Overview

The “Directional intermittent ground fault protection” function detects the intermittent ground faults in grounded, compensated, or isolated cable systems selectively. It can be operated in 2 different modes:
– Operate only by counting directional ground-current pulses
– Operate by integration of the fault current in combination with a directional criterion by counting directional ground-current pulses

For more detailed information on “Directional intermittent ground fault protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Directional intermittent ground fault protection Function

Setting Parameters


Setting parameters for Directional intermittent ground fault protection

Addr. Parameter C Setting Options Default Setting
Stage 1
_:16291:1 Stage 1:Mode   off
on
test
off
_:16291:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:16291:10 Stage 1:Blk. by meas.- volt. failure   no
yes
yes
_:16291:101 Stage 1:Directional mode   forward
reverse
forward
_:16291:102 Stage 1:Pickup mode   with 3I0>
with direction
with 3I0>
_:16291:103 Stage 1:Operating mode   Counter
Integrator and counter
Counter
_:16291:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:16291:105 Stage 1:Pickup extension time   0.00 s to 10.00 s 0.10 s
_:16291:104 Stage 1:No.of pulses for interm.GF   2 to 10 3
_:16291:106 Stage 1:Sum of extended PU times   0.00 s to 100.00 s 20.00 s
_:16291:107 Stage 1:Reset time   1.00 s to 600.00 s 300.00 s
_:16291:108 Stage 1:No. of pulses for operate   2 to 100 5
_:16291:112 Stage 1:Minimum operate delay   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Logic Diagram of the Directional Intermittent Ground-Fault Protection

Logic of the Directional Intermittent Ground-Fault Protection

Logic Diagram of Direction Determination and Pulse Counting

Logic Diagram of Direction Determination and Pulse Counting

Pickup, Operate, and Reset Logic in Operating Mode Counter

Pickup, Operate, and Reset Logic in Operating Mode Counter

Pickup, Operate, and Reset Logic in Operating Mode Integrator and Counter

Pickup, Operate, and Reset Logic in Operating Mode Integrator and Counter