Table of Contents

Siemens / Directional overcurrent protection ground (ANSI 67N) _ Setting & highlights _ SI5078

Table of Contents

Overview

The “Directional overcurrent protection ground” function detects short circuits to ground affecting electric equipment. It ensures selective ground-fault detection for parallel lines or transformers with infeed at one end, and also selective ground-fault detection in cable runs with infeed at both ends or in lines connected to form ring topologies.

For more detailed information on “Directional overcurrent protection ground” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Advanced

Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Advanced

Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Basic

Structure/Embedding of the Function Directional Overcurrent Protection, Ground – Basic

Setting Parameters


Genereal Setting Parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:9 General:Measured value   3I0 calculated
IN measured
IN measured
_:2311:101 General:Min. voltage V0 or V2   0.150 V to 20.000 V 2.000 V
_:2311:102 General:Rotation angle of ref. volt.   -180 ° to 180 ° -45 °
_:2311:103 General:Forward section
+/-
  0 ° to 90 ° 88 °
_:2311:104 General:Polarization with   zero sequence
negative sequence
zero sequence

Setting Parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:4861:1 Definite-T 1:Mode   off
on
test
off
_:4861:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:4861:105 Definite-T 1:Directional mode   forward
reverse
forward
_:4861:8 Definite-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:4861:104 Definite-T 1:Directional comparison   no
yes
no
_:4861:106 Definite-T 1:Release via input signal   no
yes
no
_:4861:10 Definite-T 1:Blk. by meas.-volt. failure   no
yes
yes
_:4861:26 Definite-T 1:Dynamic settings   no
yes
no
_:4861:27 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:4861:121 Definite-T 1:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:4861:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:4 Definite-T 1:Dropout ratio   0.90 to 0.99 0.95
_:4861:101 Definite-T 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:4861:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:4861:28 Definite-T 1:Effect. by AR off/n.ready   no
yes
no
_:4861:35 Definite-T 1:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:4861:29 Definite-T 1:Effected by AR cycle 1   no
yes
no
_:4861:36 Definite-T 1:Stage blocked   no
yes
no
_:4861:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:20 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:4861:30 Definite-T 1:Effected by AR cycle 2   no
yes
no
_:4861:37 Definite-T 1:Stage blocked   no
yes
no
_:4861:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:21 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:4861:31 Definite-T 1:Effected by AR cycle 3   no
yes
no
_:4861:38 Definite-T 1:Stage blocked   no
yes
no
_:4861:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:22 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:4861:32 Definite-T 1:Effected by AR cycle gr. 3   no
yes
no
_:4861:39 Definite-T 1:Stage blocked   no
yes
no
_:4861:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:23 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:4861:33 Definite-T 1:Effect. b. cold-load pickup   no
yes
no
_:4861:40 Definite-T 1:Stage blocked   no
yes
no
_:4861:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:24 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:4861:34 Definite-T 1:Effected by binary input   no
yes
no
_:4861:41 Definite-T 1:Stage blocked   no
yes
no
_:4861:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4861:25 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
General
_:4862:1 Definite-T 2:Mode   off
on
test
off
_:4862:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:4862:105 Definite-T 2:Directional mode   forward
reverse
forward
_:4862:8 Definite-T 2:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:4862:104 Definite-T 2:Directional comparison   no
yes
no
_:4862:106 Definite-T 2:Release via input signal   no
yes
no
_:4862:10 Definite-T 2:Blk. by meas.-volt. failure   no
yes
yes
_:4862:26 Definite-T 2:Dynamic settings   no
yes
no
_:4862:27 Definite-T 2:Blk. w. inrush curr. detect.   no
yes
no
_:4862:121 Definite-T 2:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:4862:3 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:4 Definite-T 2:Dropout ratio   0.90 to 0.99 0.95
_:4862:101 Definite-T 2:Dropout delay   0.00 s to 60.00 s 0.00 s
_:4862:6 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: AR off/n.rdy
_:4862:28 Definite-T 2:Effect. by AR off/n.ready   no
yes
no
_:4862:35 Definite-T 2:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:4862:29 Definite-T 2:Effected by AR cycle 1   no
yes
no
_:4862:36 Definite-T 2:Stage blocked   no
yes
no
_:4862:14 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:20 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: AR cycle 2
_:4862:30 Definite-T 2:Effected by AR cycle 2   no
yes
no
_:4862:37 Definite-T 2:Stage blocked   no
yes
no
_:4862:15 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:21 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: AR cycle 3
_:4862:31 Definite-T 2:Effected by AR cycle 3   no
yes
no
_:4862:38 Definite-T 2:Stage blocked   no
yes
no
_:4862:16 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:22 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: AR cycle>3
_:4862:32 Definite-T 2:Effected by AR cycle gr. 3   no
yes
no
_:4862:39 Definite-T 2:Stage blocked   no
yes
no
_:4862:17 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:23 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.s: Cold load PU
_:4862:33 Definite-T 2:Effect. b. cold-load pickup   no
yes
no
_:4862:40 Definite-T 2:Stage blocked   no
yes
no
_:4862:18 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:24 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s
Dyn.set: bin.input
_:4862:34 Definite-T 2:Effected by binary input   no
yes
no
_:4862:41 Definite-T 2:Stage blocked   no
yes
no
_:4862:19 Definite-T 2:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4862:25 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.10 s

Setting Parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:4891:1 Inverse-T 1:Mode   off
on
test
off
_:4891:2 Inverse-T 1:Operate & flt.rec. blocked   no
yes
no
_:4891:111 Inverse-T 1:Directional mode   forward
reverse
forward
_:4891:8 Inverse-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:4891:110 Inverse-T 1:Directional comparison   no
yes
no
_:4891:112 Inverse-T 1:Release via input signal   no
yes
no
_:4891:10 Inverse-T 1:Blk. by meas.-volt. failure   no
yes
yes
_:4891:26 Inverse-T 1:Dynamic settings   no
yes
no
_:4891:27 Inverse-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:4891:121 Inverse-T 1:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:4891:3 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:130 Inverse-T 1:Type of char- acter. curve      
_:4891:114 Inverse-T 1:Min. time of the curve   0.00 s to 1.00 s 0.00 s
_:4891:131 Inverse-T 1:Reset   instantaneous
disk emulation
disk emulation
_:4891:101 Inverse-T 1:Time dial   0.00 to 15.00 1.00
_:4891:115 Inverse-T 1:Additional time delay   0.00 s to 60.00 s 0.00 s
Dyn.s: AR off/n.rdy
_:4891:28 Inverse-T 1:Effect. by AR off/n.ready   no
yes
no
_:4891:35 Inverse-T 1:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:4891:29 Inverse-T 1:Effected by AR cycle 1   no
yes
no
_:4891:36 Inverse-T 1:Stage blocked   no
yes
no
_:4891:14 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:102 Inverse-T 1:Time dial   0.00 to 15.00 1.00
Dyn.set: AR cycle 2
_:4891:30 Inverse-T 1:Effected by AR cycle 2   no
yes
no
_:4891:37 Inverse-T 1:Stage blocked   no
yes
no
_:4891:15 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:103 Inverse-T 1:Time dial   0.00 to 15.00 1.00
Dyn.set: AR cycle 3
_:4891:31 Inverse-T 1:Effected by AR cycle 3   no
yes
no
_:4891:38 Inverse-T 1:Stage blocked   no
yes
no
_:4891:16 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:104 Inverse-T 1:Time dial   0.00 to 15.00 1.00
Dyn.s: AR cycle>3
_:4891:32 Inverse-T 1:Effected by AR cycle gr. 3   no
yes
no
_:4891:39 Inverse-T 1:Stage blocked   no
yes
no
_:4891:17 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:105 Inverse-T 1:Time dial   0.00 to 15.00 1.00
Dyn.s: Cold load PU
_:4891:33 Inverse-T 1:Effect. b. cold-load pickup   no
yes
no
_:4891:40 Inverse-T 1:Stage blocked   no
yes
no
_:4891:18 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:106 Inverse-T 1:Time dial   0.00 to 15.00 1.00
Dyn.set: bin.input
_:4891:34 Inverse-T 1:Effected by binary input   no
yes
no
_:4891:41 Inverse-T 1:Stage blocked   no
yes
no
_:4891:19 Inverse-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:4891:107 Inverse-T 1:Time dial   0.00 to 15.00 1.00

Setting Parameters for Stage with Inverse-Time Overcurrent Protection with Logarithmic-Inverse Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:1 Log.-inv.-T #:Mode   off
on
test
off
_:2 Log.-inv.-T #:Operate & flt.rec. blocked   no
yes
no
_:119 Log.-inv.-T #:Directional mode   forward
reverse
forward
_:8 Log.-inv.-T #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:118 Log.-inv.-T #:Directional comparison   no
yes
no
_:120 Log.-inv.-T #:Release via input signal   no
yes
no
_:10 Log.-inv.-T #:Blk. by meas.-volt. failure   no
yes
yes
_:26 Log.-inv.-T #:Dynamic settings   no
yes
no
_:27 Log.-inv.-T #:Blk. w. inrush curr. detect.   no
yes
no
_:121 Log.-inv.-T #:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:3 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:6 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
_:113 Log.-inv.-T #:Min. time of the curve   0.000 s to 60.000 s 1.200 s
_:114 Log.-inv.-T #:Max. time of the curve   0.000 s to 60.000 s 5.800 s
_:116 Log.-inv.-T #:Threshold multiplier   1.00 to 4.00 1.10
_:115 Log.-inv.-T #:Additional time delay   0.000 s to 60.000 s 0.000 s
Dyn.s: AR off/n.rdy
_:28 Log.-inv.-T #:Effect. by AR off/n.ready   no
yes
no
_:35 Log.-inv.-T #:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:29 Log.-inv.-T #:Effected by AR cycle 1   no
yes
no
_:36 Log.-inv.-T #:Stage blocked   no
yes
no
_:14 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 2
_:30 Log.-inv.-T #:Effected by AR cycle 2   no
yes
no
_:37 Log.-inv.-T #:Stage blocked   no
yes
no
_:15 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:108 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
Dyn.set: AR cycle 3
_:31 Log.-inv.-T #:Effected by AR cycle 3   no
yes
no
_:38 Log.-inv.-T #:Stage blocked   no
yes
no
_:16 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
Dyn.s: AR cycle>3
_:32 Log.-inv.-T #:Effected by AR cycle gr. 3   no
yes
no
_:39 Log.-inv.-T #:Stage blocked   no
yes
no
_:17 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
Dyn.s: Cold load PU
_:33 Log.-inv.-T #:Effect. b. cold-load pickup   no
yes
no
_:40 Log.-inv.-T #:Stage blocked   no
yes
no
_:18 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:111 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s
Dyn.set: bin.input
_:34 Log.-inv.-T #:Effected by binary input   no
yes
no
_:41 Log.-inv.-T #:Stage blocked   no
yes
no
_:19 Log.-inv.-T #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:112 Log.-inv.-T #:Time dial   0.000 s to 60.000 s 1.250 s

Setting Parameters for Stage with Knee-Point Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:1 Log.inv.T KP #:Mode   off
on
test
off
_:2 Log.inv.T KP #:Operate & flt.rec. blocked   no
yes
no
_:108 Log.inv.T KP #:Direc- tional mode   forward
reverse
forward
_:8 Log.inv.T KP #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:107 Log.inv.T KP #:Direc- tional comparison   no
yes
no
_:106 Log.inv.T KP #:Release via input signal   no
yes
no
_:10 Log.inv.T KP #:Blk. by meas.-volt. failure   no
yes
yes
_:27 Log.inv.T KP #:Blk. w. inrush curr. detect.   no
yes
no
_:121 Log.inv.T KP #:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:3 Log.inv.T KP #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:109 Log.inv.T KP #:Time dial   0.05 to 1.50 0.20
_:101 Log.inv.T KP #:Knee- point current 1 A @ 100 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.500 A
_:105 Log.inv.T KP #:Knee- point time   0.00 s to 100.00 s 23.60 s
_:102 Log.inv.T KP #:Current at Min. time 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 Log.inv.T KP #:Min. time of the curve   0.00 s to 30.00 s 0.80 s
_:103 Log.inv.T KP #:Max. time of the curve   0.00 s to 200.00 s 93.00 s

Setting Parameters for Stage with User-Defined Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:1 User curve #:Mode   off
on
test
off
_:2 User curve #:Operate & flt.rec. blocked   no
yes
no
_:113 User curve #:Directional mode   forward
reverse
forward
_:8 User curve #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:112 User curve #:Directional comparison   no
yes
no
_:114 User curve #:Release via input signal   no
yes
no
_:10 User curve #:Blk. by meas.-volt. failure   no
yes
yes
_:26 User curve #:Dynamic settings   no
yes
no
_:27 User curve #:Blk. w. inrush curr. detect.   no
yes
no
_:121 User curve #:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:3 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:110 User curve #:Reset   instantaneous
disk emulation
disk emulation
_:101 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: AR off/n.rdy
_:28 User curve #:Effect. by AR off/n.ready   no
yes
no
_:35 User curve #:Stage blocked   no
yes
no
Dyn.set: AR cycle 1
_:29 User curve #:Effected by AR cycle 1   no
yes
no
_:36 User curve #:Stage blocked   no
yes
no
_:14 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:102 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 2
_:30 User curve #:Effected by AR cycle 2   no
yes
no
_:37 User curve #:Stage blocked   no
yes
no
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:103 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by AR cycle 3   no
yes
no
_:38 User curve #:Stage blocked   no
yes
no
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:104 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by AR cycle gr. 3   no
yes
no
_:39 User curve #:Stage blocked   no
yes
no
_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:105 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b. cold-load pickup   no
yes
no
_:40 User curve #:Stage blocked   no
yes
no
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:106 User curve #:Time dial   0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by binary input   no
yes
no
_:41 User curve #:Stage blocked   no
yes
no
_:19 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 6.000 A
_:107 User curve #:Time dial   0.05 to 15.00 1.00

Logic Diagrams & highlights


Logic Diagram of Measured-Value Selection

Logic Diagram of Measured-Value Selection

Threshold Setting Range

Threshold Setting Range

Logic Diagram of Direction Determination

Logic Diagram of Direction Determination

Measured-Value Definition

Measured-Value Definition

Rotation of the Reference Voltage, Directional Overcurrent Protection, Ground Function withZero-Sequence Values

Rotation of the Reference Voltage, Directional Overcurrent Protection, Ground Function withZero-Sequence Values

Forward/Reverse Characteristic of the Directional Overcurrent Protection, Ground Function

Forward/Reverse Characteristic of the Directional Overcurrent Protection, Ground Function

Example Settings

Example Settings

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Advanced

Logic Diagram of the Directional Definite-Time Overcurrent Protection, Ground – Advanced

Threshold Setting Range

Threshold Setting Range

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Basic

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Advanced

Logic Diagram of the Directional Inverse-Time Overcurrent Protection, Ground – Advanced

Threshold Setting Range

Threshold Setting Range

Minimum Operating Time of the Curve

Minimum Operating Time of the Curve

Logic Diagram of the Directional Logarithmic Inverse-Time Overcurrent Protection, Ground

Logic Diagram of the Directional Logarithmic Inverse-Time Overcurrent Protection, Ground

Operate Curve of Logarithmic Inverse-Time Characteristic

Operate Curve of Logarithmic Inverse-Time Characteristic

Logic Diagram of the Directional Logarithmic Inverse Time with Knee-Point Overcurrent Protection, Ground

Logic Diagram of the Directional Logarithmic Inverse Time with Knee-Point Overcurrent Protection, Ground

Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example of Threshold = 0.004 A)

Operate Curve of the Logarithmic Inverse Time with Knee-Point Characteristic (In the Example of Threshold = 0.004 A)

Logic Diagram of the Directional User-Defined Characteristic Curve Overcurrent Protection, Ground

Logic Diagram of the Directional User-Defined Characteristic Curve Overcurrent Protection, Ground

Pickup and Dropout Behaviors when Using a User-Defined Characteristic Curve

Pickup and Dropout Behaviors when Using a User-Defined Characteristic Curve

Principle of the Dynamic Settings in the Example of 1st Definite-Time Overcurrent Protection

Principle of the Dynamic Settings in the Example of 1st Definite-Time Overcurrent Protection

Influence of the AREC Signals on the Overcurrent-Protection Stage

Influence of the AREC Signals on the Overcurrent-Protection Stage

Influence of the Cold-Load Pickup Detection on the Overcurrent-Protection Stage

Influence of the Cold-Load Pickup Detection on the Overcurrent-Protection Stage

Influence of the Binary Input on the Overcurrent-Protection Stage

Influence of the Binary Input on the Overcurrent-Protection Stage

error: Content is protected !!