Overview
The “Directional overcurrent protection ground” function detects short circuits to ground affecting electric equipment. It ensures selective ground-fault detection for parallel lines or transformers with infeed at one end, and also selective ground-fault detection in cable runs with infeed at both ends or in lines connected to form ring topologies.
For more detailed information on “Directional overcurrent protection ground” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Advanced

Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Basic

Setting Parameters
Genereal Setting Parameters
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:9 | General:Measured value | 3I0 calculated IN measured |
IN measured | |
_:2311:101 | General:Min. voltage V0 or V2 | 0.150 V to 20.000 V | 2.000 V | |
_:2311:102 | General:Rotation angle of ref. volt. | -180 ° to 180 ° | -45 ° | |
_:2311:103 | General:Forward section +/- |
0 ° to 90 ° | 88 ° | |
_:2311:104 | General:Polarization with | zero sequence negative sequence |
zero sequence | |
Setting Parameters for Stage with Definite-Time Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:4861:1 | Definite-T 1:Mode | off on test |
off | |
_:4861:2 | Definite-T 1:Operate & flt.rec. blocked | no yes |
no | |
_:4861:105 | Definite-T 1:Directional mode | forward reverse |
forward | |
_:4861:8 | Definite-T 1:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:4861:104 | Definite-T 1:Directional comparison | no yes |
no | |
_:4861:106 | Definite-T 1:Release via input signal | no yes |
no | |
_:4861:10 | Definite-T 1:Blk. by meas.-volt. failure | no yes |
yes | |
_:4861:26 | Definite-T 1:Dynamic settings | no yes |
no | |
_:4861:27 | Definite-T 1:Blk. w. inrush curr. detect. | no yes |
no | |
_:4861:121 | Definite-T 1:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:4861:3 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:4 | Definite-T 1:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:4861:101 | Definite-T 1:Dropout delay | 0.00 s to 60.00 s | 0.00 s | |
_:4861:6 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.s: AR off/n.rdy | ||||
_:4861:28 | Definite-T 1:Effect. by AR off/n.ready | no yes |
no | |
_:4861:35 | Definite-T 1:Stage blocked | no yes |
no | |
Dyn.set: AR cycle 1 | ||||
_:4861:29 | Definite-T 1:Effected by AR cycle 1 | no yes |
no | |
_:4861:36 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:14 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:20 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.set: AR cycle 2 | ||||
_:4861:30 | Definite-T 1:Effected by AR cycle 2 | no yes |
no | |
_:4861:37 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:15 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:21 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.set: AR cycle 3 | ||||
_:4861:31 | Definite-T 1:Effected by AR cycle 3 | no yes |
no | |
_:4861:38 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:16 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:22 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.s: AR cycle>3 | ||||
_:4861:32 | Definite-T 1:Effected by AR cycle gr. 3 | no yes |
no | |
_:4861:39 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:17 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:23 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.s: Cold load PU | ||||
_:4861:33 | Definite-T 1:Effect. b. cold-load pickup | no yes |
no | |
_:4861:40 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:18 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:24 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Dyn.set: bin.input | ||||
_:4861:34 | Definite-T 1:Effected by binary input | no yes |
no | |
_:4861:41 | Definite-T 1:Stage blocked | no yes |
no | |
_:4861:19 | Definite-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4861:25 | Definite-T 1:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
General | ||||
_:4862:1 | Definite-T 2:Mode | off on test |
off | |
_:4862:2 | Definite-T 2:Operate & flt.rec. blocked | no yes |
no | |
_:4862:105 | Definite-T 2:Directional mode | forward reverse |
forward | |
_:4862:8 | Definite-T 2:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:4862:104 | Definite-T 2:Directional comparison | no yes |
no | |
_:4862:106 | Definite-T 2:Release via input signal | no yes |
no | |
_:4862:10 | Definite-T 2:Blk. by meas.-volt. failure | no yes |
yes | |
_:4862:26 | Definite-T 2:Dynamic settings | no yes |
no | |
_:4862:27 | Definite-T 2:Blk. w. inrush curr. detect. | no yes |
no | |
_:4862:121 | Definite-T 2:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:4862:3 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:4 | Definite-T 2:Dropout ratio | 0.90 to 0.99 | 0.95 | |
_:4862:101 | Definite-T 2:Dropout delay | 0.00 s to 60.00 s | 0.00 s | |
_:4862:6 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.s: AR off/n.rdy | ||||
_:4862:28 | Definite-T 2:Effect. by AR off/n.ready | no yes |
no | |
_:4862:35 | Definite-T 2:Stage blocked | no yes |
no | |
Dyn.set: AR cycle 1 | ||||
_:4862:29 | Definite-T 2:Effected by AR cycle 1 | no yes |
no | |
_:4862:36 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:14 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:20 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.set: AR cycle 2 | ||||
_:4862:30 | Definite-T 2:Effected by AR cycle 2 | no yes |
no | |
_:4862:37 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:15 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:21 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.set: AR cycle 3 | ||||
_:4862:31 | Definite-T 2:Effected by AR cycle 3 | no yes |
no | |
_:4862:38 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:16 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:22 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.s: AR cycle>3 | ||||
_:4862:32 | Definite-T 2:Effected by AR cycle gr. 3 | no yes |
no | |
_:4862:39 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:17 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:23 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.s: Cold load PU | ||||
_:4862:33 | Definite-T 2:Effect. b. cold-load pickup | no yes |
no | |
_:4862:40 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:18 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:24 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Dyn.set: bin.input | ||||
_:4862:34 | Definite-T 2:Effected by binary input | no yes |
no | |
_:4862:41 | Definite-T 2:Stage blocked | no yes |
no | |
_:4862:19 | Definite-T 2:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4862:25 | Definite-T 2:Operate delay | 0.00 s to 60.00 s | 0.10 s | |
Setting Parameters for Stage with Inverse-Time Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:4891:1 | Inverse-T 1:Mode | off on test |
off | |
_:4891:2 | Inverse-T 1:Operate & flt.rec. blocked | no yes |
no | |
_:4891:111 | Inverse-T 1:Directional mode | forward reverse |
forward | |
_:4891:8 | Inverse-T 1:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:4891:110 | Inverse-T 1:Directional comparison | no yes |
no | |
_:4891:112 | Inverse-T 1:Release via input signal | no yes |
no | |
_:4891:10 | Inverse-T 1:Blk. by meas.-volt. failure | no yes |
yes | |
_:4891:26 | Inverse-T 1:Dynamic settings | no yes |
no | |
_:4891:27 | Inverse-T 1:Blk. w. inrush curr. detect. | no yes |
no | |
_:4891:121 | Inverse-T 1:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:4891:3 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:130 | Inverse-T 1:Type of char- acter. curve | |||
_:4891:114 | Inverse-T 1:Min. time of the curve | 0.00 s to 1.00 s | 0.00 s | |
_:4891:131 | Inverse-T 1:Reset | instantaneous disk emulation |
disk emulation | |
_:4891:101 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
_:4891:115 | Inverse-T 1:Additional time delay | 0.00 s to 60.00 s | 0.00 s | |
Dyn.s: AR off/n.rdy | ||||
_:4891:28 | Inverse-T 1:Effect. by AR off/n.ready | no yes |
no | |
_:4891:35 | Inverse-T 1:Stage blocked | no yes |
no | |
Dyn.set: AR cycle 1 | ||||
_:4891:29 | Inverse-T 1:Effected by AR cycle 1 | no yes |
no | |
_:4891:36 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:14 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:102 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Dyn.set: AR cycle 2 | ||||
_:4891:30 | Inverse-T 1:Effected by AR cycle 2 | no yes |
no | |
_:4891:37 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:15 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:103 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Dyn.set: AR cycle 3 | ||||
_:4891:31 | Inverse-T 1:Effected by AR cycle 3 | no yes |
no | |
_:4891:38 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:16 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:104 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Dyn.s: AR cycle>3 | ||||
_:4891:32 | Inverse-T 1:Effected by AR cycle gr. 3 | no yes |
no | |
_:4891:39 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:17 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:105 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Dyn.s: Cold load PU | ||||
_:4891:33 | Inverse-T 1:Effect. b. cold-load pickup | no yes |
no | |
_:4891:40 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:18 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:106 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Dyn.set: bin.input | ||||
_:4891:34 | Inverse-T 1:Effected by binary input | no yes |
no | |
_:4891:41 | Inverse-T 1:Stage blocked | no yes |
no | |
_:4891:19 | Inverse-T 1:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:4891:107 | Inverse-T 1:Time dial | 0.00 to 15.00 | 1.00 | |
Setting Parameters for Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:1 | Log.-inv.-T #:Mode | off on test |
off | |
_:2 | Log.-inv.-T #:Operate & flt.rec. blocked | no yes |
no | |
_:119 | Log.-inv.-T #:Directional mode | forward reverse |
forward | |
_:8 | Log.-inv.-T #:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:118 | Log.-inv.-T #:Directional comparison | no yes |
no | |
_:120 | Log.-inv.-T #:Release via input signal | no yes |
no | |
_:10 | Log.-inv.-T #:Blk. by meas.-volt. failure | no yes |
yes | |
_:26 | Log.-inv.-T #:Dynamic settings | no yes |
no | |
_:27 | Log.-inv.-T #:Blk. w. inrush curr. detect. | no yes |
no | |
_:121 | Log.-inv.-T #:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:3 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:6 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
_:113 | Log.-inv.-T #:Min. time of the curve | 0.000 s to 60.000 s | 1.200 s | |
_:114 | Log.-inv.-T #:Max. time of the curve | 0.000 s to 60.000 s | 5.800 s | |
_:116 | Log.-inv.-T #:Threshold multiplier | 1.00 to 4.00 | 1.10 | |
_:115 | Log.-inv.-T #:Additional time delay | 0.000 s to 60.000 s | 0.000 s | |
Dyn.s: AR off/n.rdy | ||||
_:28 | Log.-inv.-T #:Effect. by AR off/n.ready | no yes |
no | |
_:35 | Log.-inv.-T #:Stage blocked | no yes |
no | |
Dyn.set: AR cycle 1 | ||||
_:29 | Log.-inv.-T #:Effected by AR cycle 1 | no yes |
no | |
_:36 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:14 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:107 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Dyn.set: AR cycle 2 | ||||
_:30 | Log.-inv.-T #:Effected by AR cycle 2 | no yes |
no | |
_:37 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:15 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:108 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Dyn.set: AR cycle 3 | ||||
_:31 | Log.-inv.-T #:Effected by AR cycle 3 | no yes |
no | |
_:38 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:16 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:109 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Dyn.s: AR cycle>3 | ||||
_:32 | Log.-inv.-T #:Effected by AR cycle gr. 3 | no yes |
no | |
_:39 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:17 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:110 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Dyn.s: Cold load PU | ||||
_:33 | Log.-inv.-T #:Effect. b. cold-load pickup | no yes |
no | |
_:40 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:18 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:111 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Dyn.set: bin.input | ||||
_:34 | Log.-inv.-T #:Effected by binary input | no yes |
no | |
_:41 | Log.-inv.-T #:Stage blocked | no yes |
no | |
_:19 | Log.-inv.-T #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:112 | Log.-inv.-T #:Time dial | 0.000 s to 60.000 s | 1.250 s | |
Setting Parameters for Stage with Knee-Point Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:1 | Log.inv.T KP #:Mode | off on test |
off | |
_:2 | Log.inv.T KP #:Operate & flt.rec. blocked | no yes |
no | |
_:108 | Log.inv.T KP #:Direc- tional mode | forward reverse |
forward | |
_:8 | Log.inv.T KP #:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:107 | Log.inv.T KP #:Direc- tional comparison | no yes |
no | |
_:106 | Log.inv.T KP #:Release via input signal | no yes |
no | |
_:10 | Log.inv.T KP #:Blk. by meas.-volt. failure | no yes |
yes | |
_:27 | Log.inv.T KP #:Blk. w. inrush curr. detect. | no yes |
no | |
_:121 | Log.inv.T KP #:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:3 | Log.inv.T KP #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:109 | Log.inv.T KP #:Time dial | 0.05 to 1.50 | 0.20 | |
_:101 | Log.inv.T KP #:Knee- point current | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.300 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.50 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.300 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.50 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.300 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.500 A | ||
_:105 | Log.inv.T KP #:Knee- point time | 0.00 s to 100.00 s | 23.60 s | |
_:102 | Log.inv.T KP #:Current at Min. time | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.500 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 7.50 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.500 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 7.50 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.500 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 7.500 A | ||
_:104 | Log.inv.T KP #:Min. time of the curve | 0.00 s to 30.00 s | 0.80 s | |
_:103 | Log.inv.T KP #:Max. time of the curve | 0.00 s to 200.00 s | 93.00 s | |
Setting Parameters for Stage with User-Defined Characteristic Curve
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:1 | User curve #:Mode | off on test |
off | |
_:2 | User curve #:Operate & flt.rec. blocked | no yes |
no | |
_:113 | User curve #:Directional mode | forward reverse |
forward | |
_:8 | User curve #:Method of measurement | fundamental comp. RMS value |
fundamental comp. | |
_:112 | User curve #:Directional comparison | no yes |
no | |
_:114 | User curve #:Release via input signal | no yes |
no | |
_:10 | User curve #:Blk. by meas.-volt. failure | no yes |
yes | |
_:26 | User curve #:Dynamic settings | no yes |
no | |
_:27 | User curve #:Blk. w. inrush curr. detect. | no yes |
no | |
_:121 | User curve #:Blk. w. 2nd harm. gnd. det. | no yes |
no | |
_:3 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:110 | User curve #:Reset | instantaneous disk emulation |
disk emulation | |
_:101 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.s: AR off/n.rdy | ||||
_:28 | User curve #:Effect. by AR off/n.ready | no yes |
no | |
_:35 | User curve #:Stage blocked | no yes |
no | |
Dyn.set: AR cycle 1 | ||||
_:29 | User curve #:Effected by AR cycle 1 | no yes |
no | |
_:36 | User curve #:Stage blocked | no yes |
no | |
_:14 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:102 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.set: AR cycle 2 | ||||
_:30 | User curve #:Effected by AR cycle 2 | no yes |
no | |
_:37 | User curve #:Stage blocked | no yes |
no | |
_:15 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:103 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.set: AR cycle 3 | ||||
_:31 | User curve #:Effected by AR cycle 3 | no yes |
no | |
_:38 | User curve #:Stage blocked | no yes |
no | |
_:16 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:104 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.s: AR cycle>3 | ||||
_:32 | User curve #:Effected by AR cycle gr. 3 | no yes |
no | |
_:39 | User curve #:Stage blocked | no yes |
no | |
_:17 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:105 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.s: Cold load PU | ||||
_:33 | User curve #:Effect. b. cold-load pickup | no yes |
no | |
_:40 | User curve #:Stage blocked | no yes |
no | |
_:18 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:106 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Dyn.set: bin.input | ||||
_:34 | User curve #:Effected by binary input | no yes |
no | |
_:41 | User curve #:Stage blocked | no yes |
no | |
_:19 | User curve #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.200 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 50 Irated | 0.030 A to 35.000 A | 1.200 A | ||
5 A @ 50 Irated | 0.15 A to 175.00 A | 6.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.200 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 6.000 A | ||
_:107 | User curve #:Time dial | 0.05 to 15.00 | 1.00 | |
Logic Diagrams & highlights
Logic Diagram of Measured-Value Selection

Threshold Setting Range

Logic Diagram of Direction Determination

Measured-Value Definition

Rotation of the Reference Voltage, Directional Overcurrent Protection, Ground Function withZero-Sequence Values

Forward/Reverse Characteristic of the Directional Overcurrent Protection, Ground Function

Example Settings

Logic Diagram of the Stage Control

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Advanced

Threshold Setting Range

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Advanced

Threshold Setting Range

Minimum Operating Time of the Curve

Logic Diagram of the Directional Logarithmic Inverse-Time Overcurrent Protection, Ground

Operate Curve of Logarithmic Inverse-Time Characteristic

Logic Diagram of the Directional Logarithmic Inverse Time with Knee-Point Overcurrent Protection, Ground

Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example of Threshold = 0.004 A)

Logic Diagram of the Directional User-Defined Characteristic Curve Overcurrent Protection, Ground

Pickup and Dropout Behaviors when Using a User-Defined Characteristic Curve

Principle of the Dynamic Settings in the Example of 1st Definite-Time Overcurrent Protection

Influence of the AREC Signals on the Overcurrent-Protection Stage

Influence of the Cold-Load Pickup Detection on the Overcurrent-Protection Stage

Influence of the Binary Input on the Overcurrent-Protection Stage