“Capacitor bank diff” function group _ Setting & highlights _ SI5219


Overview

The individual function-group types are stored in the “Capacitor bank diff” function group folder and can be selected. The “Capacitor bank diff.” function group contains the differential protection function and protection-function relevant measured values. In the “Capacitor bank side” function group, all of the functions that are necessary for protecting and supervising a capacitor bank side can be used.

For more detailed information on “Capacitor bank diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of Function-Group Types Capacitor Bank Diff

Function-Group Types Capacitor Bank Diff

Function-Group Type Capacitor Bank Diff


Structure of the Capacitor Bank Diff. Function Group

Structure of the Capacitor Bank Diff. Function Group

Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

Generation of Operate Indication of the Capacitor Bank Diff. Function Group

Generation of Operate Indication of the Capacitor Bank Diff. Function Group

Function-Group Type Capacitor-Bank Side


Structure of the Capacitor Bank Side Function Group

Structure of the Capacitor Bank Side Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:1781:15571:103 Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
Side data
_:1781:14611:130 Side number   not assigned
Side 1
Side 2
Side 3
Side 2
_:1781:14611:210 MI3ph1 usesMeasP with ID   0 to 100 8
_:1781:14611:215 CT mismatch M I-3ph 1   0.010 to 100.000 1.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:15571:101 General:Capacitor reference curr.   1.00 A to 100000.00 A 1000.00 A
_:1781:15571:102 General:Capacitor reference volt.   0.20 kV to 1200.00 kV 400.00 kV
Side data
_:1781:15571:149 General:Neutral point   grounded
isolated
isolated
_:1781:15571:104 General:Winding configuration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:1781:15571:100 General:Vector group numeral   0 to 11 0
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Phase-angle rotation & Vector group numeral

Phase-angle rotation & Vector group numeral

Possible Operational Measured Values of the Capacitor Bank Side Function Group

Possible Operational Measured Values of the Capacitor Bank Side Function Group

Generation of Pickup Indication of the Capacitor Bank Side Function Group

Generation of Pickup Indication of the Capacitor Bank Side Function Group

Generation of Operate Indication of the Capacitor Bank Side Function Group

Generation of Operate Indication of the Capacitor Bank Side Function Group

“Capacitor bank” function group _ Setting & highlights _ SI5218


Overview

In the “Capacitor bank” function group, all the functions that are necessary for protecting and monitoring a capacitor bank can be used. Some of these functions are exclusively used for protecting capacitor banks, and others are universal standard functions which can be used for other protected objects as well.

For more detailed information on “Capacitor bank” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Capacitor Bank Function Group

Structure of the Capacitor Bank Function Group

Setting Parameters


Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:14641:103 General:Rated apparent power   -1.00 MVA to -1.00 MVA 0.00 MVA

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:14641:101 General:Capacitor reference curr.   1.00 A to 100000.00 A 1000.00 A
_:14641:102 General:Capacitor reference volt.   0.20 kV to 1200.00 kV 400.00 kV
Cap.bank data
_:14641:106 General:Capacitor element type   fused
unfused
fused
_:14641:107 General:Blk.cls.cmd.dur. discharge   off
on
off
_:14641:108 General:Discharge time   1 s to 1200 s 300 s
_:14641:109 General:Cap.-bank neutral point   grounded
isolated
isolated
Measurements
_:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Logic Diagrams & highlights


Logic Diagram of Capacitor Bank Device Status and Blocking of Circuit- breaker Closing during Discharging

Logic Diagram of Capacitor Bank Device Status and Blocking of Circuit- breaker Closing during Discharging

Logic Diagram of Processing the Blocked by Discharge Signal

Logic Diagram of Processing the Blocked by Discharge Signal

Operational Measured Values (True RMS) of the Function Group Capacitor Bank

Operational Measured Values (True RMS) of the Function Group Capacitor Bank

Fundamental and Symmetrical Components Measurement Values of the Function Group Capacitor Bank

Fundamental and Symmetrical Components Measurement Values of the Function Group Capacitor Bank

Generation of the Pickup Indication of the Capacitor Bank Function Group

Generation of the Pickup Indication of the Capacitor Bank Function Group

Generation of the Operate Indication of the Capacitor Bank Function Group

Generation of the Operate Indication of the Capacitor Bank Function Group

“Generator diff” function group _ Setting & highlights _ SI5215


Overview

The individual function-group types are stored in the “Generator diff” function group folder. The “Generator diff” function group contains the differential protection function and measured values relevant for protection functions. Device-specific protection and supervision functions can work in the “Generator side” function group. The scope depends on the selected type of protection concept. All of the functions needed for the protection and supervision of the generator are working in the “Generator stator” function group.

For more detailed information on “Generator diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Generator Diff Function-Group Types

Generator Diff Function-Group Types

Function-Group Type Generator Differential Protection


Structure of the Generator Diff Function Group

Structure of the Generator Diff Function Group

Settings

Addr. Parameter C Setting Options Default Setting
General
_:91:149 General:Neutral point   grounded
isolated
grounded

Generation of Pickup Indication of the Generator Diff Function Group

Generation of Pickup Indication of the Generator Diff Function Group

Generation of Operate Indication of the Generator Diff Function Group

Generation of Operate Indication of the Generator Diff Function Group

Function-Group Type Generator Side


Structure of the Generator Side Function Group

Structure of the Generator Side Function Group

Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:101 General:Rated current   -1 A to -1 A 0 A
Side data
_:1781:14611:130 Further settings:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:1781:14611:210 Further settings:MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 Further settings:MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 Further settings:MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 Further settings:MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:214 Further settings:M I-1ph uses MeasP with ID   0 to 100 0
_:1781:14611:215 Further settings:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:1781:14611:216 Further settings:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:1781:14611:217 Further settings:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:1781:14611:218 Further settings:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:1781:14611:219 Further settings:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:1781:14611:220 Further settings:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:1781:14611:221 Further settings:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:1781:14611:222 Further settings:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000
_:1781:14611:223 Further settings:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 46.60 MVA
  General:Rated voltage   0.300 V to 340.000 V 1100.000 V
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of Generator Side Function Group

Possible Operational Measured Values of Generator Side Function Group

Generation of Pickup Indication of the Generator Side Function Group

Generation of Pickup Indication of the Generator Side Function Group

Generation of Operate Indication of the Generator Side Function Group

Generation of Operate Indication of the Generator Side Function Group

Function-Group Type Generator Stator


Structure of the Generator Stator Function Group

Structure of the Generator Stator Function Group

Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:101 General:Rated current   1 A to 100 000 A 1000 A
Side data
_:1781:14611:130 Further settings:Side number   not assigned
Side 1
Side 2
not assigned
_:1781:14611:210 Further settings:MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 Further settings:MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 Further settings:MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 Further settings:MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:214 Further settings:M I-1ph uses MeasP with ID   0 to 100 0
_:1781:14611:215 Further settings:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:1781:14611:216 Further settings:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:1781:14611:217 Further settings:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:1781:14611:218 Further settings:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:1781:14611:219 Further settings:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:1781:14611:220 Further settings:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:1781:14611:221 Further settings:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:1781:14611:222 Further settings:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
:103_:1781:14671 General:Rated apparent power   0.20 MVA to 5000.00 MVA 46.60 MVA
_:1781:14671:102 General:Rated voltage   0.300 V to 340.000 V 1100.000 V
_:1781:14671:101 General:Rated current   -1 A to -1 A 0 A
SGF3Har. conf.
_:1781:14671:105 General:V SGF connected to   neutr. transf.
broken-delta winding
not connected
neutr. transf.
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed
Add.Meas.Value
_:1781:18301:101 Add.Meas.Value:Synchro nous reactance   30.0 % to 300.0 % 180.0 %

Possible Operational Measured Values of Generator Stator Function Group

Possible Operational Measured Values of Generator Stator Function Group

Additional Measured Values

Additional Measured Values

Generation of Pickup Indication of the Generator Stator Function Group

Generation of Pickup Indication of the Generator Stator Function Group

Generation of Operate Indication of the Generator Stator Function Group

Generation of Operate Indication of the Generator Stator Function Group

“Motor diff” function group _ Setting & highlights _ SI5213


Overview

The individual function-group types are stored in the “Motor diff” function group folder. The “Motor differential” function group contains the differential protection function and protection-function-relevant measured values. In the “Motor side” function group, all of the functions that are necessary for protecting and supervising a motor side can be used.

For more detailed information on “Motor diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Function-Group Types Motor differential

Function-Group Types Motor differential

Function-Group Type Motor Differential


Structure of the Motor Differential Protection Function Group

Structure of the Motor Differential Protection Function Group

Generation of Pickup Indication of the Motor Differential Protection Function Group

Generation of Pickup Indication of the Motor Differential Protection Function Group

Generation of Operate Indication of the Motor Differential Protection Function Group

Generation of Operate Indication of the Motor Differential Protection Function Group

Function-Group Type Motor Side


Structure of the Motor Side Function Group

Structure of the Motor Side Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:1781:14671:101 Motor rated current   1 A to 100 000 A 1000 A
Side data
_:1781:14611:130 Side number   not assigned
Side 1
Side 2
Side 3
not assigned
_:1781:14611:210 MI3ph1 usesMeasP with ID   0 to 100 0
_:1781:14611:211 MI3ph2 usesMeasP with ID   0 to 100 0
_:1781:14611:212 MI3ph3 usesMeasP with ID   0 to 100 0
_:1781:14611:213 MI3ph4 usesMeasP with ID   0 to 100 0
_:1781:14611:215 CT mismatch M I-3ph 1   0.010 to 100.000 0.000
_:1781:14611:216 CT mismatch M I-3ph 1 IN   0.010 to 100.000 0.000
_:1781:14611:217 CT mismatch M I-3ph 2   0.010 to 100.000 0.000
_:1781:14611:218 CT mismatch M I-3ph 2 IN   0.010 to 100.000 0.000
_:1781:14611:219 CT mismatch M I-3ph 3   0.010 to 100.000 0.000
_:1781:14611:220 CT mismatch M I-3ph 3 IN   0.010 to 100.000 0.000
_:1781:14611:221 CT mismatch M I-3ph 4   0.010 to 100.000 0.000
_:1781:14611:222 CT mismatch M I-3ph 4 IN   0.010 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:14671:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:1781:14671:102 General:Motor rated voltage   0.40 kVto 800.00 kV 400.00 kV
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Motor Side Function Group

Possible Operational Measured Values of the Motor Side Function Group

Generation of Pickup Indication of the Motor Side Function Group

Generation of Pickup Indication of the Motor Side Function Group

Generation of Operate Indication of the Motor Side Function Group

Generation of Operate Indication of the Motor Side Function Group

“Auto transformer diff” function group _ Setting & highlights _ SI5208


Overview

The individual function-group types are stored in the “Auto transformer diff” function group folder. The “Auto transf. Diff.” function group contains the differential protection function and protection function relevant measured values. In the “Auto transf. auto side” function group all functions required for protection and supervision of an auto transformer auto side can be used. In the “Auto transf. comp. side” all the functions required for protection and supervision of an auto transformer compensation side can be used. In the “Auto transf. ground side” function group all the functions required for protection and supervision of an auto transformer ground side can be used. In the “Auto transf. neutral point” function group all the necessary functions for protection and for supervision of an auto transformer, which are related to a neutral-point current, are used.

For more detailed information on “Auto transformer diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Function-Group Types Auto Transformer Diff.

Function-Group Types Auto Transformer Diff.

Function-Group Type Auto Transformer Differential Protection


Structure of the Auto Transf. Diff. Function Group

Structure of the Auto Transf. Diff. Function Group

Settings

Addr. Parameter C Setting Options Default Setting
General
_:91:149 General:Neutral point   grounded
isolated
grounded

Generation of Pickup Indication of the Auto Transformer Diff. Function Group

Generation of Pickup Indication of the Auto Transformer Diff. Function Group

Generation of Operate Indication of the Auto Transformer Diff. Function Group

Generation of Operate Indication of the Auto Transformer Diff. Function Group

Function-Group Type Auto Transformer Auto Side


Structure of the Auto Transf. Auto Side Function Group

Structure of the Auto Transf. Auto Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.40 kVto 800.00 kV 400.00 kV
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Auto Transformer Auto Side Function Group

Possible Operational Measured Values of the Auto Transformer Auto Side Function Group

Generation of Pickup Indication of the Auto Transformer Auto Side Function Group

Generation of Pickup Indication of the Auto Transformer Auto Side Function Group

Generation of Operate Indication of the Auto Transformer Auto Side Function Group

Generation of Operate Indication of the Auto Transformer Auto Side Function Group

Function-Group Type Auto Transformer Compensation Side


Structure of the Auto Transf. Comp. Side Function Group

Structure of the Auto Transf. Comp. Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:223 General:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.300 V to 340.000 V 40 000.000 V
Side data
_:91:149 General:Neutral point   grounded
isolated
isolated
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
D (Delta)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
1
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group

Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group

Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group

Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group

Generation of Operate Indication of the Auto Transformer Comp. Side Function Group

Generation of Operate Indication of the Auto Transformer Comp. Side Function Group

Function-Group Type Auto Transformer Ground Side


Structure of the Auto Transformer Ground Side Function Group

Structure of the Auto Transformer Ground Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000

Possible Operational Measured Values of the Auto Transformer Ground Side Function Group

Possible Operational Measured Values of the Auto Transformer Ground Side Function Group

Generation of Pickup Indication of the Auto Transformer Ground Side Function Group

Generation of Pickup Indication of the Auto Transformer Ground Side Function Group

Generation of Operate Indication of the Auto Transformer Ground Side Function Group

Generation of Operate Indication of the Auto Transformer Ground Side Function Group

Function-Group Type Auto Transformer Neutral Point


Structure of the Auto Transf. Neutral Point Function Group

Structure of the Auto Transf. Neutral Point Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:9421:101 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:102 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
_:9421:103 General:Rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA
_:9421:104 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:105 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
Power-system data
_:9421:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:9421:223 General:CT mismatch M I-1ph   0.00 to 100.00 0.000

Operational Measured Values of the Auto Transf. Neutral Point Function Group

Operational Measured Values of the Auto Transf. Neutral Point Function Group

Generation of Pickup Indication of the Auto Transf. Neutral Point Function Group

Generation of Pickup Indication of the Auto Transf. Neutral Point Function Group

Generation of Operate Indication of the Auto Transf. Neutral Point Function Group

Generation of Operate Indication of the Auto Transf. Neutral Point Function Group

“Transformer diff” function group _ Setting & highlights _ SI5205


Overview

The individual function group types are stored in the “Transformer diff” function group folder. The “Transf. diff.” function group contains the differential protection function and protection function relevant measured values. In the “Transformer side” function group, all of the functions that are necessary for protecting and monitoring a transformer side can be used. In the “Transf. neutral point” function group all the necessary functions for protection and for supervision of a transformer which are related to a neutral-point current, are used

For more detailed information on “Transformer differential” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Transformer Diff Function-Group Types

Transformer Diff Function-Group Types

Function-Group Type Transformer Differential Protection


Structure of the Transformer Differential Function Group

Structure of the Transformer Differential Function Group

Generation of Pickup Indication of the Transf. Diff. Function Group

Generation of Pickup Indication of the Transf. Diff. Function Group

Generation of Operate Indication of the Transf. Diff. Function Group

Generation of Operate Indication of the Transf. Diff. Function Group

Function-Group Type Transformer Side


Structure of the Transformer Side Function Group

Structure of the Transformer Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
Rated values
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000
_:91:223 General:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.300 V to 340.000 V 40 000.000 V
Side data
_:91:149 General:Neutral point   grounded
isolated
grounded
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
0
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Transformer Side Function Group

Possible Operational Measured Values of the Transformer Side Function Group

Generation of Pickup Indication of the Transformer Side Function Group

Generation of Pickup Indication of the Transformer Side Function Group

Generation of an Operate Indication of the Transformer Side Function Group

Generation of an Operate Indication of the Transformer Side Function Group

Function-Group Type Transformer Neutral Point


Structure of the Transf. Neutral Point Function Group

Structure of the Transf. Neutral Point Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:9421:103 General:Rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA
_:9421:104 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:105 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
Power-system data
_:9421:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:9421:223 General:CT mismatch M I-1ph   0.00 to 100.00 0.000

Operational Measured Values of the Transformer Neutral Point Function Group

Operational Measured Values of the Transformer Neutral Point Function Group

Generation of Pickup Indication of the Transf. Neutral Point Function Group

Generation of Pickup Indication of the Transf. Neutral Point Function Group

Generation of Operate Indication of the Transf. Neutral Point Function Group

Generation of Operate Indication of the Transf. Neutral Point Function Group

“Circuit breaker” function group _ Setting & highlights _ SI5204


Overview

The “Circuit breaker” function group combines all the user functions that relate to a circuit breaker. It contains all of the protection, control, and supervision functions that you can use for this device type.

For more detailed information on “Circuit breaker” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Circuit-Breaker Function Group

Structure of the Circuit-Breaker Function Group

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
Ref. for %-values
_:2311:101 General:Rated normal current   0.20 A to 100000.00 A 1000.00 A
_:2311:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Breaker settings
_:2311:112 General:Current thresh. CB open 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:136 General:Op. mode BFP   unbalancing
I> query
unbalancing

Setting parameters for Trip logic

Addr. Parameter C Setting Options Default Setting
Trip logic
_:103 Trip logic:Reset of trip command   with I<
with I< & aux.contact
with dropout
with I<

Setting parameters for Circuit breaker auxiliary contacts

Addr. Parameter C Setting Options Default Setting
Circuit break.
_:101 Circuit break.:Output time   0.02 s to 1800.00 s 0.10 s
_:105 Circuit break.:Indicat. of breaking values   with trip
always
always

Setting parameters for Manual close detection

Addr. Parameter C Setting Options Default Setting
Manual close
_:101 Manual close:Action time   0.01 s to 60.00 s 0.30 s
_:102 Manual close:CB open dropout delay   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Trip Command

Trip Command

Trip-Command Reset

Trip-Command Reset

Tripping, Opening, and Closing the Circuit Breaker

Tripping, Opening, and Closing the Circuit Breaker

Detection of the Circuit-Breaker Information

Detection of the Circuit-Breaker Information

Definitive Tripping and Circuit-Breaker Tripping Alarm Suppression

Definitive Tripping and Circuit-Breaker Tripping Alarm Suppression

Breaking Information

Breaking Information

Statistics Information About the Circuit Breaker

Statistics Information About the Circuit Breaker

Routings for Activation of the Circuit Breaker

Routings for Activation of the Circuit Breaker

Routing for Analysis of the Circuit-Breaker Switch Position

Routing for Analysis of the Circuit-Breaker Switch Position

Circuit-Breaker Tripping Alarm Suppression

Circuit-Breaker Tripping Alarm Suppression

The Circuit-Breaker Condition Position Function

Overview of the Circuit-Breaker Condition Position Function

Logic for Manual Closure Detection


Connection of the Input Signal to the Control Circuit of the Circuit-Breaker Closing Coil


“Voltage 3 phase” function group _ Setting & highlights _ SI5203


Overview

In the “Voltage 3 phase” function group, all functions can be used for protecting and for monitoring a protected object or equipment which allows a 3-phase voltage measurement. The function group also contains the operational measurement for the protected object or equipment.

For more detailed information on “Voltage 3 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Voltage 3-Phase Function Group

Structure of the Voltage 3-Phase Function Group

Setting Parameters


Setting parameters for Voltage 3-Phase Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9421:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV

Logic Diagrams & highlights


Operational Measured Values of the Voltage 3-Phase Function Group

Operational Measured Values of the Voltage 3-Phase Function Group

“Line” function group _ Setting & highlights _ SI5200


Overview

In the “Line” function group, all of the functions that are necessary for protecting and monitoring a line can be used. The Line function group also contains the measuring functions.

For more detailed information on “Line” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Line Function Group

Structure of the Line Function Group

Structure/Embedding of the Process Monitor (FG Line)

Structure/Embedding of the Process Monitor (FG Line)

Setting Parameters


Setting parameters for Line Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9001:101 General:Rated current   1 A to 100000 A 1000 A
_:9001:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Line data
_:9001:149 General:Neutral point   grounded
suppress. coil grounded
isolated
grounded
_:9001:112 General:C1 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:148 General:C0 per length unit 1 A 0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A 0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:113 General:X per length unit 1 A 0.0010 Ω/km to 9.5000 Ω/km 0.0525 Ω/km
5 A 0.0002 Ω/km to 1.9000 Ω/km 0.0105 Ω/km
_:9001:114 General:Line length   0.10 km to 1000.00 km 60.00 km
_:9001:108 General:Line angle   10.00 ° to 89.00 ° 85.00 °
_:9001:104 General:Kr   -0.33 to 11.00 1.00
_:9001:105 General:Kx   -0.33 to 11.00 1.00
_:9001:118 General:K0   0.000 to 11.000 1.000
_:9001:150 General:Angle (K0)   -180.00 ° to 180.00 ° 0.00 °
_:9001:106 General:KmR   0.00 to 8.00 1.00
_:9001:107 General:KmX   0.00 to 8.00 1.00
_:9001:124 General:Km0   0.000 to 8.000 1.000
_:9001:125 General:Angle (Km0)   -180.00 ° to 180.00 ° 0.00 °
_:9001:109 General:Gnd.curr.ratio(Mut Comp)   50 % to 95 % 85 %
_:9001:119 General:CT saturation detection   no
yes
no
_:9001:120 General:CT saturation threshold 1 A 0.030 A to 125.000 A 10.000 A
5 A 0.150 A to 625.000 A 50.000 A
_:9001:111 General:Series compensa- tion   no
yes
no
_:9001:110 General:Series capacit. reactance 1 A 0.000 Ω to 600.000 Ω 0.000 Ω
5 A 0.000 Ω to 120.000 Ω 0.000 Ω
Closure detec.
_:1131:4681:10 1 Closure detec.:Operating mode   Manual close only
I open and V open
CB and I open
I open
Manual close only
_:1131:4681:10 2 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:1131:4681:10 3 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s
1pol.open det.
_:1131:4711:10 1 1pol.open det.:Operating mode   off
with measurement
CB and I open
with measurement

Setting parameters for Process Monitor: Current-Flow Criterion

Addr. Parameter C Setting Options Default Setting
Breaker settings
_:2311:112 General:Current thresh. CB open 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:2311:136 General:Op. mode BFP   unbalancing
I> query
unbalancing

Setting parameters for Process Monitor: Closure Detection

Addr. Parameter C Setting Options Default Setting
Closure detec.
_:4681:101 Closure detec.:Operating mode   Manual close only
Iopen,Vopen,ManCl
CB, Iopen, ManCl
Iopen, ManCl
Manual close only
_:4681:102 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:4681:103 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s

Setting parameters for Process Monitor: Voltage Criterion (Optional)

Addr. Parameter C Setting Options Default Setting
Volt.criterion
_:101 Volt.criterion:Threshold U open   0.300 V to 170.000 V 51.960 V

Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)

Addr. Parameter C Setting Options Default Setting
Cold-load PU
_:1 Cold-load PU:Mode   off
on
test
off
_:101 Cold-load PU:Operating mode   I open
CB and I open
I open
_:102 Cold-load PU:Dropout threshold current 1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout delay curr.crit.   1sto600 s 600s
_:104 Cold-load PU:Dropout delay CB closed   1 s to 21600 s 3600 s
_:105 Cold-load PU:Min. CB- open time   0 s to 21600 s 3600 s

Setting parameters for Process Monitor:Closure detec.

Addr. Parameter C Setting Options Default Setting
Closure detec.
_:4681:101 Closure detec.:Operating mode   Manual close only
CB and I open
I open and V open
I open
Manual close only
_:4681:102 Closure detec.:Action time after closure   0.01 s to 60.00 s 0.05 s
_:4681:103 Closure detec.:Min. time feeder open   0.05 s to 60.00 s 0.25 s

Logic Diagrams & highlights


Operational Measured Values of the Function Group Line

Operational Measured Values of the Function Group Line

Generation of a Pickup Indication of the Line Function Group

Generation of a Pickup Indication of the Line Function Group

Generation of an Operate Indication of the Line Function Group

Generation of an Operate Indication of the Line Function Group

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Closure-Detection Function Block

Logic Diagram of the Closure-Detection Function Bloc

Logic Diagram of the 1-Pole Open Detector Function Block

Logic Diagram of the 1-Pole Open Detector Function Block

Logic Diagram of the Voltage-Criterion Function Block

Logic Diagram of the Voltage-Criterion Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block

“Voltage current 3 phase” function group _ Setting & highlights _ SI5201


Overview

In the “Voltage current 3 phase” function group, you can use all the functions for protection and supervision of a protected object or equipment that allows 3-phase current and voltage measurement. The function group also contains the operational measurement for the protected object or equipment.

For more detailed information on “Voltage current 3 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Voltage-Current 3-Phase Function Group

Structure of the Voltage-Current 3-Phase Function Group

Structure/Embedding of the Process Monitor Function

Structure/Embedding of the Process Monitor Function

Setting Parameters


Write-Protected Settings for Voltage-Current 3-Phase Function Group

Addr. Parameters C Range of Values Default Setting
Network data
_:103 General:rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA

Setting parameters for Voltage-Current 3-Phase Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9451:101 General:Rated current   1.00 A to 100000.00 A 1000.00 A
_:9451:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Power-system data
_:9451:149 General:Power-sys. neutral point   grounded
suppress. coil grounded
isolated
grounded
Measurements
_:9451:158 General:P, Q sign   not reversed
reversed
not reversed

Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)

Addr. Parameter C Setting Options Default Setting
Cold-load PU
_:1 Cold-load PU:Mode   off
on
test
off
_:101 Cold-load PU:Operating mode   I open
CB and I open
I open
_:102 Cold-load PU:Dropout threshold current 1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout delay curr.crit.   1 s to 600 s 600 s
_:104 Cold-load PU:Dropout delay CB closed   1 s to 21600 s 3600 s
_:105 Cold-load PU:Min. CB- open time   0 s to 21600 s 3600 s

Logic Diagrams & highlights


Operational Measured Values of the Voltage-Current 3-Phase Function Group

Operational Measured Values of the Voltage-Current 3-Phase Function Group

Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group

Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group

Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group

Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of Closure Detection

Logic Diagram of Closure Detection

Logic Diagram of the Cold-Load Pickup Detection Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block