GE / Disturbance detector element _ Element settings & highlights _ GU8058

Table of Contents

Overview

The “Disturbance detector” element (50DD) is an 87L-dedicated sensitive current disturbance detector that is used to detect any disturbance on the protected system. It is intended for such functions as trip output supervision and starting oscillography.

For more detailed information on “Disturbance detector” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
L30, L90 3D2D 50DD Function 0 to 1 1 F102 0 (Disabled)
" 3D2E 50DD Non Current Supervision 0 to 4294967295 1 F300 0
" 3D30 50DD Control Logic 0 to 4294967295 1 F300 0
" 3D32 50DD Logic Seal In 0 to 4294967295 1 F300 0
" 3D34 50DD Events 0 to 1 1 F102 0 (Disabled)
" 3D35 50DD Seal-In by 87LG 0 to 1 1 F102 0 (Disabled)
" 3D36 50DD Voltage Supv 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled

Logics & highlights


Disturbance detector logic

Disturbance detector logic