Overview
The “Current jump detection” function detects jumps in the phase or zero-sequence current (ΔI), and generates an indication when the measurands change by more than a configured threshold value from one system period to the next.
For more detailed information on “Current jump detection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions click here.
Structure/Embedding of the Function

Setting Parameters
Setting parameters for Current jump detection Function
| Addr. | Parameter | C | Setting Options | Default Setting |
| I-jump det. # | ||||
| _:1 | I-jump det. #:Mode | off on test |
off | |
| _:9 | I-jump det. #:Measured value | phase currents zero-sequence current |
phase currents | |
| _:101 | I-jump det. #:Threshold | 1 A @ 100 Irated | 0.030 A to 35.000 A | 0.100 A |
| 5 A @ 100 Irated | 0.15 A to 175.00 A | 0.50 A | ||
| 1 A @ 50 Irated | 0.030 A to 35.000 A | 0.100 A | ||
| 5 A @ 50 Irated | 0.15 A to 175.00 A | 0.50 A | ||
| 1 A @ 1.6 Irated | 0.001 A to 1.600 A | 0.100 A | ||
| 5 A @ 1.6 Irated | 0.005 A to 8.000 A | 0.500 A | ||
| _:102 | I-jump det. #:Minimum pulse length | 0.01 s to 60.00 s | 0.10 s | |
Logic Diagrams & highlights
Current-Jump Detection Logic