Siemens / Differential protection for phase angle regulating transformer (PST) _ Setting & highlights _ SI5074

Table of Contents

Overview

The “Differential protection for phase angle regulating transformers” function supplements the existing “Transformer differential protection” function (ANSI 87T). Phase-angle regulating transformers are used to control the reactive-power flow and active-power flow in high-voltage power systems.

Power Distribution between 2 Lines when Using Different Phase-Angle Values
Power Distribution between 2 Lines when Using Different Phase-Angle Values

For more detailed information on “Differential protection for phase angle regulating transformer” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Function Blocks

Function Blocks

Instances of the Phase-Angle Regulating Transformer

Instances of the Phase-Angle Regulating Transformer

Setting Parameters


Setting parameters for the Single-Core PST

Addr. Parameter C Setting Options Default Setting
Tap changer
_:91:138 General:Basic position   -128 to 127 8
_:91:139 General:Volt. diff. adja- cent taps   0.000 kV to 800.000 kV 0.000 kV
_:91:44 General:Tap changer   Setting options depend on configuration  
_:91:45 General:Tap changer   Setting options depend on configuration  
Sing.-core PST
_:101 Sing.-core PST:Use AR switch   no
Block function
no
_:102 Sing.-core PST:Blocking time ARS   0.00 s to 60.00 s 12.00 s

Setting parameters for the Special Transformer

Addr. Parameter C Setting Options Default Setting
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
0
_:91:162 General:Phase shift   -180.000 ° to 180.000 ° 0.000 °

Setting parameters for the Two-Core PST

Addr. Parameter C Setting Options Default Setting
Side data
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
0
_:91:162 General:Phase shift   -180.000 ° to 180.000 ° 0.000 °
Two-core PST
_:91:167 General:Two-core side type   Source side
Load side
Exciter primary side
Exciter regulating side
Source side
_:101 Two-core PST:Use AR switch   no
Block function
Block fct. & switch VG
no
_:102 Two-core PST:Blocking time ARS   0.00 s to 60.00 s 12.00 s
_:2311:188 General:Diff function mode   87T primary prot
87T secondary prot
87T primary prot
_:2311:189 General:Series unit ratio   0.001 to 100.000 1.000

Logic Diagrams & highlights


Asymmetrical Single-Core Transformer Scheme, Single-Core PST

Asymmetrical Single-Core Transformer Scheme, Single-Core PST

Instance of the Single-Core PST Function Block

Instance of the Single-Core PST Function Block

Logic of the Single-Core PST Function Block

Logic of the Single-Core PST Function Block

Basic Scheme of a Special Transformer

Basic Scheme of a Special Transformer

Instance of the Special Transformer Function Block

Instance of the Special Transformer Function Block

Logic of the Special Transformer Function Block

Logic of the Special Transformer Function Block

Symmetrical Two-Core Transformer Scheme, Two-Core PST

Symmetrical Two-Core Transformer Scheme, Two-Core PST

Instance of the Two-Core PST Function Block

Instance of the Two-Core PST Function Block

Logic of the Two-Core PST Function Block

Logic of the Two-Core PST Function Block