GE / Direct underreaching transfer trip (DUTT) _ Element settings & highlights _ GU8211

Table of Contents

Overview

The “Direct underreaching transfer trip” scheme uses an under-reaching Zone 1 distance element to key a transfer trip signal(s) to the remote end(s), where on receipt, the DUTT pilot scheme operates without additional protection supervision. For proper operation of the scheme, the Zone 1 phase and ground distance elements must be enabled, configured, and set per rules of distance relaying.

For more detailed information on “Direct under-reaching transfer trip” scheme, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D60, L90 4260 DUTT Function 0 to 1 1 F102 0 (Disabled)
" 4261 DUTT Seal In Delay 0 to 65.535 s 0.001 F001 0
" 4262 DUTT 1P Number of Communication Bits 0 to 2 1 F198 0 (1)
" 4263 DUTT RX1 0 to 4294967295 1 F300 0
" 4265 DUTT RX2 0 to 4294967295 1 F300 0
" 4267 DUTT RX3 0 to 4294967295 1 F300 0
" 4269 DUTT RX4 0 to 4294967295 1 F300 0
" 426B DUTT 1P Target 0 to 2 1 F109 0 (Self-reset)
" 426C DUTT 1P Event 0 to 1 1 F102 0 (Disabled)
" 426D DUTT 1P Scheme Block 0 to 4294967295 1 F300 0
" 426F Reserved (6 items) 0 to 1 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Direct underreaching transfer trip (DUTT)

Direct underreaching transfer trip (DUTT)