Siemens / Directional negative sequence protection with current independent time delay (ANSI 46) _ Setting & highlights _ SI5037

Table of Contents

Overview

The “Directional negative sequence protection with current independent time delay” function serves as the backup short-circuit protection for unbalanced faults. With the negative-sequence system, various supervision and protection tasks can be realized.

For more detailed information on “Directional negative sequence protection with current independent time delay” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Directional negative sequence protection with current independent time delay Function

Setting Parameters


Setting parameters of the Function

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Angle forward α   0 ° to 360 ° 338 °
_:2311:102 General:Angle forward β   0 ° to 360 ° 122 °
_:2311:107 General:Min. neg.-seq. voltage V2   0.150 V to 34.000 V 1.213 V
_:2311:106 General:Min. neg.-seq. current I2 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Definite-T 1
_:8101:1 Definite-T 1:Mode   off
on
test
off
_:8101:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:8101:114 Definite-T 1:Directional mode   non-directional
forward
reverse
forward
_:8101:111 Definite-T 1:Stabiliz. w. phase current   0 % to 30 % 10 %
_:8101:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8101:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 0.30 s
_:8101:116 Definite-T 1:Blk. w. inrush curr. detect.   no
yes
no
_:8101:130 Definite-T 1:Blocking by prot. pickup   every pickup
1-phase pickup
multi-phase pickup
no pickup
every pickup
_:8101:129 Definite-T 1:Op.mode at 1p dead time   blocked
non-directional
blocked
_:8101:112 Definite-T 1:Hold mode 1p dead time   0.000 s to 60.000 s 0.040 s
_:8101:140 Definite-T 1:Blocking by   Setting options depend on configuration  

Logic Diagrams & highlights


Stage Control of the Directional Negative-Sequence Protection

Stage Control of the Directional Negative-Sequence Protection

Logic Diagram of the Function Directional Negative-Sequence System Protection with Current-Independent Time Delay

Logic Diagram of the Function Directional Negative-Sequence System Protection with Current-Independent Time Delay

Stabilization with Phase Currents

Stabilization with Phase Currents

Phasor Diagram for Direction Determination with Negative-Sequence System Values

Phasor Diagram for Direction Determination with Negative-Sequence System Values

Logic of Direction Determination

Logic of Direction Determination