Overview

Generally, the “Directional comparison blocking” scheme compares the direction to a fault at all terminals of the line. Unlike the permissive schemes, the absence of a blocking signal permits operation of the scheme. By default, this scheme uses only a forward-looking over-reaching zone 2 distance element to identify forward faults.

For more detailed information on “Directional comparison blocking” scheme, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D60, L90 42AB Blocking Scheme 1P Function 0 to 1 1 F102 0 (Disabled)
" 42AC Block 1P Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
" 42AD Block 1P Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 30
" 42AE Block 1P Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" 42AF Blocking Scheme 1P Seal In Delay 0 to 65.535 s 0.001 F001 0
" 42B0 Blocking Scheme 1P Gnd Directional Overcurrent Fwd 0 to 4294967295 1 F300 0
" 42B2 Blocking Scheme 1P Gnd Directional Overcurrent Rev 0 to 4294967295 1 F300 0
" 42B4 Blocking Scheme 1P Number of Communication Bits 0 to 2 1 F198 0 (1)
" 42B5 Blocking Scheme 1P Rx1 0 to 4294967295 1 F300 0
" 42B7 Blocking Scheme 1P Rx2 0 to 4294967295 1 F300 0
" 42B9 Blocking Scheme 1P Rx3 0 to 4294967295 1 F300 0
" 42BB Blocking Scheme 1P Rx4 0 to 4294967295 1 F300 0
" 42BD Blocking 1P Target 0 to 2 1 F109 0 (Self-reset)
" 42BE Blocking 1P Event 0 to 1 1 F102 0 (Disabled)
" 42BF Blocking Scheme 1P Block 0 to 4294967295 1 F300 0
" 42C1 Reserved (5 items) 0 to 1 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F198 0 = 1, 1 = 2, 2 = 4

Logics & highlights


Directional blocking scheme logic

Directional blocking scheme logic