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 16 | 4A | 10 | Input L16 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 17 | 4A | 11 | Input L17 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 18 | 4A | 12 | Input L18 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 19 | 4A | 13 | Input L19 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 20 | 4A | 14 | Input L20 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 21 | 4A | 15 | Input L21 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 22 | 4A | 16 | Input L22 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 23 | 4A | 17 | Input L23 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 24 | 4A | 18 | Input L24 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 25 | 4A | 19 | Input L25 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 26 | 4A | 1A | Input L26 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 27 | 4A | 1B | Input L27 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 28 | 4A | 1C | Input L28 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 29 | 4A | 1D | Input L29 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 30 | 4A | 1E | Input L30 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 31 | 4A | 1F | Input L31 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Opto Input 32 | 4A | 20 | Input L32 | 16-character text string (32 to 163) |
Text label to describe each individual opto input | ||||
Output Labels
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: OUTPUT LABELS | 4B | 00 | ||
This column contains GROUP 1: OUTPUT LABELS parameters | ||||
Relay 1 | 4B | 01 | Output R1 Not Used | 16-character text string (32 to 163) |
P642, P643, P645 and P746. Text label to describe each individual relay output contact. This text is displayed in the programmable scheme logic and event record description of the relay output contact |
||||
Relay 2 | 4B | 02 | Output R2 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 3 | 4B | 03 | Output R3 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 4 | 4B | 04 | Output R4 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 5 | 4B | 05 | Output R5 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 6 | 4B | 06 | Output R6 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 7 | 4B | 07 | Output R7 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 8 | 4B | 08 | Output R8 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 9 | 4B | 09 | Output R9 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 10 | 4B | 0A | Output R10 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 11 | 4B | 0B | Output R11 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 12 | 4B | 0C | Output R12 Not Used | 16-character text string (32 to 163) |
This works in the same way as Relay 1. | ||||
Relay 13 | 4B | 0D | Output R13 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. Text label to describe each individual relay output contact. This text is displayed in the programmable scheme logic and event record description of the relay output contact |
||||
Relay 14 | 4B | 0E | Output R14 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 15 | 4B | 0F | Output R15 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 16 | 4B | 10 | Output R16 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 17 | 4B | 11 | Output R17 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 18 | 4B | 12 | Output R18 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 19 | 4B | 13 | Output R19 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 20 | 4B | 14 | Output R20 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 21 | 4B | 15 | Output R21 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 22 | 4B | 16 | Output R22 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 23 | 4B | 17 | Output R23 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 24 | 4B | 18 | Output R24 Not Used | 16-character text string (32 to 163) |
P643, P645 and P746 only. This works in the same way as Relay 12. |
||||
Relay 25 | 4B | 19 | Output R25 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. Text label to describe each individual relay output contact. This text is displayed in the programmable scheme logic and event record description of the relay output contact |
||||
Relay 26 | 4B | 1A | Output R26 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 27 | 4B | 1B | Output R27 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 28 | 4B | 1C | Output R28 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 29 | 4B | 1D | Output R29 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 30 | 4B | 1E | Output R30 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 31 | 4B | 1F | Output R31 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
Relay 32 | 4B | 20 | Output R32 Not Used | 16-character text string (32 to 163) |
P645 and P746 only. This works in the same way as Relay 19. |
||||
RTD Labels
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: RTD LABE | 4C | 00 | ||
This column contains GROUP 1: RTD LABELS parameters | ||||
RTD 1 | 4C | 01 | RTD 1 | 16-character text string (32 to 163) |
Text label to describe each individual RTD. This text is displayed in the Measurements 3 menu and fault records for the description of the RTDs. | ||||
RTD 2 | 4C | 02 | RTD 2 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 3 | 4C | 03 | RTD 3 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 4 | 4C | 04 | RTD 4 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 5 | 4C | 05 | RTD 5 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 6 | 4C | 06 | RTD 6 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 7 | 4C | 07 | RTD 7 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 8 | 4C | 08 | RTD 8 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 9 | 4C | 09 | RTD 9 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
RTD 10 | 4C | 0A | RTD 10 | 16-character text string (32 to 163) |
This works in the same way as RTD 1. | ||||
Current Loop Inputs and Outputs (CLIO) Protection
Menu Text | Row | Col | Default Setting | Available Setting |
Description | ||||
GROUP 1: CLIO PROTECTION |
4D | 00 | ||
This column contains GROUP 1: CLIO PROTECTION parameters | ||||
CLI1 PROTECTION | 4D | 01 | Sub-Heading | Sub-Heading |
CLI1 PROTECTION | ||||
CLI Input Status | 4D | 02 | Enabled | Enabled or Disabled |
Enables or disables the current loop (transducer) input 1 element | ||||
CLI Input Type | 4D | 04 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 input type | ||||
CLI Input Label | 4D | 06 | CLIO Input 1 | 16-character text string (32 to 163) |
Current loop 1 input description. The minimum and maximum settings define the range but they have no units. The user can use the label to enter the transducer function and unit of measurement | ||||
CLI Minimum | 4D | 08 | 0 | -9999 to 9999 step 0.1 |
Current loop input 1 minimum setting. Defines the lower range of the physical or electrical quantity measured by the transducer | ||||
CLI Maximum | 4D | 0A | 100 | -9999 to 9999 step 0.1 |
Current loop input 1 maximum setting. Defines the upper range of the physical or electrical quantity measured by the transducer | ||||
CLI Alarm | 4D | 0C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 alarm element | ||||
CLI Alarm Fn | 4D | 0E | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Alarm Set | 4D | 10 | 50 | From "MIN(CLI1Min, Max)" to "MAX(CLI1Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 alarm element | ||||
CLI Alarm Delay | 4D | 12 | 1 | 0s to 100s step 0.1s |
Operating time-delay setting of current loop input 1 alarm element | ||||
CLI Trip | 4D | 14 | Disabled | Enabled or Disabled |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Fn | 4D | 16 | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Trip Set | 4D | 18 | 60 | LI1Min, Max)" to "MAX(CLI1Min, tep 0.1 |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Delay | 4D | 1A | 0 | 0s to 100s step 0.1s |
Operating mode of the current loop input 1 trip element | ||||
CLI I< Alarm | 4D | 1C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 undercurrent element used to supervise the 4-20 mA input only | ||||
CLI I< Alm Set | 4D | 1E | 0.0035 | 0mA to 4mA step 0.1mA |
Pick-up setting for the current loop input 1 undercurrent element. (4 – 20 mA input only) | ||||
CLI2 PROTECTION | 4D | 21 | Sub-Heading | Sub-Heading |
CLI2 PROTECTION | ||||
CLI Input Status | 4D | 22 | Enabled | Enabled or Disabled |
Enables or disables the current loop (transducer) input 1 element | ||||
CLI Input Type | 4D | 24 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 input type | ||||
CLI Input Label | 4D | 26 | CLIO Input 2 | 16-character text string (32 to 163) |
Current loop 1 input description. The minimum and maximum settings define the range but they have no units. The user can use the label to enter the transducer function and unit of measurement | ||||
CLI Minimum | 4D | 28 | 0 | -9999 to 9999 step 0.1 |
Current loop input 1 minimum setting. Defines the lower range of the physical or electrical quantity measured by the transducer | ||||
CLI Maximum | 4D | 2A | 100 | -9999 to 9999 step 0.1 |
Current loop input 1 maximum setting. Defines the upper range of the physical or electrical quantity measured by the transducer | ||||
CLI Alarm | 4D | 2C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 alarm element | ||||
CLI Alarm Fn | 4D | 2E | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Alarm Set | 4D | 30 | 50 | From "MIN(CLI2Min, Max)" to "MAX(CLI2Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 alarm element | ||||
CLI Alarm Delay | 4D | 32 | 1s | 0s to 100s step 0.1s |
Operating time-delay setting of current loop input 1 alarm element | ||||
CLI Trip | 4D | 34 | Disabled | Enabled or Disabled |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Fn | 4D | 36 | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Trip Set | 4D | 38 | 60 | From "MIN(CLI2Min, Max)" to "MAX(CLI2Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Delay | 4D | 3A | 0s | 0s to 100s step 0.1s |
Operating mode of the current loop input 1 trip element | ||||
CLI I< Alarm | 4D | 3C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 undercurrent element used to supervise the 4-20 mA input only | ||||
CLI I< Alm Set | 4D | 3E | 0.0035 | 0mA to 4mA step 0.1mA |
Pick-up setting for the current loop input 1 undercurrent element. (4 – 20 mA input only) | ||||
CLI3 PROTECTION | 4D | 41 | Sub-Heading | Sub-Heading |
CLI3 PROTECTION | ||||
CLI Input Status | 4D | 42 | Enabled | Enabled or Disabled |
Enables or disables the current loop (transducer) input 1 element | ||||
CLI Input Type | 4D | 44 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 input type | ||||
CLI Input Label | 4D | 46 | CLIO Input 3 | 16-character text string (32 to 163) |
Current loop 1 input description. The minimum and maximum settings define the range but they have no units. The user can use the label to enter the transducer function and unit of measurement | ||||
CLI Minimum | 4D | 48 | 0 | -9999 to 9999 step 0.1 |
Current loop input 1 minimum setting. Defines the lower range of the physical or electrical quantity measured by the transducer | ||||
CLI Maximum | 4D | 4A | 100 | -9999 to 9999 step 0.1 |
Current loop input 1 maximum setting. Defines the upper range of the physical or electrical quantity measured by the transducer | ||||
CLI Alarm | 4D | 4C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 alarm element | ||||
CLI Alarm Fn | 4D | 4E | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Alarm Set | 4D | 50 | 50 | From "MIN(CLI3Min, Max)" to "MAX(CLI3Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 alarm element | ||||
CLI Alarm Delay | 4D | 52 | 1s | 0s to 100s step 0.1s |
Operating time-delay setting of current loop input 1 alarm element | ||||
CLI Trip | 4D | 54 | Disabled | Enabled or Disabled |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Fn | 4D | 56 | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Trip Set | 4D | 58 | 60 | From "MIN(CLI3Min, Max)" to "MAX(CLI3Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Delay | 4D | 5A | 0s | 0s to 100s step 0.1s |
Operating mode of the current loop input 1 trip element | ||||
CLI I< Alarm | 4D | 5C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 undercurrent element used to supervise the 4-20 mA input only | ||||
CLI I< Alm Set | 4D | 5E | 0.0035 | 0mA to 4mA step 0.1mA |
Pick-up setting for the current loop input 1 undercurrent element. (4 – 20 mA input only) | ||||
CLI4 PROTECTION | 4D | 61 | Sub-Heading | Sub-Heading |
CLI4 PROTECTION | ||||
CLI Input Status | 4D | 62 | Enabled | Enabled or Disabled |
Enables or disables the current loop (transducer) input 1 element | ||||
CLI Input Type | 4D | 64 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 input type | ||||
CLI Input Label | 4D | 66 | CLIO Input 4 | 16-character text string (32 to 163) |
Current loop 1 input description. The minimum and maximum settings define the range but they have no units. The user can use the label to enter the transducer function and unit of measurement | ||||
CLI Minimum | 4D | 68 | 0 | -9999 to 9999 step 0.1 |
Current loop input 1 minimum setting. Defines the lower range of the physical or electrical quantity measured by the transducer | ||||
CLI Maximum | 4D | 6A | 100 | -9999 to 9999 step 0.1 |
Current loop input 1 maximum setting. Defines the upper range of the physical or electrical quantity measured by the transducer | ||||
CLI Alarm | 4D | 6C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 alarm element | ||||
CLI Alarm Fn | 4D | 6E | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Alarm Set | 4D | 70 | 50 | From "MIN(CLI4Min, Max)" to "MAX(CLI4Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 alarm element | ||||
CLI Alarm Delay | 4D | 72 | 1s | 0s to 100s step 0.1s |
Operating time-delay setting of current loop input 1 alarm element | ||||
CLI Trip | 4D | 74 | Disabled | Enabled or Disabled |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Fn | 4D | 76 | Over | Over or Under |
Operating mode of the current loop input 1 alarm element | ||||
CLI Trip Set | 4D | 78 | 60 | From "MIN(CLI4Min, Max)" to "MAX(CLI4Min, Max))" step 0.1 |
Pick-up setting for the current loop input 1 trip element | ||||
CLI Trip Delay | 4D | 7A | 0s | 0s to 100s step 0.1s |
Operating mode of the current loop input 1 trip element | ||||
CLI I< Alarm | 4D | 7C | Disabled | Enabled or Disabled |
Enables or disables the current loop input 1 undercurrent element used to supervise the 4-20 mA input only | ||||
CLI I< Alm Set | 4D | 7E | 0.0035 | 0mA to 4mA step 0.1mA |
Pick-up setting for the current loop input 1 undercurrent element. (4 – 20 mA input only) | ||||
CLO OUTPUT1 | 4D | 9F | Sub-Heading | Sub-Heading |
CLO OUTPUT1 | ||||
CLO Status | 4D | A0 | Disabled | Enabled or Disabled |
Enable or disables the current loop (transducer) output 1 element | ||||
CLO Type | 4D | A2 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 output type | ||||
CLO Set Values | 4D | A4 | Primary | Primary or Secondary |
This setting controls if the measured values from current loop output 1 are Primary or Secondary values | ||||
CLO Parameter | 4D | A6 | IA Magnitude | See CLIO measurement table |
This setting defines the measured quantity assigned to current loop output 1 | ||||
CLO Minimum | 4D | A8 | See G155 table | See CLIO measurement table |
Current loop output 1 minimum setting. Defines the lower range of the measurement | ||||
CLO Maximum | 4D | AA | See G155 table | See CLIO measurement table |
Current loop output 1 maximum setting. Defines the upper range of the measurement | ||||
CLO OUTPUT2 | 4D | AF | Sub-Heading | Sub-Heading |
CLO OUTPUT2 | ||||
CLO Status | 4D | B0 | Disabled | Enabled or Disabled |
Enable or disables the current loop (transducer) output 1 element | ||||
CLO Type | 4D | B2 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 output type | ||||
CLO Set Values | 4D | B4 | Primary | Primary or Secondary |
This setting controls if the measured values from current loop output 1 are Primary or Secondary values | ||||
CLO Parameter | 4D | B6 | IB Magnitude | See CLIO measurement table |
This setting defines the measured quantity assigned to current loop output 1 | ||||
CLO Minimum | 4D | B8 | See G155 table | See CLIO measurement table |
Current loop output 1 minimum setting. Defines the lower range of the measurement | ||||
CLO Maximum | 4D | BA | See G155 table | See CLIO measurement table |
Current loop output 1 maximum setting. Defines the upper range of the measurement | ||||
CLO OUTPUT3 | 4D | BF | Sub-Heading | Sub-Heading |
CLO OUTPUT3 | ||||
CLO Status | 4D | C0 | Disabled | Enabled or Disabled |
Enable or disables the current loop (transducer) output 1 element | ||||
CLO Type | 4D | C2 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 output type | ||||
CLO Set Values | 4D | C4 | Primary | Primary or Secondary |
This setting controls if the measured values from current loop output 1 are Primary or Secondary values | ||||
CLO Parameter | 4D | C6 | IC Magnitude | See CLIO measurement table |
This setting defines the measured quantity assigned to current loop output 1 | ||||
CLO Minimum | 4D | C8 | See G155 Table | See CLIO measurement table |
Current loop output 1 minimum setting. Defines the lower range of the measurement | ||||
CLO Maximum | 4D | CA | See G155 Table | See CLIO measurement table |
Current loop output 1 maximum setting. Defines the upper range of the measurement | ||||
CLO OUTPUT4 | 4D | CF | Sub-Heading | Sub-Heading |
CLO OUTPUT4 | ||||
CLO Status | 4D | D0 | Disabled | Enabled or Disabled |
Enable or disables the current loop (transducer) output 1 element | ||||
CLO Type | 4D | D2 | 4-20mA | 0 to 1mA, 0 to 10mA, 0 to 20mA or 4 to 20mA |
Current loop 1 output type | ||||
CLO Set Values | 4D | D4 | Primary | Primary or Secondary |
This setting controls if the measured values from current loop output 1 are Primary or Secondary values | ||||
CLO Parameter | 4D | D6 | IN Measured Mag | See CLIO measurement table |
This setting defines the measured quantity assigned to current loop output 1 | ||||
CLO Parameter | 4D | D6 | IN Derived Mag | See CLIO measurement table |
P642 only. This setting defines the measured quantity assigned to current loop output 1 |
||||
CLO Minimum | 4D | D8 | See G155 Table | See CLIO measurement table |
Current loop output 1 minimum setting. Defines the lower range of the measurement | ||||
CLO Maximum | 4D | DA | See G155 Table | See CLIO measurement table |
Current loop output 1 maximum setting. Defines the upper range of the measurement | ||||