Table of Contents

Schneider / Easergy MiCOM P44x M/Nd7 setting parameters & highlights (SC5011)

Table of Contents

Overview

Easergy MiCOM P44x provides high speed and high performance distance protection for all overhead lines and cable applications and offers a comprehensive range of protection functions as standard.

This post covers the specific versions of the MiCOM P44x (P442 & P444) products with:

  • Hardware suffix: M
  • Software sufix: E3

For more detailed information on “Easergy MiCOM P44x” relays, refer to Schneider protection relays manuals.

To see other supported devices, click here.


Configuration settings

Col Row Courier Text Default Setting Available Setting
Description
09 00 CONFIGURATION    
This column contains all the general configuration options
09 01 Restore Defaults No Operation 0 = No Operation, 1 = All Settings, 2 = Setting Group 1, 3 = Setting Group 2, 4 = Setting Group 3, 5 = Setting Group 4
Setting to restore a setting group to factory default settings.
To restore the default values to the settings in any Group settings, set the ’restore defaults’ cell to the relevant Group number. Alternatively it is possible to set the ’restore defaults’ cell to ’all settings’ to restore the default values to all of the IED’s settings, not just the Group settings.
The default settings will initially be placed in the scratchpad and will only be used by the IED after they have been confirmed by the user.
Note: Restoring defaults to all settings includes the rear communication port settings, which may result in communication via the rear port being disrupted if the new (default) settings do not match those of the master station.
09 02 Setting Group Select via Menu 0 = Select via Menu or 1 = Select via Opto
Allows setting group changes to be initiated via Opto Input or via Menu
09 03 Active Settings Group 1 0 = Group 1, 1 = Group 2, 2 = Group 3, 3 = Group 4
Selects the active setting group.
09 04 Save Changes No Operation 0 = No Operation, 1 = Save, 2 = Abort
Saves all IED settings.
09 05 Copy From Group 1 0 = Group 1, 1 = Group 2, 2 = Group 3, 3 = Group 4
Allows displayed settings to be copied from a selected setting group
09 06 Copy to No Operation 0 = No Operation, 1 = Group 1, 2 = Group 2, 3 = Group 3
Allows displayed settings to be copied to a selected setting group
09 07 Setting Group 1 Enabled 0 = Disabled or 1 = Enabled
Enables or disables Group 1 settings. If the setting is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting.
09 08 Setting Group 2 Enabled 0 = Disabled or 1 = Enabled
Enables or disables Group 2 settings. If the setting is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting.
09 09 Setting Group 3 Enabled 0 = Disabled or 1 = Enabled
Enables or disables Group 3 settings. If the setting is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting.
09 0A Setting Group 4 Enabled 0 = Disabled or 1 = Enabled
Enables or disables Group 4 settings. If the setting is disabled from the configuration, then all associated settings and signals are hidden, with the exception of this setting.
09 0D Dist. Protection Enabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Distance Protection function.
09 10 Power-Swing Enabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Power-Swing function.
09 11 Back-up I> Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Backup I> Protection function.
09 12 Neg Sequence O/C Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Negative Sequence Overcurrent Protection function. I2> stages: ANSI 46/67
09 13 Broken Conductor Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Broken Conductor function. I2/I1> stage: ANSI 46
09 14 Earth Fault PROT Disabled 0 = Disabled or 1 = Earth Fault O/C or 2 = Zero Seq. Power
To enable (activate) or disable (turn off) the back up Earth Fault Protection function. IN >stages: ANSI 50N/51N/67N
09 15 Aided D.E.F Enabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Aided D.E.F Protection function.
09 16 Volt Protection Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Voltage Protection (under/overvoltage/remote) function. V<, V> stages: ANSI 27/59
09 17 CB Fail & I< Enabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Circuit Breaker Fail Protection function: ANSI 50BF.
09 18 Supervision Enabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Supervision (VTS & CTS) functions: ANSI 47/27/46.
09 19 System Checks Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the System Checks (Check Sync. and Voltage Monitor) function: ANSI 25.
09 1A Thermal Overload Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Thermal Overload Protection function. ANSI 49.
09 1C I< Protection Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the I< Protection function.
09 1D Residual O/V NVD Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Residual Over Voltage Protection function.
09 1E Freq Protection Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Frequency Protection function.
09 24 Internal A/R Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) the Internal Autoreclose function.
09 25 Input Labels Visible 0 = Invisible, 1 = Visible
Sets the Input Labels menu visible further on in the IED setting menu.
09 26 Output Labels Visible 0 = Invisible, 1 = Visible
Sets the Output Labels menu visible further on in the IED setting menu.
09 28 CT & VT Ratios Visible 0 = Invisible, 1 = Visible
Sets the Current & Voltage Transformer Ratios menu visible further on in the IED settings menu.
09 29 Record Control Visible 0 = Invisible, 1 = Visible
Sets the Record Control menu visible further on in the IED settings menu.
09 2A Disturb Recorder Visible 0 = Invisible, 1 = Visible
Sets the Disturbance Recorder menu visible further on in the IED settings menu.
09 2B Measure’t Setup Visible 0 = Invisible, 1 = Visible
Sets the Measurement Setup menu visible further on in the IED settings menu.
09 2C Comms Settings Visible 0 = Invisible, 1 = Visible
Sets the Communications Settings menu visible further on in the IED settings menu. These are the settings associated with the 1st and 2nd rear communications ports
09 2D Commission Tests Invisible 0 = Invisible, 1 = Visible
Sets the Commissioning Tests menu visible further on in the IED settings menu.
09 2E Setting Values Secondary 0 = Primary, 1 = Secondary
This affects all protection settings that are dependent upon CT and VT ratios. All subsequent settings input must be based in terms of this reference.
09 2F Control Inputs Visible 0 = Invisible, 1 = Visible
Activates the Control Input status and operation menu further on in the IED setting menu.
09 35 Ctrl I/P Config Visible 0 = Invisible, 1 = Visible
Sets the Control Input Configuration menu visible further on in the IED setting menu.
09 36 Ctrl I/P Labels Visible 0 = Invisible, 1 = Visible
Sets the Control Input Labels menu visible further on in the IED setting menu.
09 39 Direct Access Enabled 0 = Disabled or 1 = Enabled
Defines whether direct access is allowed or not. The front direct access keys that are used as a short cut function of the menu may be:
Disabled – No function visible on the LCD.
Enabled – All control functions mapped to the Hotkeys and Control Trip/Close are available. Not available on Chinese version relays.
09 40 InterMicom Disabled 0 = Disabled or 1 = Enabled
To enable (activate) or disable (turn off) InterMiCOM.
09 48 PB CONFIG Visible 0 = Invisible, 1 = Visible
Sets the PB CONFIG menu visible in the relay setting menu.
09 50 Function Key Visible 0 = Invisible, 1 = Visible
Sets the Function Key menu visible further on in the IED setting menu.
09 70 VIR I/P Labels Invisible 0 = Invisible, 1 = Visible
This makes the virtual inputs label settings visible or invisible.
09 80 VIR O/P Labels Invisible 0 = Invisible, 1 = Visible
This makes the virtual outputs label settings visible or invisible.
09 90 Usr Alarm Labels Invisible 0 = Invisible, 1 = Visible
This makes the user alarm labels settings visible or invisible.
09 FB RP1 Read Only Disabled 0 = Disabled or 1 = Enabled
Enable Remote Read Only Mode on RP1 courier or IEC60870-5-103 communication protocol.
Visible when comms options are: 1 – Courier, 3 – CS103, 6&G – IEC61850 with 1st Rear Courier, 7&H – IEC61850 with 1st Rear CS103.
09 FC RP2 Read Only Disabled 0 = Disabled or 1 = Enabled
Enable Remote Read Only Mode on RP2 courier communication protocol. Visible when hardware options are: 7, 8, E or F.
09 FD NIC Read Only Disabled 0 = Disabled or 1 = Enabled
Enable Remote Read Only Mode on the Network Interface card (IEC 61850 tunneled courier).
Visible when comms options are: 6&G – IEC61850 with 1st Rear Courier, 7&H – IEC61850 with 1st Rear CS103, B&L- IEC61850 with DNPoE with DNP .
09 FE SettingValueBeh. Independent 0 = Independent, 1 = Locked Mode
When [09FE] = Independent, the IED will behave as original design. That means, [092E] Setting Values is independent for each interfaces
09 FF LCD Contrast 11 0 to 31 (step 1)
Sets the LCD contrast.

Distance Zone Settings

Col Row Courier Text Default Setting Available Setting
Description
30 00 GROUP 1: DISTANCE ELEMENT    
GROUP1: Distance Elements
30 01 Line setting    
Set the parameters for Protected Line in the following settings
30 02 Line Length 100km From 0.3km to 1000km step 10m
Setting of the protected line/cable length in km or in miles. This setting is available if MEASURE’T SETUP column is selected as ’Visible’ in the CONFIGURATION column. The unit (km or miles) depends on the ’Distance unit’ setting in the MEASURE’T SETUP column.
30 03 Line Length 62mi From 0.2mi to 625mi step 0.005mi
Setting of the protected line/cable length in km or in miles. This setting is available if MEASURE’T SETUP column is selected as ’Visible’ in the CONFIGURATION column. The unit (km or miles) depends on the ’Distance unit’ setting in the MEASURE’T SETUP column.
30 04 Line Impedance 12Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Setting for protected line/cable positive sequence impedance in either primary or secondary terms, depending on the “Setting Values” reference chosen in the CONFIGURATION column. The set value is used for Fault locator, and for all distance zone reaches calculation if ’Simple’ setting mode under “GROUP x LINE PARAMETERS” is selected. This line parameter can be set in polar or rectangular form (see section P44x/EN AP for a complete description)
30 05 Line Angle 70° From -90° to 90° step 0.1°
Setting of the line angle (line positive sequence impedance angle). This setting can be set in polar or rectangular form (see section P44x/EN AP).
30 06 Zone Setting    
Set the parameters for Protected Zone in the following settings
30 07 Zone Status 110110(bin) Bit 00 (last digit)=Z1X enabled Bit 01=Z2 enabled Bit 02=Zp enabled Bit 03=Zq enabled Bit 04=Z3 enabled Bit 05 (first digit)=Z4 enabled
Zone Status: Distance protection zones can be enabled or disabled individually. Setting the relevant bit to 1 will enable the zone. Zone 1 should be always enabled. The other zones should be enabled when required (for use in channel aided schemes).
If Z3 is disabled, the forward limit element becomes the smaller zone (Zp if selected forward)
If Z3 & Zp Fwd are disabled, the forward limit element becomes Z2 If Z3 & Zp Fwd & Z2 are disabled, the forward limit element becomes Z1
If Z4 is disabled, the directional limit for the fordward zone is 30°. Z4 is always reverse.
The following settings are displayed when the relevant zone is enabled. See P44x/EN AP for complete description and calculation for these elements.
30 08 kZ1 Res Comp 1 0 to 7 step 0.001
Zone 1 compensation (KZ1 residual compensation and kZ1 angle, refer to section P44x/EN AP for zone setting
30 09 kZ1 Angle From -180° to 180° step 0.1°
Zone 1 compensation (KZ1 residual compensation and kZ1 angle, refer to section P44x/EN AP for zone setting
30 0A Z1 10Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone 1 impedance setting.
30 0B Z1X 15Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Z1X impedance setting for Z1 extension schemes.
30 0C R1G 10Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R1G: Resistive reach (Earth fault element, refer to P44x/EN AP for resistive reach calculation (earth and phase) setting)
30 0D R1Ph 10Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R1Ph: Resistive reach (phase fault element, refer to P44x/EN AP for resistive reach calculation (earth and phase) settings).
30 0E tZ1 0s From 0 to 10 step 2ms
Zone 1 time delay (TZ1): Zone 1 time delay setting (refer to P44x/EN AP for setting).
30 0F kZ2 Res Comp 1 0 to 7 step 0.001
Zone 2 compensation (KZ2 residual compensation and kZ2 angle, refer to section P44x/EN AP for zone setting
30 10 kZ2 Angle From -180° to 180° step 0.1°
Zone 2 compensation (KZ2 residual compensation and kZ2 angle) setting.
30 11 Z2 20Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone 2 impedance setting.
30 12 R2G 20Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R2G: resistive reach – Earth fault element setting for zone 2.
30 13 R2Ph 20Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R2Ph: Resistive reach – phase fault elements setting for zone 2.
30 14 tZ2 200ms From 0s to 10s step 10ms
Zone 2 time delay (TZ2) setting.
30 15 kZ3/4 Res Comp 1 0 to 7 step 0.001
Zone 3/4 compensation (KZ3/4 residual compensation and kZ3/4 angle, refer to section P44x/EN AP for zone setting
30 16 kZ3/4 Angle From -180° to 180° step 0.1°
Zone 3 and 4 compensations (KZ3/4 residual compensation and kZ3/4 angle) setting.
30 17 Z3 30Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone 3 impedance setting.
30 18 R3G – R4G 30Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R3G – R4G: Resistive reach – Earth fault elements setting for zones 3 and 4.
30 19 R3Ph – R4Ph 30Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
R3Ph – R4Ph: resistive reach – Phase fault elements setting for zones 3 and 4.
30 1A tZ3 600ms From 0s to 10s step 10ms
Zone 3 time delay (TZ3) setting.
30 1B Z4 40Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone 4 impedance setting.
30 1C tZ4 1s From 0s to 10s step 10ms
Zone 4 time delay (TZ4) setting.
30 1D ZoneP – Direct Directional FWD Directional FWD, Directional REV
Zone P direction setting.
30 1E kZp Res Comp 1 0 to 7 step 0.001
Zone p compensation (KZp residual compensation and kZp angle, refer to section P44x/EN AP for zone setting
30 1F kZp Angle From -180° to 180° step 0.1°
Zone P compensation (KZp residual compensation and kZp angle).
30 20 Zp 25Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone p impedance setting.
30 21 RpG 25Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
RpG: Resistive reach – Earth fault element for zone P.
30 22 RpPh 25Ω From 0/In Ω to 400/In Ω step 0.01/In Ω
RpPh: Resistive reach – phase fault element for zone p.
30 23 tZp 400ms From 0s to 10s step 10ms
Zone P time delay (TZp)
30 24 ZoneQ – Direct Directional FWD Directional FWD, Directional REV
Zone q is a further distance zone. It can be faster or slower than any other zone (except zone 1), and it can be in either direction. The only constraint is that it must be inside the overall Z3/Z4 start-up zone.
30 25 kZq Res Comp 1 0 to 7 step 0.001
Zone q compensation (KZq residual compensation and kZq angle, refer to section P44x/EN AP for zone setting
30 26 kZq Angle From -180° to 180° step 0.1°
Zone Q compensation (KZq residual compensation and kZq angle)
30 27 Zq 27Ω From 0.001/In Ω to 500/In Ω step 0.001/In Ω
Zone q impedance setting.
30 28 RqG 27 From 0/In Ω to 400/In Ω step 0.01/In Ω
RqG: Resistive reach – Earth fault element for zone Q.
30 29 RqPh 27 From 0/In Ω to 400/In Ω step 0.01/In Ω
RqPh: Resistive reach – phase fault element for zone Q.
30 2A tZq 500ms From 0s to 10s step 10ms
Zone Q time delay (TZq)
30 2B Other Parameters    
The other parameters are configured in the following configuration.
30 2C Series Cmp. Line Disabled Enabled or Disabled
Series Compensated Line: If enabled, the Directional Line used in the Delta Algorithms is set at 90° (Fwd = Quad1&4 / Rev = Quad 2&3). If disabled, the Directional Line of the Delta algorithms is set at -30° like conventional algorithms
30 2D Overlap Z Mode Disabled Enabled or Disabled
Overlap Z Mode: If enabled, the zones overlap so a fault in Z1 will also be a Z2/Zp/Z3 start (or trip if not cleared) in LCD/Events/Drec – The internal logic is not modified
30 2E Z1m Tilt Angle From -45° to 45° step 1°
The settings dealing with the tilt (’Z1m Tilt Angle’, ’Z1p Tilt Angle’, ’Z2p/Zp/Zq Tilt Angle’) and the evolving forward zone detection to zone1 (to avoid a Z1 detection in case of impedance locus getting out from the quad, due to remote CB operating) but crossing the Z1 before being out from the quad (with enough points that a Z1 decision) can be confirmed if that timer has been set to 0ms.
Z1m and Z1p Tilt Angle: The tilt angles can be independently set (±45°) for phase-to-ground and phase-to-phase setting.
30 2F Z1p Tilt Angle From -45° to 45° step 1°
The settings dealing with the tilt (’Z1m Tilt Angle’, ’Z1p Tilt Angle’, ’Z2p/Zp/Zq Tilt Angle’) and the evolving forward zone detection to zone1 (to avoid a Z1 detection in case of impedance locus getting out from the quad, due to remote CB operating) but crossing the Z1 before being out from the quad (with enough points that a Z1 decision) can be confirmed if that timer has been set to 0ms.
Z1m and Z1p Tilt Angle: The tilt angles can be independently set (±45°) for phase-to-ground and phase-to-phase setting.
30 30 Z2/p/q Tilt Angl From -45° to 45° step 1°
Tilt characteristic for zone 2, zone P and zone Q (common setting for phase-to-ground and phase-to-phase).
30 31 Fwd Z Chg. Delay 30ms From 0s to 100ms step 10ms
This time delay is set to prevent maloperation due to zone evolution from zone n to zone n-1 by CB operation.
30 32 V Mem Validity 10s From 0s to 10s step 10ms
The duration of the voltage memory availability after fault detection can be set. When the voltage memory is declared unavailable (e.g. the V Mem Validity set duration has expired, SOTF Mode, no healthy network to record memory voltage), other polarizing quantities can be considered. These include zero, negative and positive sequence (if voltage is sufficient). Otherwise directional decision is forced to forward.
30 33 Earth I Detect. 0.05*I1 0*I1 to 0.1*I1 step 0.01*I1
The residual current threshold (Earth I Detect.) is used by the conventional algorithm to detect earth faults.
30 34 Smart Zone 0.15 From 0% to 100% step 1%
Sets the ratio “smart zone impedance / load impedance limit Z3/Z4”. If Z3/Z4 impedance exceeds this limit (for more than 20 ms) an alarm is raised.
30 40 Fault Locator    
Fault localtor setting
30 41 kZm Mutual Comp 0 0 to 7 step 0.01
Zone m compensation (KZm residual compensation)
30 42 kZm Angle step 0.1°
Zone m compensation (kZm angle)
30 43 Busbar isolation mode    
 
30 44 Busbar isol.Mode Disabled Enabled or Disabled
Enables or disables Busbar Isolation. ‘Enabled’ setting forces busbar isolation (e.g. for maintenance). In this case, all zones are symmetric, tripping mode is only a 3-pole trip and no scheme logic is used

Distance Protection Schemes

Col Row Courier Text Default Setting Available Setting
Description
31 00 GROUP 1: DISTANCE SCHEMES    
GROUP1: Distance Schemes
31 01 Program Mode Standard Scheme Standard Scheme Open Scheme
The ’Program Mode’ cell is used to select the standard program mode or open program mode. When Standard program mode is set, a standard basis scheme is selectable.
When a scheme is not covered in the Standard modes, the open programming mode can be selected. The user then has the facility to decide which distance relay zone is to be used to program the signalling channel, and what type of aided scheme runs when the channel is received. The signal send zone options, and the aided scheme options on channel receipt are settable.
31 02 Standard Mode Basic + Z1X Basic + Z1X, P.O.P Z1, P.O.P Z2, P.U.P Z2, P.U.P FWD, B.O.P Z1, B.O.P Z2
The following schemes are available when the Standard program mode is selected:
– Basic + Zone 1 extended (see section P44x/EN AP),
– Permissive Underreach Transfer Trip Schemes PUP Z2 and PUP Fwd,
– Permissive Overreach Transfer Trip Schemes POP Z2 and POP Z1;
– Blocking Schemes BOP Z2 and BOP Z1.
The PUP, POP and BOP schemes are detailed in section P44x/EN AP
31 03 Fault Type Both enabled Phase to Ground, Phase to Phase, Both enabled.
Fault type setting
31 04 Trip Mode Force 3 poles Force 3 poles, 1P Z1 & CR, 1P Z1 Z2 & CR
Sets the tripping mode: 1-pole trip or 3-pole trip.
31 05 Sig Send Zone None None, CsZ1, CsZ2, CsZ4.
The ’Signal Send Zone’ option is available when an open scheme program mode is set. The user can decide which distance relay zone is used to send the signalling channel:
– CsZ1 or CsZ2 (’Carrier send’ from Z1 or Z2): when a fault is detected in zone 1, or zone 2, the ’Carrier Send’ is emitted from this zone to the relay. These settings are used to configure a permissive scheme.
– CsZ4 (’Carrier send’ from Z4) when a fault is detected in zone 4 (reverse). This setting can be used to configure a blocking scheme. See section decision logic in the section P44x/EN AP.
31 06 DistCR None None, PermZ1, PermZ2, PermFWD, BlkZ1, BlkZ2.
The ’Distance Carrier received’ option is available when an open scheme program mode is set. Aided scheme options on CR receipt:
– Select ’None’ to configure a basic scheme,
– Select ’PermZ1’ or ’PermZ2’ to configure a permissive scheme where Zone 1 or Zone 2 can only trip (without waiting tZ1 or tZ2 timeout) if a signal is received,
– Select ’BlkZ1’ or ’BlkZ2’ to configure a blocking scheme where Zone 1 or Zone 2 can only trip if a Distance Carrier is NOT received,
– Select ’PermFwd’ to configure a permissive scheme where any forward distance zone start will cause an aided trip if a Distance Carrier is received.
31 07 Tp 20ms From 0s to 1s step 2ms
Time setting
31 08 tReversal Guard 20ms From 0s to 150ms step 2ms
Where appropriate, the tReversal Guard and ’Aid Dist Delay’ (transmission time in blocking scheme) time-delays (in the case of a blocking scheme covering the transmission time) settings will appear in the relay menu. Further customising of distance schemes can be achieved using the Programmable Scheme Logic to condition send and receive logic.
31 09 Unblocking Logic None None, Loss of Guard, Loss of Carrier.
Three modes of unblocking logic are available for use with permissive schemes (blocking schemes are excluded):
– None (basic mode),
– Loss of Guard mode,
– Loss of carrier mode.
See section P44x/EN AP for details.
31 0A SOTF/TOR Mode 100000000110000(bin) Bit 00=TOR Z1 enabled Bit 01=TOR Z2 enabled Bit 02=TOR Z3 enabled Bit 03=TOR All Zones Bit 04=TOR Dist. Scheme Bit 05=SOTF All Zones Bit 06=SOTF Lev. Detect. Bit 07=SOTF Z1 enabled Bit 08=SOTF Z2 enabled Bit 09=SOTF Z3 enabled Bit 0A=SOTF Z1 + Rev en. Bit 0B=SOTF Z2 + Rev en. Bit 0C=SOTF Dist. Scheme Bit 0D=SOTF Disable Bit 0E=SOTF I>3 enabled
Sets individual protection zones to enable or disable the TOR / SOTF protection. Setting the relevant bit to 1 will enable TOR / SOTF for the selected zone, setting bits to 0 will disable TOR / SOTF for the selected zone:
– TOR (or SOTF) Zi enabled: TOR or SOTF logic enabled in case of fault in zone i,
– TOR (or SOTF) All Zones: TOR or SOTF logic enabled for all zones,
– TOR (or SOTF) Dist. Scheme: TOR or SOTF logic enabled for aided trip zones,
– SOTF I>3 enabled: TOR and SOTF initiated after detection by I>3 overcurrent,
– SOTF Lev. Detect.: SOTF initiated by level detectors.
See SOTF / TOR section P44x/EN AP for TOR-SOFT logic and SOFT-TOR trip logic.
31 0B SOTF Delay 110s 10s to 3600s step 1s
The Switch On To Fault (SOTF) protection (high speed clearance of any detected fault immediately following manual closure of the circuit breaker) and Trip On Reclose (TOR) protection (high speed clearance of any fault detected immediately following autoreclosure of the circuit breaker).
It is possible to set the time-delay to trip when, for example, the relay has detected a fault that is still present on a feeder after energising.
31 0C Z1Ext Fail Disabled Disabled or Enabled
Enable or disable the “Z1X extension on channel fail”: For the duration of any alarm condition (loss of guard, loss of carrier), the “zone 1 extension” trip logic will be invoked if this option has been enabled.
31 0D Weak Infeed    
Weak Infeed schemes are used when there is a weak source at one end of the line
31 0E WI:Mode Status Disabled Disabled, PAP, Echo, Trip & Echo
Weak infeed logic can be enabled with weak infeed echo option or weak infeed trip option (PAP is a specific customer application).
Refer to Weak Infeed section (P44x/EN AP) for mode status and settings.
31 12 PAP:Tele Trip En Disabled Disabled or Enabled
PAP (Passive Antenna Protection) is a specific customer application.
31 13 PAP:Del. Trip En Disabled Disabled or Enabled
PAP (Passive Antenna Protection) is a specific customer application.
31 14 PAP:P1 Disabled Disabled or Enabled
PAP (Passive Antenna Protection) is a specific customer application.
31 15 PAP:1P Time Del 500ms From 100ms to 1.5s step 100ms
PAP (Passive Antenna Protection) is a specific customer application.
31 16 PAP:P2 Disabled Disabled or Enabled
PAP (Passive Antenna Protection) is a specific customer application.
31 17 PAP:P3 Disabled Disabled or Enabled
PAP (Passive Antenna Protection) is a specific customer application.
31 18 PAP:3P Time Del 2s From 100ms to 12s step 100ms
PAP (Passive Antenna Protection) is a specific customer application.
31 19 PAP:IN Thres 0.5*I1 0.1*I1 to 1*I1 step 0.01*I1
PAP (Passive Antenna Protection) is a specific customer application.
31 1A PAP: K (%Vn) 0.5 0.5 to 1 step 0.05
PAP (Passive Antenna Protection) is a specific customer application.
31 1B Loss Of Load    
The loss of load (LoL) provides fast fault clearance for faults (see P44x/EN AP, LOL section)
31 1C LoL:Mode Status Disabled Disabled or Enabled
Setting that enables (turns on) or disables (turns off) the Loss of Load scheme. When enabled, the loss of load logic provides fast fault clearance for faults over the whole of a double end fed protected circuit for all types of fault, except three phases.   
31 1D LoL:Chan Fail Disabled Disabled or Enabled
The Loss of Load logic can be chosen to be enabled when the channel associated with an aided scheme has failed.
31 1E LoL:I< 0.5*I1 0.05*I1 to 1*I1 step 0.05*I1
LOL undercurrent detector that indicates a loss of load condition on the unfaulted phases, indicating that the remote end has just opened.
31 1F LoL:Window 40ms From 10ms to 100ms step 10ms
Length of  OL window – the time window in which Zone 2 accelerated tripping can occur following LOL undercurrent detector operation.

Power Swing Detection and Blocking (PSB)

Col Row Courier Text Default Setting Available Setting
Description
32 00 GROUP 1: POWER- SWING    
GROUP1: Power-Swing
32 01 Delta R 0.5Ω 0 to 400/I1 Ω step 0.01/I1 Ω
Power swing detection Resistive band which surrounds phase fault trip characteristic (see section P44x/EN AP, section 4.1). Typically, the ΔR and ΔX band settings are both set between 10 – 30% of R3Ph. This gives a secondary impedance between
0.6 and 1.8Ω. For convenience, 1.0Ω could be set.
The width of the power swing band is calculated as follows: ΔR = 1.3 × tan(π × Δf × Δt) × RLOAD
Assuming that the load corresponds to 60° angles between sources and if the resistive reach is set so that Rlim = RLOAD/2, the following is obtained:
ΔR = 0.032 × Δf × RLOAD
To ensure that a power swing frequency of 5Hz is detected, the following is obtained: ΔR = 0.16 × RLOAD
Where:
ΔR: width of the power swing detection band Δf: power swing frequency (fA – fB)
Rlim resistive reach of the starting characteristic (=R3ph-R4ph)
Z: network impedance corresponding to the sum of the reverse (Z4) and forward (Z3) impedances
32 02 Delta X 0.5Ω 0 to 400/I1 Ω step 0.01/I1 Ω
Power swing detection Reactive band which surrounds phase fault trip characteristic (see section P44x/EN AP).
32 03 IN> status Enabled Disabled or Enabled
Residual current power swing unblocking criteria activation:
Enables or disables the earth fault protection during Power Swing Bloc.king. When enabled, the relay will trip when IN > ’IN > (% Imax)’ or when IN < 0.1 × In.
32 04 IN> (%Imax) 0.4 10% to 100% step 1%
Residual current threshold for power swing unblocking. It is a percentage of the highest measured current on any phase.
– Typical setting: 40%
– Minimum setting (to avoid maloperation for asymmetric in power swing currents): > 30%
– Maximum setting (to ensure unblocking for line faults): < 100%
32 05 I2> status Enabled Disabled or Enabled
Negative Sequence current power swing unblocking criteria activation:
Enables or disables the phase-phase fault protection during Power Swing Blocking. When enabled, the relay will trip when I2 > ’I2 > (% Imax)’ or when I2 < 0.1 × In.
32 06 I2> (%Imax) 0.3 10% to 100% step 1%
Negative Sequence current threshold for power swing unblocking. It is a percentage of the highest measured current on any phase.
– Typical setting: 30%
– Minimum setting (to avoid maloperation for asymmetric in power swing currents): > 10%
– Maximum setting (to ensure unblocking for line faults): < 50%
32 07 ImaxLine> Status Enabled Disabled or Enabled
Phase current power swing unblocking criteria activation:
Enables or disables the three-phase fault protection during Power Swing Blocking. When enabled, the relay will trip when phase current threeshold exceeds Imax line >.
32 08 ImaxLine > 3*I1 1*I1 to 20*I1 step 0.01*I1
Phase current threshold for power swing unblocking (unit:A)
– Minimum setting: 1.2 × [ maximum power swing current ]
– Maximum setting: 0.8 × [ minimum phase fault current level ]
32 09 Delta I Status Enabled Disabled or Enabled
Delta I criterion status activation:
Enables or disables the unblocking logic three-phase fault protection during Power Swing Blocking. Time delay is settable.
32 0A Unblocking delay 30s From 0s to 30s step 100ms
Time-delay after which blocking criteria is automatically removed. Typical setting:
– 30s if a near permanent block is required,
– 2s if unblocking is required to split the system.
32 0B Blocking Zones 000000(bin) Bit 00=Z1&Z1X blocking Bit 01=Z2 blocking Bit 02=Zp blocking, Bit 03=Zq blocking Bit 04=Z3 blocking Bit 05=Z4 blocking
Allow zone blocking in case of a power swing.
The Blocked Zones function bits are set to 1 to block zone tripping or are set to 0 to allow tripping as normal.
When the criteria for power swing detection are met (3 single phase loop inside the quad & crossing the ΔR band in less than 5 ms in a 50 Hz network), and when out of step tripping is selected, then the distance protection with all of its stages is blocked – in order to prevent tripping by the distance protection (the relay can operate normally for any fault occurring during a power swing as there are different criteria which can be used by monitoring current & delta current).
32 0C Out of Step 1 1 to 255 step 1
Threshold of number of out of steps. Triggers DDB #352 when reached. Setting of the number of steps to confirm Out Of Step (OOS) condition.
32 0D Stable Swing 1 1 to 255 step 1
f number of Stable Swings. Triggers DDB #353 when reached. Setting of the number of steps to confirm Stable condition

Directional and Non-Directional Overcurrent Protection

Col Row Courier Text Default Setting Available Setting
Description
35 00 GROUP 1: BACK-UP I>    
GROUP1: Back-Up I>
35 01 I>1 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the first phase overcurrent threshold (I>1) characteristic.
35 02 I>1 Directional Directional FWD Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage overcurrent element.
35 03 I>1 VTS Block Block Block, Non Directional
When the directional control for the ’I>1’ is set, sets the Voltage Transformer Supervision (VTS) directionality (see section P44x/EN AP). The operation of the VTS will block the stage or will revert to Non-directional upon operation of the VTS.
35 04 I>1 Current Set 1.5*I1 0.08*I1 to 10.0*I1 step 0.01*I1
Sets the value for the overcurrent threshold.
35 05 I>1 Time delay 1s From 0s to 100s step 10ms
Sets the time delay associated with I>1. The setting is available only when DT function is selected.
35 06 I>1 Time VTS 200ms From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
35 07 I>1 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
35 08 I>1 Time Dial 7 0.5 to 15 step 0.1
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
35 09 I>1 Reset Char DT DT or Inverse
Setting to determine the type of reset / release characteristics of IEEE / US curves.
35 0A I>1 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
35 0B I>2 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the second phase overcurrent threshold (I>1) characteristic.
35 0C I>2 Directional Non Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the second stage overcurrent element.
35 0D I>2 VTS Block Block Block, Non Directional
When the directional control for the ’I>2’ is set, sets the Voltage Transformer Supervision (VTS) directionality (see section P44x/EN AP). The operation of the VTS will block the stage or will revert to Non-directional upon operation of the VTS.
35 0E I>2 Current Set 2*I1 0.08*I1 to 10.0*I1 step 0.01*I1
Sets the value for the overcurrent threshold.
35 0F I>2 Time delay 2s From 0s to 100s step 10ms
Sets the time delay associated with I>2. The setting is available only when DT function is selected.
35 10 I>2 Time VTS 2s From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
35 11 I>2 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
35 12 I>2 Time Dial 7 0.5 to 15 step 0.1
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
35 13 I>2 Reset Char DT DT or Inverse
Setting to determine the type of reset / release characteristics of IEEE / US curves.
35 14 I>2 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
35 15 I>3 Status Enabled Disabled or Enabled
The third element is fixed as non-directional, for instantaneous or definite time delayed tripping.
35 16 I>3 Current Set 3*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the overcurrent threshold.
35 17 I>3 Time delay 3s From 0s to 100s step 10ms
Sets the time delay associated with I>3.
35 18 I>4 Status Disabled Disabled or Enabled
The fourth element is non directional and can be used for stub bus protection. If the “stub bus enable” input is equal to 0, the I>4 function operates as a normal overcurrent stage with I>4 time delay, if the “stub bus enable” input is equal to 1, only the I>4 function is active (not I>1, I>2 and I>3) and it operates instantaneously.
35 19 I>4 Current Set 4*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the overcurrent threshold.
35 1A I>4 Time delay 4s From 0s to 100s step 10ms
Sets the time delay associated with I>4 if no stub bus condition is activated through the binary input "stub bus enable"

Negative Sequence Overcurrent Protection

Col Row Courier Text Default Setting Available Setting
Description
36 00 GROUP 1: NEG SEQUENCE O/C    
GROUP1: Negative Sequence O/C
36 01 I2>1 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the first negtive sequence overcurrent threshold (I2>1) characteristic.
36 02 I2>1 Directional Non Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage negative sequence element
36 03 I2>1 VTS Block Block Block, Non Directional
When the directional control for the ’I2>1’ is set, sets the VoltWhen the directional control for the ’I2>1’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non-directional upon operation of the VTS.
36 04 I2>1 Current Set 0.2*I1 0.08*I1 to 4*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
36 05 I2>1 Time delay 10s From 0s to 100s step 10ms
Sets the time delay associated with I2>1. The setting is available only when DT function is selected.
36 06 I2>1 Time VTS 200ms From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay in seconds under VTS conditions
36 07 I2>1 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
36 08 I2>1 Time Dial 1 0.01 to 100 step 0.01
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
36 09 I2>1 Reset Char DT DT, Inverse
Setting to determine the type of reset / release characteristics of IEEE / US curves.
36 0A I2>1 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
36 0B I2>2 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the second negtive sequence overcurrent threshold (I2>2) characteristic.
36 0C I2>2 Directional Non Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage negative sequence element
36 0D I2>2 VTS Block Block Block, Non Directional
When the directional control for the ’I2>2’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
36 0E I2>2 Current Set 0.2*I1 0.08*I1 to 4*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
36 0F I2>2 Time delay 10s From 0s to 100s step 10ms
Sets the time delay associated with I2>2. The setting is available only when DT function is selected.
36 10 I2>2 Time VTS 200ms From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay in seconds under VTS conditions
36 11 I2>2 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
36 12 I2>2 Time Dial 1 0.01 to 100 step 0.01
Sets the time dial settings, to adjust the operating time of the IEEE/US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
36 13 I2>2 Reset Char DT DT, Inverse
Setting to determine the type of reset / release characteristics of IEEE / US curves.
36 14 I2>2 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
36 15 I2>3 Status Disabled Disabled, Enabled
The third element can be used for instantaneous or definite time delayed tripping.
36 16 I2>3 Directional Non Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage negative sequence element
36 17 I2>3 VTS Block Block Block, Non Directional
When the directional control for the ’I2>3’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
36 18 I2>3 Current Set 0.2*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
36 19 I2>3 Time delay 10s From 0s to 100s step 10ms
Sets the time delay associated with I2>3.
36 1A I2>3 Time VTS 200ms From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay in seconds under VTS conditions
36 1B I2>4 Status Disabled Disabled, Enabled
The fourth element can be used for instantaneous or definite time delayed tripping.
36 1C I2>4 Directional Non Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage negative sequence element
36 1D I2>4 VTS Block Block Block, Non Directional
When the directional control for the ’I2>4’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
36 1E I2>4 Current Set 0.2*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
36 1F I2>4 Time delay 10s From 0s to 100s step 10ms
Sets the time delay associated with I2>4.
36 20 I2>4 Time VTS 200ms From 0s to 100s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay in seconds under VTS conditions
36 21 I2> Char Angle -45º -95º to 95º step 1º
Where negative phase sequence current may flow in either direction through a relay location, such as parallel lines or ring main systems, directional control of the element should be employed (see section P44x/EN AP). It should be set equal to the phase angle of the negative phase sequence current, with respect to the inverted Negative phase sequence voltage (-V2).

Maximum of Residual Power Protection – Zero Sequence Power Protection

Col Row Courier Text Default Setting Available Setting
Description
3C 00 GROUP 1: ZERO SEQ. POWER    
GROUP1: Zero Sequence Power
3C 01 P0 Status   Disabled, Enabled
Setting that enables or disables the zero sequence power protection.
3C 02 Time Delay Fact. 0s From 0s to 2s step 200ms
Setting for the K time delay factor. The K time delay factor adjusts the IDMT T(s) time-delay. T(s) = K × (Sref/Sr) where:
– Sref = Reference residual power
– Sr = Residual power generated by the fault
3C 03 Fix Time Delay 1s From 0s to 10s step 10ms
Setting for the fixed time delay
3C 04 IN Current Set 0.1*I1 0.05*I1 to 1*I1 step 0.01*I1
Setting for the residual current
3C 05 P0 Threshold 0.5*V1*I1 From 0.3*I1*V1 to 6*I1*V1 step 0.01*I1*V1
Setting to adjust the residual power threshold

Broken Conductor Detection

Col Row Courier Text Default Setting Available Setting
Description
37 00 GROUP 1: BROKEN CONDUCTOR    
GROUP1: Broken Conductor
37 01 Broken Conductor Enabled Disabled, Enabled
Setting that enables or disables the broken conductor protection
37 02 I2/I1 Setting 0.2 0.2 to 1 step 0.01
Setting to determine the pick-up level of the negative sequence to positive sequence current ratio.
37 03 I2/I1 Time delay 60s From 0s to 100s step 100ms
Setting for the function operating time-delay.
37 04 I2/I1 Trip Disabled Disabled, Enabled
Enables or disables the negative to positive current ratio protection. If disabled, only a Broken Conductor Alarm is possible.

Directional and Non-Directional Earth Fault

Col Row Courier Text Default Setting Available Setting
Description
38 00 GROUP 1: EARTH FAULT
O/C
   
GROUP1: Earth Fault O/C
38 01 IN>1 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the first earth fault overcurrent threshold (IN>1) characteristic.
38 02 IN>1 Directional Directional FWD Non Directional, Directional FWD, Directional REV
Sets the directional control for the first stage earth fault element
38 03 IN>1 VTS Block Block Block, Non Directional
When the directional control for the ’IN>1’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
38 04 IN>1 Current Set 0.2*I1 0.08*I1 to 10.0*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
38 05 IN>1 Time delay 1s From 0s to 200s step 10ms
Sets the time delay associated with IN>1. The setting is available only when DT function is selected.
38 06 IN>1 Time VTS 200ms From 0s to 200s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
38 07 IN>1 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
38 08 IN>1 Time Dial 7 0.5 to 15 step 0.1
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
38 09 IN>1 Reset Char DT DT, Inverse
Setting that determines the reset / release time reset characteristics.
38 0A IN>1 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
38 0B IN>2 Function DT Disabled, DT, IEC S Inverse, IEC V Inverse, IEC E Inverse, UK LT Inverse, IEEE M Inverse, IEEE V Inverse, IEEE E Inverse, US Inverse, US ST Inverse
Sets the second earth fault overcurrent threshold (IN>2) characteristic.
38 0C IN>2 Directional Non-Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the second stage earth fault element
38 0D IN>2 VTS Block Block Block, Non Directional
When the directional control for the ’IN>2’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
38 0E IN>2 Current Set 0.3*I1 0.08*I1 to 10.0*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
38 0F IN>2 Time delay 2s From 0s to 200s step 10ms
Sets the time delay associated with IN>2. The setting is available only when DT function is selected.
38 10 IN>2 Time VTS 2s From 0s to 200s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
38 11 IN>2 TMS 1 0.025 to 1.2 step 0.005
Sets the Time Multiplier Setting (TMS), to adjust the operating time of the IEC/UK IDMT characteristics.
38 12 IN>2 Time Dial 7 0.5 to 15 step 0.1
Sets the time dial settings, to adjust the operating time of the IEEE/ US IDMT curves. The Time Dial is a multiplier of the standard curve equation, in order to achieve the required tripping time. The reference curve is based on Time Dial = 1.
Care: Certain manufacturer’s use a mid-range value of time dial = 5 or 7. So; it may be necessary to divide by 5 or 7 to achieve parity.
38 13 IN>2 Reset Char DT DT, Inverse
Setting that determines the reset / release time reset characteristics.
38 14 IN>2 tReset 0s From 0s to 100s step 10ms
Setting that determines the reset/release time for definite time reset characteristic.
38 15 IN>3 Status Enabled Disabled, Enabled
The third element can be used for instantaneous or definite time delayed tripping.
38 16 IN>3 Directional Non-Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the third stage earth fault element
38 17 IN>3 VTS Block Block Block, Non Directional
When the directional control for the ’IN>3’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
38 18 IN>3 Current Set 0.3*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
38 19 IN>3 Time delay 2s From 0s to 200s step 10ms
Sets the time delay associated with IN>3. The setting is available only when DT function is selected.
38 1A IN>3 Time VTS 2s From 0s to 200s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
38 1B IN>4 Status Enabled Disabled, Enabled
The fourth element can be used for instantaneous or definite time delayed tripping.
38 1C IN>4 Directional Non-Directional Non Directional, Directional FWD, Directional REV
Sets the directional control for the fourth stage earth fault element
38 1D IN>4 VTS Block Block Block, Non Directional
When the directional control for the ’IN>4’ is set, sets the Voltage Transformer Supervision (VTS) directionality. The operation of the VTS will block the stage or will revert to Non- directional upon operation of the VTS.
38 1E IN>4 Current Set 0.3*I1 0.08*I1 to 32*I1 step 0.01*I1
Sets the value for the negative sequence current threshold.
38 1F IN>4 Time delay 2s From 0s to 200s step 10ms
Sets the time delay associated with IN>4. The setting is available only when DT function is selected.
38 20 IN>4 Time VTS 2s From 0s to 200s step 10ms
If VTS Block is set to Non-Directional the element will operate with this time delay under VTS conditions
38 21 IN> DIRECTIONAL    
This setting determines the direction of measurement for the earth fault overcurrent element.
38 22 IN Char Angle -45° From -95° to 95° step 1°
Earth fault (or, if set in “Polarisation” cell, negative sequence) relay characteristic angle. Comparison of the angle between the earth fault voltage and the earth fault current to achieve directionality (see section P44x/EN AP). It should be set equal to the phase angle of the earth fault current, with respect to the inverted earth fault voltage (-VN)
38 23 Polarisation Zero sequence Zero sequence, Neg sequence
Sets earth fault or negative sequence for relay characteristic angle setting.
38 24 IN> BLOCKING    
Neutral overcurrent blocking setting
38 25 Block Pole Dead Enabled Disabled, Enabled
When enabled, neutral (residual) overcurrent element will block pole dead detection.

Aided Directional Earth Fault (DEF) Protection

Col Row Courier Text Default Setting Available Setting
Description
39 00 GROUP 1: AIDED DEF    
GROUP1: Aided DEF
39 01 Aided ch. Status Enabled Disabled, Enabled
To enable (activate) or disable (turn off) the Directional Earth Fault Element that is used in an aided scheme.
39 02 Polarisation Zero sequence Zero sequence, Neg sequence
Setting that defines the method of DEF polarisation. Either zero, or negative sequence voltage can be taken as the directional reference.
The applications of zero sequence and negative sequence polarisation are described in section P44x/EN AP, section Directional Directional and non directional Earth Fault Protection).
39 03 V> Voltage Set 1V From 0.5V to 20V step 0.01V
The V> threshold defines the minimum residual voltage required to enable the aided DEF directional decision. A residual voltage measured below this setting would block the directional decision, and hence there would be no tripping from the scheme.
39 04 IN Forward 0.1*I1 0.05*I1 to 4*I1 step 0.01*I1
Setting of the netural current threshold in forward direction.
39 05 Time Delay 0s From 0s to 10s step 2ms
Setting of the time delay
39 06 Scheme Logic Shared Shared, Blocking, Permissive
To select shared, blocking or permissive scheme logic.
39 07 Tripping Three Phase Any phase, Three phase
Setting of tripping type, three phase or single phase.
39 08 Tp 20ms From 0s to 1s step 2ms
Aid Dist Delay (if blocking scheme not shared)
Transmission time in blocking scheme. The Aided distribution time-delay (in the case of a blocking scheme covering the transmission time) settings will appear in the relay menu. Further customising of distance schemes can be achieved using the Programmable Scheme Logic to condition send and receive logic.
39 09 IN Rev Factor 0.6 0.1 to 1 step 0.1
’IN Rev Factor’ enhances the sensitivity for the residual current in case of reverse fault (for instance to create a faster blocking logic scheme).
39 0A Block. Time Add. 150ms From 0s to 10s step 10ms
“Block. Time Add.” is an additional time-delay, set to extend a pole dead or convergence detection.

Thermal Overload

Col Row Courier Text Default Setting Available Setting
Description
3A 00 GROUP 1: THERMAL OVERLOAD    
GROUP1: Thernal Overload
3A 01 Characteristic Single Disabled, Single, Dual
Thermal characteristic setting. Available choices are: ’Disabled”, ’Single’ (for line and cable protection) and ’Dual’ (for oil-filled transformers with natural air cooling protection)
3A 02 Thermal Trip 1*I1 0.08*I1 to 3.2*I1 step 0.01*I1
Sets the full load current (ΙFLC) allowed and the pick-up threshold of the thermal characteristic.
3A 03 Thermal Alarm 0.7 From 50% to 100% step 1%
An alarm can be raised on reaching a thermal state corresponding to a percentage of the trip threshold. A typical setting might be ’Thermal Trip’ = 70% of thermal capacity.
3A 04 Time Constant 1 10 From 1 to 200 step 1
Setting in minutes for the thermal time constant (τ1) for a single time constant characteristic, or the first time constant for the dual time constant characteristic.
3A 05 Time Constant 2 5 From 1 to 200 step 1
Setting in minutes for the second time constant (τ2) for the dual time constant characteristic.

Residual Overvoltage (Neutral Displacement) Protection

Col Row Courier Text Default Setting Available Setting
Description
3B 00 GROUP 1: RESIDUAL O/V NVD    
GROUP1: Residual Over Voltage
3B 01 VN Type Residual Residual, Homopolar
Select VN> settings as residual (3V0) or homopolar (V0) voltage
3B 02 VN>1 Function DT Disabled, DT, IDMT
Select the residual overvoltage stage 1 as either Inverse Definite Minimum Time (IDMT), Definite Time (DT) or disabled. The following submenus are visible according to this setting.
3B 03 VN>1 Voltage Set 5V From 1V to 180V step 1V
Setting for the voltage threshold of the first stage VN> protection.
3B 04 VN>1 Voltage Set 1.5V From 0.5V to 60V step 0.5V
Setting for the voltage threshold of the first stage VN> protection.
3B 05 VN>1 Time Delay 5s From 0s to 100s step 10ms
Operating time delay setting for the first stage definite time residual overvoltage element.
3B 06 VN>1 TMS 1 0.5 to 100 step 0.5
Setting for the Time Multiplier Setting to adjust the operating time of the IDMT characteristic. where K = Time Multiplier Setting (TMS), K = Operating time (in second) and M = measured voltage / relay setting voltage (V<).
3B 07 VN>1 tReset 0s From 0s to 100s step 10ms
Setting to determine the reset/release definite time for the first stage characteristic.
3B 08 VN>2 Status Disabled Disabled or Enabled
Setting to enable or disable the second stage definite time residual overvoltage element.
3B 09 VN>2 Voltage Set 10V From 1V to 180V step 1V
Setting for the voltage threshold of the second stage VN> protection.
3B 0A VN>2 Voltage Set 3V From 0.5V to 60V step 0.5V
Setting for the voltage threshold of the second stage VN> protection.
3B 0B VN>2 Time Delay 10s From 0s to 100s step 10ms
Operating time delay setting for the second stage residual overvoltage element

Undercurrent Protection

Col Row Courier Text Default Setting Available Setting
Description
3B 00 GROUP 1: RESIDUAL O/V NVD    
GROUP1: Residual Over Voltage
3B 01 VN Type Residual Residual, Homopolar
Select VN> settings as residual (3V0) or homopolar (V0) voltage
3B 02 VN>1 Function DT Disabled, DT, IDMT
Select the residual overvoltage stage 1 as either Inverse Definite Minimum Time (IDMT), Definite Time (DT) or disabled. The following submenus are visible according to this setting.
3B 03 VN>1 Voltage Set 5V From 1V to 180V step 1V
Setting for the voltage threshold of the first stage VN> protection.
3B 04 VN>1 Voltage Set 1.5V From 0.5V to 60V step 0.5V
Setting for the voltage threshold of the first stage VN> protection.
3B 05 VN>1 Time Delay 5s From 0s to 100s step 10ms
Operating time delay setting for the first stage definite time residual overvoltage element.
3B 06 VN>1 TMS 1 0.5 to 100 step 0.5
Setting for the Time Multiplier Setting to adjust the operating time of the IDMT characteristic. where K = Time Multiplier Setting (TMS), K = Operating time (in second) and M = measured voltage / relay setting voltage (V<).
3B 07 VN>1 tReset 0s From 0s to 100s step 10ms
Setting to determine the reset/release definite time for the first stage characteristic.
3B 08 VN>2 Status Disabled Disabled or Enabled
Setting to enable or disable the second stage definite time residual overvoltage element.
3B 09 VN>2 Voltage Set 10V From 1V to 180V step 1V
Setting for the voltage threshold of the second stage VN> protection.
3B 0A VN>2 Voltage Set 3V From 0.5V to 60V step 0.5V
Setting for the voltage threshold of the second stage VN> protection.
3B 0B VN>2 Time Delay 10s From 0s to 100s step 10ms
Operating time delay setting for the second stage residual overvoltage element

Voltage Protection Menu

Col Row Courier Text Default Setting Available Setting
Description
42 00 GROUP 1: VOLT PROTECTION    
GROUP1: Voltage Protection
42 01 V< & V> MODE 00000000(bin) Bit 00=V<1 Trip Bit 01=V<2 Trip Bit 02=V<3 Trip Bit 03=V<4 Trip Bit 04=V>1 Trip Bit 05=V>2 Trip Bit 06=V>3 Trip Bit 07=V>4 Trip
Determines whether the stage will operate the "Any Trip" signal. Visible if either element is Enabled
42 02 UNDER VOLTAGE    
Set the parameters for V< protection in the following settings
42 03 V< Measur’t Mode Phase_Neutral Phase_Neutral, Phase_Phase
Select the undervoltage protection to operate from a phase to phase voltage or phase to neutral measurement.
42 04 V<1 Function DT Disabled, DT, IDMT
Select the first undervoltage threshold as either Inverse Definite Minimum Time (IDMT), Definite Time (DT) or disabled. The three following submenus (Voltage, time delay and time multiplier setting) are visible according to this setting.
42 05 V<1 Voltage Set 50V From 10V to 120V step 1V
Sets the pick-up setting for first stage undervoltage element.
42 06 V<1 Time Delay 10s From 0s to 100s step 10ms
Setting for the operating time-delay for the first stage definite time undervoltage element.
42 07 V<1 TMS 1 0.5 to 100 step 0.5
"The following formula defines the IDMT characteristics: t = K / (1 – M),
where K = Time Multiplier Setting (TMS), t = Operating time (in seconds) and M = measured voltage / relay setting voltage (V<)."
42 08 V<2 Status Disabled Disabled, Enabled
Enable or disable the second undervoltage threshold. The voltage and time-delay (following submenus) are settable when V<2 status is enabled. Stage 2 is DT only.
42 09 V<2 Voltage Set 38V From 10V to 120V step 1V
Sets the pick-up setting for second stage undervoltage element.
42 0A V<2 Time Delay 500ms From 0s to 100s step 10ms
Setting for the operating time-delay for the second stage definite time undervoltage element.
42 0B V<3 Status Disabled Disabled, Enabled
Enable or disable 3rd undervoltage threshold. The voltage and time-delay (following submenus) are settable when V<3 status is enabled. Stage 3 is DT only.
42 0C V<3 Voltage Set 30V From 10V to 120V step 1V
Sets the pick-up setting for third stage undervoltage element.
42 0D V<3 Time Delay 1s From 0s to 100s step 10ms
Setting for the operating time-delay for the third stage definite time undervoltage element.
42 0E V<4 Status Disabled Disabled, Enabled
Enable or disable 4th undervoltage threshold. The voltage and time-delay (following submenus) are settable when V<4 status is enabled. Stage 4 is DT only.
42 0F V<4 Voltage Set 25V From 10V to 120V step 1V
Sets the pick-up setting for fourth stage undervoltage element.
42 10 V<4 Time Delay 1s From 0s to 100s step 10ms
Setting for the operating time-delay for the fourth stage definite time undervoltage element.
42 11 OVERVOLTAGE    
Set the parameters for V> protection in the following settings
42 12 V> Measur’t Mode Phase_Neutral Phase-phase, Phase-neutral
Select the overvoltage protection to operate from a phase to phase voltage or phase to neutral measurement.
42 13 V>1 Function DT Disabled, DT, IDMT
Select the first overvoltage threshold as either Inverse Definite Minimum Time (IDMT), Definite Time (DT) or disabled (see setting guidelines, section 2.4). The three following submenus (Voltage, time delay and time multiplier setting) are visible according to this setting.
42 14 V>1 Voltage Set 75V From 40V to 185V step 1V
Sets the pick-up setting for first stage overvoltage element.
42 15 V>1 Time Delay 10s From 0s to 100s step 10ms
Setting for the operating time-delay for the first stage definite time overvoltage element.
42 16 V>1 TMS 1 0.5 to 100 step 0.5
"The following formula defines the IDMT characteristics: t = K / (M – 1),
where K = Time Multiplier Setting (TMS), t = Operating time (in seconds) and M = measured voltage / relay setting voltage (V>)."
4604 Sets maximum I> threshold. The setting is used to override a voltage supervision block in the event of a phase fault occurring on the system (where 3 voltages are lost and the line is energized) that could trigger the voltage supervision logic.
42 17 V>2 Status Disabled Disabled, Enabled
Enable or disable the second overvoltage threshold. The voltage and time-delay (following submenus) are settable when V>2 status is enabled. Stage 2 is DT only.
42 18 V>2 Voltage Set 90V From 40V to 185V step 1V
Sets the pick-up setting for second stage overvoltage element.
42 19 V>2 Time Delay 500ms From 0s to 100s step 10ms
Setting for the operating time-delay for the second stage definite time overvoltage element.
42 1A V>3 Status Disabled Disabled, Enabled
Enable or disable 3rd overvoltage threshold. The voltage and time-delay (following submenus) are settable when V>3 status is enabled. Stage 3 is DT only.
42 1B V>3 Voltage Set 100V From 40V to 185V step 1V
Sets the pick-up setting for third stage overvoltage element.
42 1C V>3 Time Delay 1s From 0s to 100s step 10ms
Setting for the operating time-delay for the third stage definite time overvoltage element.
42 1D V>4 Status Disabled Disabled, Enabled
Enable or disable 4th overvoltage threshold. The voltage and time-delay (following submenus) are settable when V>4 status is enabled. Stage 4 is DT only.
42 1E V>4 Voltage Set 105V From 40V to 185V step 1V
Sets the pick-up setting for fourth stage overvoltage element.
42 1F V>4 Time Delay 1s From 0s to 100s step 10ms
Setting for the operating time-delay for the fourth stage definite time overvoltage element.

Frequency Protection

Col Row Courier Text Default Setting Available Setting
Description
43 00 GROUP 1: FREQ PROTECTION    
GROUP1: Frequency Protection
43 01 UNDER FREQUENCY    
Set the parameters for F< protection in the following settings
43 02 F<1 Status Disabled Disabled / Enabled
Setting to enable or disable the first underfrequency element. The F<1 threshold setting and time-delay (following submenus) are settable when F<1 status is enabled.
43 03 F<1 Freq Set 49.5Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the first stage underfrequency element.
43 04 F<1 Time Delay 4s From 0s to 100s step 10ms
Setting that determines the minimum operating time-delay for the first stage underfrequency element.
43 05 F<2 Status Disabled Disabled / Enabled
Setting to enable or disable the second underfrequency threshold (same setting as stage 1).
43 06 F<2 Freq Set 49Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the second stage underfrequency element.
43 07 F<2 Time Delay 3s From 0s to 100s step 10ms
Setting that determines the minimum operating time-delay for the second stage underfrequency element.
43 08 F<3 Status Disabled Disabled / Enabled
Setting to enable or disable the 3rd underfrequency threshold (same setting as stage 1).
43 09 F<3 Freq Set 48.5Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the third stage underfrequency element.
43 0A F<3 Time Delay 2s From 0s to 100s step 10ms
Setting that determines the minimum operating time-delay for the third stage underfrequency element.
43 0B F<4 Status Disabled Disabled / Enabled
Setting to enable or disable the 4th underfrequency threshold (same setting as stage 1).
43 0C F<4 Freq Set 48Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the fourth stage underfrequency element.
43 0D F<4 Time Delay 1s From 0s to 100s step 10ms
Setting that determines the minimum operating time-delay for the fourth stage underfrequency element.
43 0E OVER FREQUENCY    
Set the parameters for F> protection in the following settings
43 0F F>1 Status Disabled Disabled / Enabled
Setting to enable or disable the first overfrequency element. The F>1 threshold setting and time-delay (following submenus) are settable when F>1 status is enabled.
43 10 F>1 Freq Set 50.5Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the first stage overfrequency element.
43 11 F>1 Time Delay 2s From 0s to 100s step 10ms
Setting that determines the minimum operating time-delay for the first stage overfrequency element.
43 12 F>2 Status Disabled Disabled / Enabled
Setting to enable or disable the second overfrequency threshold (same setting as stage 1).
43 13 F>2 Freq Set 51Hz From 45Hz to 65Hz step 0.01Hz
Setting that determines the pick-up threshold for the second stage overfrequency element.
43 14 F>2 Time Delay 1s tep 10ms
Setting that determines the minimum operating time-delay for the second stage overfrequency element.

Circuit Breaker Fail (CBF) Protection

Col Row Courier Text Default Setting Available Setting
Description
45 00 GROUP 1: CB FAIL & I<    
GROUP1: CB Fail & I<
45 01 BREAKER FAIL    
Set the parameters for Circuit Breaker Failure in the following settings
45 02 CB Fail 1 Status Enabled Enabled, Disabled
Setting to enable or disable the first stage of the circuit breaker function.
45 03 CB Fail 1 Timer 200ms From 0s to 10s step 5ms
Setting for the circuit breaker fail timer stage 1, during which breaker opening must be detected.
45 04 CB Fail 2 Status Disabled Disabled / Enabled
Setting to enable or disable the second stage of the circuit breaker function.
45 05 CB Fail 2 Timer 400ms From 0s to 10s step 5ms
Setting for the circuit breaker fail timer stage 2, during which breaker opening must be detected.
45 06 CBF Non I Reset CB open & I< I< Only, CB open & I<, Prot Reset & I<, Disable, Prot Reset or I<
Setting which determines the elements that will reset the circuit breaker fail time for undercurrent protection function initiated circuit breaker fail conditions.
45 07 CBF Ext Reset CB open & I< I< Only, CB open & I<, Prot Reset & I<, Disable, Prot Reset or I<
Setting which determines the elements that will reset the circuit breaker fail time for external protection function initiated circuit breaker fail conditions.
45 08 UNDERCURRENT    
Set the parameter for Under Current in the following settings
45 09 I < Current Set 0.05*I1 0.05*I1 to 3.2*I1 step 0.1*I1
Setting that determines the circuit breaker fail timer reset current for overcurrent based protection circuit breaker fail initiation.

System Data

Col Row Courier Text Default Setting Available Setting
Description
00 00 SYSTEM DATA    
This column contains general system settings
00 01 Language English English, French, German, Italian, Spanish, Chinese (UI only)
The default language used by the device. Selectable as English, French, German, Spanish, Italian and Chinese. Chinese is UI only.
00 04 Description MiCOM 32 to 234 step 1
Editable 16-character description of the unit
00 05 Plant Reference MiCOM 32 to 234 step 1
Plant description: Can be edited
00 06 Model Number Model number <Model number>
Displays the model number. This can not be edited
00 08 Serial Number Serial number <Serial number>
Displays the serial number. This can not be edited.
00 09 Frequency 50 Hz 50Hz or 60 Hz
Sets the main frequency
00 0A Comms Level 2 <conformance level displayed>
Displays the conformance of the relay to the Courier Level 2 comms
00 0B Relay Address 255
1
1
1
0 to 255 step 1 (Courier)
1 to 247 step 1 (Modbus)
0 to 254 step 1 (CS103)
0 to 65519 step 1 (DNP3)
Sets the first rear port relay address.
Build = Courier (Address available via LCD) Build = Modbus (Address available via LCD) Build = CS103 (Address available via LCD) Build = DNP3.0 (Address available via LCD)
00 0C Plant Status   Not Settable
Displays the circuit breaker plant status.
00 0D Control Status   Not Settable
Not used
00 0E Active Group 1 Not Settable
Displays the active settings group
00 10 CB Trip/Close No Operation 0 = No Operation, 1 = Trip, 2 = Close
Supports trip and close commands if enabled in the Circuit Breaker Control menu.
00 11 Software Ref. 1   <Software Ref. 1>
Displays the relay software version including protocol and relay model.
00 12 Software Ref. 2   <Software Ref. 2>
Relay Ethernet card software reference. Visible when Ethernet card fitted.
00 13 Software Ref. 3   <Software Ref. 3>
Relay Process Bus card software reference. Visible when Process Bus card fitted.
00 14 NIC Platform Ref   <NIC platform reference>
Displays the relay NIC platform reference. Visible when Ethernet card fitted.
00 15 IEC61850 Edition 2 1 or 2
Selects IEC 61850 Editions, Edition 1 or Edition 2. This setting can only be changed via HMI and the changes will cause the Ethernet board to reboot.
00 16 ETH COMM Mode Dual IP Dual IP, PRP, HSR, RSTP
Sets the redundancy protocol. This setting can only be changed via the UI and the changes will cause the Ethernet board to reboot.
00 17 PB COMM Mode Dual IP Dual IP, PRP
Sets the redundancy protocol. This setting can only be changed via the UI and the changes will cause the Process Bus board to reboot.
00 20 Opto I/P Status   Not Settable
Display the status of the available opto inputs fitted.
00 21 Relay Status 1   Not Settable
Displays the status of the first 32 output relays.
00 22 Alarm Status 1   Not Settable
This menu cell displays the status of the first 32 alarms as a binary string.
1 indicates an ON state and 0 an OFF state. Includes fixed and user settable alarms.
00 40 Relay Status 1   Not Settable
Displays the status of the first 32 relay outputs.
00 41 Relay Status 2   Not Settable
Displays the status of the next 32 relay outputs. This setting does not apply to P442 relays.
00 50 Alarm Status 1   Not Settable
This menu cell displays the status of the first 32 alarms as a binary string.
1 indicates an ON state and 0 an OFF state. Includes fixed and user settable alarms.
00 51 Alarm Status 2   Not Settable
This menu cell displays the status of the second 32 alarms as a binary string.1 indicates an ON state and 0 an OFF state.
00 52 Alarm Status 3   Not Settable
This menu cell displays the status of the third 32 alarms as a binary string. 1 indicates an ON state and 0 an OFF state. Assigned specifically for platform alarms.
00 53 Usr Alarm Status   Not Settable
This menu cell displays the status of the 32 user alarms as a binary string. 1 indicates an ON state and 0 an OFF state.
00 D0 Access Level ENGINEER Not Settable
Display the Role(s) of the current logged in user, if no one logged in, it shall be "NONE".
00 D3 New Eng.Level PW   ASCII 33 to 122
Allows user to change password for EngineerLevel. Visible on UI only.
00 D4 New Op.Level PW   ASCII 33 to 122
Allows user to change password for OperatorLevel. Visible on UI only.
00 DF Security Feature 3 Not Settable
Displays the level of cyber security inmplemented.
00 E1 Password   <Password>
Used to send encrypted password. Not visible on UI
00 E5 Encryption Salt   <Encryption Salt>
Random data used with encrypted password. Not visible on UI
00 F1 Enter username   <User Name>
User selection for login. Not visible on UI
00 F2 Number of users 2 Not Settable
Shows the number of users configured within the relays RBAC
00 F3 New UI pwd   <Second Simple Password>
Hidden cell reserved for second password modification. Not in use currently.
00 F4 New password   <Encrpted Password>
Allow password change if engineer or operator logged in and CSL0 model. Not visible on UI.

Date and Time Settings

Col Row Courier Text Default Setting Available Setting
Description
08 00 DATE AND TIME    
This column contains Date and Time settings
08 01 Date/Time   <Date/Time>
Displays the IED’s current date and time.
08 02 Date   <Date>
Front Panel Menu only
08 03 Time   <Time>
Front Panel Menu only
08 04 IRIG-B Sync Disabled 0 = Disabled or 1 = Enabled
Enable IRIG-B time synchronization.
08 05 IRIG-B Status   Not Settable
Displays the status of IRIG-B
08 06 Battery Status   Not Settable
Displays whether the battery is healthy or not
08 07 Battery Alarm Enabled 0 = Disabled or 1 = Enabled
Enables or disables battery alarm. The battery alarm needs to be disabled when a battery is removed or not used
08 13 SNTP Status   Not Settable
IEC61850 or DNP3.0 over Ethernet versions only. Displays information about the SNTP time synchronization status
08 20 LocalTime Enable Fixed 0 = Disabled, 1 = Fixed or 2 = Flexible
Setting to turn on/off local time adjustments.
Disabled – No local time zone will be maintained. Time synchronization from any interface will be used to directly set the master clock and all displayed (or read) times on all interfaces will be based on the master clock with no adjustment.
Fixed – A local time zone adjustment can be defined using the LocalTime offset setting and all interfaces will use local time except SNTP time synchronization and IEC 61850 timestamps.
Flexible – A local time zone adjustment can be defined using the LocalTime offset setting and each interface can be assigned to the UTC zone or local time zone with the exception of the local interfaces which will always be in the local time zone and IEC 61850/SNTP which will always be in the UTC zone.
08 21 LocalTime Offset 0min From -720min to 720min step 15min
Setting to specify an offset of -12 to +12 hrs in 15 minute intervals for local time zone.  This adjustment is applied to the time based on the master clock which is UTC/GMT
08 22 DST Enable Enabled 0 = Disabled or 1 = Enabled
Setting to turn on/off daylight saving time adjustment to local time.
08 23 DST Offset 60min From 30min to 60min step 30min
Setting to specify daylight saving offset which will be used for the time adjustment to local time.
08 24 DST Start Last 0 = First, 1 = Second, 2 = Third, 3 = Fourth or 4 = Last
Setting to specify the week of the month in which daylight saving time adjustment starts
08 25 DST Start Day Sunday 0 = Sunday, 1 = Monday, 2 = Tuesday, 3 = Wednesday, 4 = Thursday, 5 = Friday or 6 = Saturday
Setting to specify the day of the week in which daylight saving time adjustment starts
08 26 DST Start Month March 0 = January, 1 = February, 2 = March, 3 =
April, 4 = May, 5 = June, 6 = July, 7 =
August,  8 = September, 9 = October, 10 = November or 11 = December
Setting to specify the month in which daylight saving time adjustment starts
08 27 DST Start Mins 60min From 0min to 1425min step 15min
Setting to specify the time of day in which daylight saving time adjustment starts.  This is set relative to 00:00 hrs on the selected day when time adjustment is to start
08 28 DST End Last 0 = First, 1 = Second, 2 = Third, 3 = Fourth or 4 = Last
Setting to specify the week of the month in which daylight saving time adjustment ends
08 29 DST End Day Sunday 0 = Sunday, 1 = Monday, 2 = Tuesday, 3 = Wednesday, 4 = Thursday, 5 = Friday or 6 = Saturday
Setting to specify the day of the week in which daylight saving time adjustment ends
08 2A DST End Month October 0 = January, 1 = February, 2 = March, 3 =
April, 4 = May, 5 = June, 6 = July, 7 =
August,  8 = September, 9 = October, 10 = November or 11 = December
Setting to specify the month in which daylight saving time adjustment ends
08 2B DST End Mins 60min From 0min to 1425min step 15min
Setting to specify the time of day in which daylight saving time adjustment ends.  This is set relative to 00:00 hrs on the selected day when time adjustment is to end
08 30 RP1 Time Zone Local 0 = UTC or 1 = Local
Setting for the rear port 1 interface to specify if time synchronization received will be local or universal time co-ordinated
08 31 RP2 Time Zone Local 0 = UTC or 1 = Local
Setting for the rear port 2 interface to specify if time synchronization received will be local or universal time co-ordinated
08 32 DNPOE Time Zone UTC 0 = UTC or 1 = Local
IEC61850+DNP3oE versions only. Setting to specify if time synchronisation received will be local or universal time co- ordinated.
08 33 Tunnel Time Zone Local 0 = UTC or 1 = Local
Ethernet versions only for tunnelled courier. Setting to specify if time synchronization received will be local or universal time co- ordinated
08 40 1588 Sync DISABLE 0 = Disabled or 1 = Intfc 1 Enabled or 2 =
Intfc 2 Enabled or 3 = Intfc 1 & 2 Enabled
The setting that indicate the 1588 enable or the Intfc 1,Intfc 2 OR Both.
08 41 1588 DomainNum 0 0 to 255 step 1
The domian number of 1588 which define the scope of PTP message communication, state, operations, data sets, and timescale.
08 42 1588 PdelInterv 0 0 to 5 step 1
The initialization value is implementation-specific consistent
08 43 1588 KP 1.2 0 to 5 step 0.01
The coefficient  Kp value that use calculate the sync time
08 50 1588 Status    
Indication the status of 1588
08 51 InterfaceNum    
The value of the port number
08 52 OffsetFromMaster    
An implementation-specific representation of the current value of the time difference between a master and a slave as computed by the slave
08 53 PeerMeanPDelay    
An estimate of the current one-way propagation delay on the link
08 54 StepsRemoved    
The number of communication paths traversed between the local clock and the grandmaster clock.
08 55 ParentClockId    
The clock clockIdentity of the parent clock.
08 56 ParentPortNum    
The value of parent port number
08 57 ParentClockClass    
The parent clock class which is the attribute defining a clock’s TAI traceability
08 58 ParentClockAcc    
The parent clock accuracy which is the attribute defining the accuracy of a clock
08 59 ParentClockVar    
The parent clock variance which is the attribute defining the stability of a clock
08 5A ParentPriority1    
A user configurable designation that a clock belongs to an ordered set of clocks from which a master is selected
08 5B ParentPriority2    
A user configurable designation that provides finer grained ordering among otherwise equivalent clocks

CT and VT Ratio

Col Row Courier Text Default Setting Available Setting
Description
0A 00 CT AND VT RATIOS    
This column contains settings for Current and Voltage Transformer ratios
0A 01 Main VT Primary 110V From 100V to 1MV step 1V
Sets the main voltage transformer input primary voltage.
0A 02 Main VT Sec’y 110V From 80V to 140V step 1V
Sets the main voltage transformer input secondary voltage. Multiplier M1=[0A01]/[0A02]
0A 03 C/S VT Primary 110V From 100V to 1MV step 1V
Sets the System Check Synchronism voltage transformer input primary voltage.
0A 04 C/S VT Secondary 110V From 80V to 140V step 1V
Sets the System Check Synchronism voltage transformer input secondary voltage. Multiplier M2=[0A03]/[0A04]
0A 07 Phase CT Primary 1A From 1A to 30kA step 1A
Sets the phase current transformer input primary current rating. I1=Phase CT secondary rating.
0A 08 Phase CT Sec’y 1A From 1A to 5A step 4A
Sets the phase current transformer input secondary current rating. Multiplier M4=[0A07]/[0A08]
0A 0D Mcomp CT Primary 1A From 1A to 30kA step 1A
Sets the mutual compensation current transformer input primary current rating.
0A 0E Mcomp CT Sec’y 1A From 1A to 5A step 4A
Sets the mutual compensation current transformer input secondary current rating. Multiplier M6=[0A0D]/[0A0E]
0A 0F C/S Input A-N A-N, B-N, C-N, A-B, B-C, C-A
Selects the System Check Synchronism Input voltage measurement.
0A 10 Main VT Location Line 0 = Line or  1 = Bus
Sets the Main VT Location.
0A 11 CT Polarity Standard 0 = Standard or 1 = Inverted
Sets standard or reverse CT polarity.
error: Content is protected !!