Siemens / Circuit breaker failure protection 1-Pole/3-Pole (ANSI 50BF) _ Setting & highlights _ SI5101

Table of Contents

Overview

The “Circuit breaker failure protection” function monitors the tripping of the associated circuit breaker (CB) and generates a backup trip signal if the circuit-breaker fails. The circuit breaker failure protection in the busbar protection has some more tasks.

For more detailed information on “Circuit breaker failure protection 1-Pole/3-Pole” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Function Logic Overview

Function Logic Overview

Setting Parameters


Setting parameters for Circuit breaker failure protection

Addr. Parameter C Setting Options Default Setting
50BF Ad.CBF #
_:1 50BF Ad.CBF #:Mode   off
on
test
on
_:105 50BF Ad.CBF #:Holding int. start signal   no
yes
yes
_:107 50BF Ad.CBF #:Start via binary input   no
2 channel
1 channel
no
_:106 50BF Ad.CBF #:Holding ext. start signal   no
yes
no
_:108 50BF Ad.CBF #:Sup.time
f. release signal
  0.00 s to 1.00 s 0.06 s
_:103 50BF Ad.CBF #:CB
aux.cont. crit. allowed
  no
w. ‘CB pos. closed 3p.’
w. ‘CB pos. closed Lx’
no
_:104 50BF Ad.CBF #:Dropout   with effective criterion
w. aux.c. and curr.crit.
with effective criterion
_:110 50BF Ad.CBF #:Retrip after T1   no
start T2 after T1
parallel start T2, T1
no
_:109 50BF Ad.CBF #:Retrip 1-/3-pole   3-pole
1-pole
3-pole
_:102 50BF Ad.CBF #:Threshold phase current 1 A @ 100 Irated 0.030 A to 35.000 A 0.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 2.50 A
_:101 50BF Ad.CBF #:Threshold sensitive 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
_:111 50BF Ad.CBF #:Delay T1
for 3-pole retrip
  0.000 s to 60.000 s 0.250 s
_:113 50BF Ad.CBF #:Delay T1
for 1-pole retrip
  0.000 s to 60.000 s 0.050 s
_:112 50BF Ad.CBF #:Delay T2
for 3-pole trip
  0.050 s to 60.000 s 0.130 s
_:114 50BF Ad.CBF #:Delay T2
for 1-pole trip
  0.050 s to 60.000 s 0.130 s
_:115 50BF Ad.CBF #:Minimum operate time   0.00 s to 60.00 s 0.10 s
_:120 50BF Ad.CBF #:3I0 crite-
rion
  Direct release
Plausibility check
Plausibility check
_:121 50BF Ad.CBF #:I2 crite- rion   Direct release
Plausibility check
Plausibility check
_:122 50BF Ad.CBF #:Threshold 3I0 dir. release 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
_:123 50BF Ad.CBF #:Threshold I2 dir. release 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
_:124 50BF Ad.CBF #:Monit.
time for BI ">Start"
  0.05 s to 60.00 s 15.00 s
_:125 50BF Ad.CBF
#:Monit.tm. f.BI ">Release"
  0.05 s to 60.00 s 15.00 s
_:154 50BF Ad.CBF #:Imme-
diate dropout
  0
1
true
_:155 50BF Ad.CBF #:BI start external latch   0
1
true

V8.40 Enhancement, Intended for Use with the Distributed Busbar Protection

Addr. Parameter C Setting Options Default Setting
50BF Ad.CBF #
_:153 50BF Ad.CBF #:CBFP
interact. with dBBP
  no
yes
no

Logic Diagrams & highlights


Internal CBFP Start

Internal CBFP Start

Configuration of the External Start of the Circuit-Breaker Failure Protection Function

Configuration of the External Start of the Circuit-Breaker Failure Protection Function

External Start of the Circuit-Breaker Failure Protection Function, Logic

External Start of the Circuit-Breaker Failure Protection Function, Logic

Processing the Starting Signals of CBFP

Processing the Starting Signals of CBFP

Current-Flow Criterion

Current-Flow Criterion

Circuit-Breaker Auxiliary-Contact Criterion

Circuit-Breaker Auxiliary-Contact Criterion

Pickup/Dropout of the Circuit-Breaker Failure Protection Function

Pickup/Dropout of the Circuit-Breaker Failure Protection Function

Delay/Tripping of the Circuit-Breaker Failure Protection Function

Delay/Tripping of the Circuit-Breaker Failure Protection Function

Interaction of Circuit-Breaker Failure Protection and Busbar Protection

Interaction of Circuit-Breaker Failure Protection and Busbar Protection

Characteristic Curves of the Circuit-Breaker Failure Protection

Characteristic Curves of the Circuit-Breaker Failure Protection

Circuit-Breaker Failure Protection with External Pole-Selective Start, Pole-Selective Tripping Repetition, and 3-Pole Tripping (T2)

Circuit-Breaker Failure Protection with External Pole-Selective Start, Pole-Selective Tripping Repetition, and 3-Pole Tripping (T2)