Table of Contents

Siemens / Directional overcurrent protection, phases (ANSI 67) _ Setting & highlights _ SI5027

Table of Contents

Overview

The “Directional overcurrent protection, phases” function detects short circuits at electrical equipment. It can be used as backup or emergency overcurrent protection in addition to the main protection. It ensures selective fault detection for parallel lines or transformers with infeed at one end and selective fault detection in cable runs with infeed at both ends or in lines connected to form ring topologies.

For more detailed information on “Directional overcurrent protection, phases” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding the Function Directional Overcurrent Protection, Phases – Advanced

Structure/Embedding the Function Directional overcurrent protection, Phases – Advanced

Structure/Embedding the Function Directional Overcurrent Protection, Phases – Basic

Structure/Embedding the Function Directional overcurrent orotection, Phases – Basic

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Emergency mode   no
caused by main prot.
caused by binary input
no
_:2311:102 General:Rotation angle of ref. volt.   -180 ° to 180 ° 45 °
General
_:8131:1 Definite-T 1:Mode   off
on
test
off
_:8131:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:8131:105 Definite-T 1:Directional mode   forward
reverse
forward
_:8131:8 Definite-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:8131:107 Definite-T 1:Non-direc- tional pickup   no
at volt.< & mem.empty
at volt.< & mem.empty
_:8131:104 Definite-T 1:Directional comparison   no
yes
no
_:8131:106 Definite-T 1:Release via input signal   no
yes
no
_:8131:10 Definite-T 1:Blk. by meas.-volt. failure   no
yes
yes
_:8131:26 Definite-T 1:Dynamic settings   no
yes
no
_:8131:27 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:8131:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:4 Definite-T 1:Dropout ratio   0.90 to 0.99 0.95
_:8131:101 Definite-T 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:8131:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:8131:28 Definite-T 1:Effect. by AR off/n.ready   no
yes
no
_:8131:35 Definite-T 1:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:8131:29 Definite-T 1:Effected by AR cycle 1   no
yes
no
_:8131:36 Definite-T 1:Stage blocked   no
yes
no
_:8131:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:20 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:8131:30 Definite-T 1:Effected by AR cycle 2   no
yes
no
_:8131:37 Definite-T 1:Stage blocked   no
yes
no
_:8131:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:21 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:8131:31 Definite-T 1:Effected by AR cycle 3   no
yes
no
_:8131:38 Definite-T 1:Stage blocked   no
yes
no
_:8131:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:22 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:8131:32 Definite-T 1:Effected by AR cycle gr. 3   no
yes
no
_:8131:39 Definite-T 1:Stage blocked   no
yes
no
_:8131:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:23 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:8131:33 Definite-T 1:Effect. b. cold-load pickup   no
yes
no
_:8131:40 Definite-T 1:Stage blocked   no
yes
no
_:8131:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:24 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:8131:34 Definite-T 1:Effected by binary input   no
yes
no
_:8131:41 Definite-T 1:Stage blocked   no
yes
no
_:8131:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:25 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
General
_:8132:1 Definite-T 2:Mode   off
on
test
off
_:8132:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:8132:105 Definite-T 2:Directional mode   forward
reverse
forward
_:8132:8 Definite-T 2:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:8132:107 Definite-T 2:Non-direc- tional pickup   no
at volt.< & mem.empty
at volt.< & mem.empty
_:8132:104 Definite-T 2:Directional comparison   no
yes
no
_:8132:106 Definite-T 2:Release via input signal   no
yes
no
_:8132:10 Definite-T 2:Blk. by meas.-volt. failure   no
yes
yes
_:8132:26 Definite-T 2:Dynamic settings   no
yes
no
_:8132:27 Definite-T 2:Blk. w. inrush curr. detect.   no
yes
no
_:8132:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:4 Definite-T 2:Dropout ratio   0.90 to 0.99 0.95
_:8132:101 Definite-T 2:Dropout delay   0.00 s to 60.00 s 0.00 s
_:8132:6 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: AR off/n.rdy
_:8132:28 Definite-T 2:Effect. by AR off/n.ready   no
yes
no
_:8132:35 Definite-T 2:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:8132:29 Definite-T 2:Effected by AR cycle 1   no
yes
no
_:8132:36 Definite-T 2:Stage blocked   no
yes
no
_:8132:14 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:20 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: AR cycle 2
_:8132:30 Definite-T 2:Effected by AR cycle 2   no
yes
no
_:8132:37 Definite-T 2:Stage blocked   no
yes
no
_:8132:15 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:21 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: AR cycle 3
_:8132:31 Definite-T 2:Effected by AR cycle 3   no
yes
no
_:8132:38 Definite-T 2:Stage blocked   no
yes
no
_:8132:16 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:22 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: AR cycle>3
_:8132:32 Definite-T 2:Effected by AR cycle gr. 3   no
yes
no
_:8132:39 Definite-T 2:Stage blocked   no
yes
no
_:8132:17 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:23 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: Cold load PU
_:8132:33 Definite-T 2:Effect. b. cold-load pickup   no
yes
no
_:8132:40 Definite-T 2:Stage blocked   no
yes
no
_:8132:18 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:24 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: bin.input
_:8132:34 Definite-T 2:Effected by binary input   no
yes
no
_:8132:41 Definite-T 2:Stage blocked   no
yes
no
_:8132:19 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.150 A to 175.000 A 10.000 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:8132:25 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:2311:102 General:Rotation angle of ref. volt.   -180 ° to 180 ° 45 °
General
_:8341:1 Inverse-T 1:Mode   off
on
test
off
_:8341:2 Inverse-T 1:Operate & flt.rec. blocked   no
yes
no
_:8341:111 Inverse-T 1:Directional mode   forward
reverse
forward
_:8341:11 Inverse-T 1:1-pole operate allowed   no
yes
no
_:8341:8 Inverse-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:8341:113 Inverse-T 1:Non-direc- tional pickup   no
at volt.< & mem.empty
at volt.< & mem.empty
_:8341:110 Inverse-T 1:Directional comparison   no
yes
no
_:8341:112 Inverse-T 1:Release via input signal   no
yes
no
_:8341:10 Inverse-T 1:Blk. by meas.-volt. failure   no
yes
yes
_:8341:26 Inverse-T 1:Dynamic settings   no
yes
no
_:8341:27 Inverse-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:8341:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:130 Inverse-T 1:Type of char- acter. curve      
_:8341:114 Inverse-T 1:Min. time of the curve   0.00 s to 1.00 s 0.00 s
_:8341:131 Inverse-T 1:Reset   instantaneous
disk emulation
disk emulation
_:8341:101 Inverse-T 1:Time dial   0.05 to 15.00 1.00
_:8341:115 Inverse-T 1:Additional time delay   0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:8341:28 Inverse-T 1:Effect. by AR off/n.ready   no
yes
no
_:8341:35 Inverse-T 1:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:8341:29 Inverse-T 1:Effected by AR cycle 1   no
yes
no
_:8341:36 Inverse-T 1:Stage blocked   no
yes
no
_:8341:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:102 Inverse-T 1:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:8341:30 Inverse-T 1:Effected by AR cycle 2   no
yes
no
_:8341:37 Inverse-T 1:Stage blocked   no
yes
no
_:8341:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:103 Inverse-T 1:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:8341:31 Inverse-T 1:Effected by AR cycle 3   no
yes
no
_:8341:38 Inverse-T 1:Stage blocked   no
yes
no
_:8341:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:104 Inverse-T 1:Time dial   0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:8341:32 Inverse-T 1:Effected by AR cycle gr. 3   no
yes
no
_:8341:39 Inverse-T 1:Stage blocked   no
yes
 
_:8341:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:105 Inverse-T 1:Time dial   0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:8341:33 Inverse-T 1:Effect. b. cold-load pickup   no
yes
no
_:8341:40 Inverse-T 1:Stage blocked   no
yes
no
_:8341:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:106 Inverse-T 1:Time dial   0.05 to 15.00 1.00
Dyn.set: bin.input
_:8341:34 Inverse-T 1:Effected by binary input   no
yes
no
_:8341:41 Inverse-T 1:Stage blocked   no
yes
no
_:8341:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8341:107 Inverse-T 1:Time dial   0.05 to 15.00 1.00

Setting parameters for Stage with User-Defined Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode   off
on
test
off
_:2 User curve #:Operate & flt.rec. blocked   no
yes
no
_:110 User curve #:Directional mode   forward
reverse
forward
_:8 User curve #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:112 User curve #:Non-direc- tional pickup   no
at volt.< & mem.empty
at volt.< & mem.empty
_:109 User curve #:Directional comparison   no
yes
no
_:111 User curve #:Release via input signal   no
yes
no
_:10 User curve #:Blk. by meas.-volt. failure   no
yes
no
_:26 User curve #:Dynamic settings   no
yes
no
_:27 User curve #:Blk. w. inrush curr. detect.   no
yes
no
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:115 User curve #:Reset   instantaneous
disk emulation
disk emulation
_:101 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by AR off/n.ready   no
yes
no
_:35 User curve #:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by AR cycle 1   no
yes
no
_:36 User curve #:Stage blocked   no
yes
no
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:102 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by AR cycle 2   no
yes
no
_:37 User curve #:Stage blocked   no
yes
no
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by AR cycle 3   no
yes
no
_:38 User curve #:Stage blocked   no
yes
no
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by AR cycle gr. 3   no
yes
no
_:39 User curve #:Stage blocked   no
yes
no
_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:105 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b. cold-load pickup   no
yes
no
_:40 User curve #:Stage blocked   no
yes
no
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:106 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by binary input   no
yes
no
_:41 User curve #:Stage blocked   no
yes
no
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:107 User curve #:Time dial   0.05 to 15.00 1.00

Logic Diagrams & highlights


Stage-Control Logic Diagram

Stage-Control Logic Diagram

Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases – Basic

Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases - Basic

Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases – Advanced

Logic Diagram of the Directional, Definite-Time Overcurrent Protection, Phases - Advanced

Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases – Basic

Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases - Basic

Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases – Advanced

Logic Diagram of the Directional, Inverse-Time Overcurrent Protection, Phases - Advanced

Minimum Operating Time of the Curve

Minimum Operating Time of the Curve

Pickup and Dropout Behaviors when Using a Directional User-Defined Characteristic Curve

Pickup and Dropout Behaviors when Using a Directional User-Defined Characteristic Curve

Cross-Polarized Voltages for Direction Determination

Cross-Polarized Voltages for Direction Determination

Measurands for Direction Determining

Measurands for Direction Determining

Rotation of the Reference Voltage, Phase-Measuring Element

Rotation of the Reference Voltage, Phase-Measuring Element

Forward Characteristic of the Directional Function, Phase-Measuring Element

Forward Characteristic of the Directional Function, Phase-Measuring Element

Example for settings

Example settings

Parallel Line with Transformers

Parallel Line with Transformers

Cable Runs with Infeed at Both Ends

Cable Runs with Infeed at Both Ends

Selectivity through Directional Comparison Protection

Selectivity through Directional Comparison Protection