The individual function-group types are stored in the “Capacitor bank diff” function group folder and can be selected. The “Capacitor bank diff.” function group contains the differential protection function and protection-function relevant measured values. In the “Capacitor bank side” function group, all of the functions that are necessary for protecting and supervising a capacitor bank side can be used.
For more detailed information on “Capacitor bank diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of Function-Group Types Capacitor Bank Diff
Function-Group Type Capacitor Bank Diff
Structure of the Capacitor Bank Diff. Function Group
Generation of Pickup Indication of the Capacitor Bank Diff. Function Group
Generation of Operate Indication of the Capacitor Bank Diff. Function Group
Function-Group Type Capacitor-Bank Side
Structure of the Capacitor Bank Side Function Group
Write-Protected Settings
Addr.
Parameter
C
Range of Values
Default Setting
Rated values
_:1781:15571:103
Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
Side data
_:1781:14611:130
Side number
not assigned
Side 1
Side 2
Side 3
Side 2
_:1781:14611:210
MI3ph1 usesMeasP with ID
0 to 100
8
_:1781:14611:215
CT mismatch M I-3ph 1
0.010 to 100.000
1.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:1781:15571:101
General:Capacitor reference curr.
1.00 A to 100000.00 A
1000.00 A
_:1781:15571:102
General:Capacitor reference volt.
0.20 kV to 1200.00 kV
400.00 kV
Side data
_:1781:15571:149
General:Neutral point
grounded
isolated
isolated
_:1781:15571:104
General:Winding configuration
Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:1781:15571:100
General:Vector group numeral
0 to 11
0
Measurements
_:1781:14611:158
Further settings:P, Q sign
not reversed
reversed
not reversed
Phase-angle rotation & Vector group numeral
Possible Operational Measured Values of the Capacitor Bank Side Function Group
Generation of Pickup Indication of the Capacitor Bank Side Function Group
Generation of Operate Indication of the Capacitor Bank Side Function Group
In the “Capacitor bank” function group, all the functions that are necessary for protecting and monitoring a capacitor bank can be used. Some of these functions are exclusively used for protecting capacitor banks, and others are universal standard functions which can be used for other protected objects as well.
For more detailed information on “Capacitor bank” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Capacitor Bank Function Group
Setting Parameters
Write-Protected Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:14641:103
General:Rated apparent power
-1.00 MVA to -1.00 MVA
0.00 MVA
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:14641:101
General:Capacitor reference curr.
1.00 A to 100000.00 A
1000.00 A
_:14641:102
General:Capacitor reference volt.
0.20 kV to 1200.00 kV
400.00 kV
Cap.bank data
_:14641:106
General:Capacitor element type
fused
unfused
fused
_:14641:107
General:Blk.cls.cmd.dur. discharge
off
on
off
_:14641:108
General:Discharge time
1 s to 1200 s
300 s
_:14641:109
General:Cap.-bank neutral point
grounded
isolated
isolated
Measurements
_:14611:158
Further settings:P, Q sign
not reversed
reversed
not reversed
Logic Diagrams & highlights
Logic Diagram of Capacitor Bank Device Status and Blocking of Circuit- breaker Closing during Discharging
Logic Diagram of Processing the Blocked by Discharge Signal
Operational Measured Values (True RMS) of the Function Group Capacitor Bank
Fundamental and Symmetrical Components Measurement Values of the Function Group Capacitor Bank
Generation of the Pickup Indication of the Capacitor Bank Function Group
Generation of the Operate Indication of the Capacitor Bank Function Group
The individual function-group types are stored in the “Generator diff” function group folder. The “Generator diff” function group contains the differential protection function and measured values relevant for protection functions. Device-specific protection and supervision functions can work in the “Generator side” function group. The scope depends on the selected type of protection concept. All of the functions needed for the protection and supervision of the generator are working in the “Generator stator” function group.
For more detailed information on “Generator diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Generator Diff Function-Group Types
Function-Group Type Generator Differential Protection
Structure of the Generator Diff Function Group
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:91:149
General:Neutral point
grounded
isolated
grounded
Generation of Pickup Indication of the Generator Diff Function Group
Generation of Operate Indication of the Generator Diff Function Group
Function-Group Type Generator Side
Structure of the Generator Side Function Group
Write-Protected Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:1781:14671:101
General:Rated current
-1 A to -1 A
0 A
Side data
_:1781:14611:130
Further settings:Side number
not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:1781:14611:210
Further settings:MI3ph1 usesMeasP with
ID
0 to 100
0
_:1781:14611:211
Further settings:MI3ph2 usesMeasP with
ID
0 to 100
0
_:1781:14611:212
Further settings:MI3ph3 usesMeasP with
ID
0 to 100
0
_:1781:14611:213
Further settings:MI3ph4 usesMeasP with
ID
0 to 100
0
_:1781:14611:214
Further settings:M I-1ph uses MeasP
with ID
0 to 100
0
_:1781:14611:215
Further settings:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:1781:14611:216
Further settings:CT mismatch M I-3ph 1
IN
0.000 to 100.000
0.000
_:1781:14611:217
Further settings:CT mismatch M I-3ph 2
0.000 to 100.000
0.000
_:1781:14611:218
Further settings:CT mismatch M I-3ph 2
IN
0.000 to 100.000
0.000
_:1781:14611:219
Further settings:CT mismatch M I-3ph 3
0.000 to 100.000
0.000
_:1781:14611:220
Further settings:CT mismatch M I-3ph 3
IN
0.000 to 100.000
0.000
_:1781:14611:221
Further settings:CT mismatch M I-3ph 4
0.000 to 100.000
0.000
_:1781:14611:222
Further settings:CT mismatch M I-3ph 4
IN
0.000 to 100.000
0.000
_:1781:14611:223
Further settings:CT mismatch M I-1ph
0.000 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:1781:14671:103
General:Rated apparent power
0.20 MVA to 5000.00 MVA
46.60 MVA
General:Rated voltage
0.300 V to 340.000 V
1100.000 V
Measurements
_:1781:14611:158
Further settings:P, Q sign
not reversed
reversed
not reversed
Possible Operational Measured Values of Generator Side Function Group
Generation of Pickup Indication of the Generator Side Function Group
Generation of Operate Indication of the Generator Side Function Group
Function-Group Type Generator Stator
Structure of the Generator Stator Function Group
Write-Protected Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:1781:14671:101
General:Rated current
1 A to 100 000 A
1000 A
Side data
_:1781:14611:130
Further settings:Side number
not assigned
Side 1
Side 2
not assigned
_:1781:14611:210
Further settings:MI3ph1 usesMeasP with ID
0 to 100
0
_:1781:14611:211
Further settings:MI3ph2 usesMeasP with ID
0 to 100
0
_:1781:14611:212
Further settings:MI3ph3 usesMeasP with ID
0 to 100
0
_:1781:14611:213
Further settings:MI3ph4 usesMeasP with ID
0 to 100
0
_:1781:14611:214
Further settings:M I-1ph uses MeasP with ID
0 to 100
0
_:1781:14611:215
Further settings:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:1781:14611:216
Further settings:CT mismatch M I-3ph 1
IN
0.000 to 100.000
0.000
_:1781:14611:217
Further settings:CT mismatch M I-3ph 2
0.000 to 100.000
0.000
_:1781:14611:218
Further settings:CT mismatch M I-3ph 2
IN
0.000 to 100.000
0.000
_:1781:14611:219
Further settings:CT mismatch M I-3ph 3
0.000 to 100.000
0.000
_:1781:14611:220
Further settings:CT mismatch M I-3ph 3
IN
0.000 to 100.000
0.000
_:1781:14611:221
Further settings:CT mismatch M I-3ph 4
0.000 to 100.000
0.000
_:1781:14611:222
Further settings:CT mismatch M I-3ph 4
IN
0.000 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
:103_:1781:14671
General:Rated apparent power
0.20 MVA to 5000.00 MVA
46.60 MVA
_:1781:14671:102
General:Rated voltage
0.300 V to 340.000 V
1100.000 V
_:1781:14671:101
General:Rated current
-1 A to -1 A
0 A
SGF3Har. conf.
_:1781:14671:105
General:V SGF connected to
neutr. transf.
broken-delta winding
not connected
neutr. transf.
Measurements
_:1781:14611:158
Further settings:P, Q sign
not reversed
reversed
not reversed
Add.Meas.Value
_:1781:18301:101
Add.Meas.Value:Synchro nous reactance
30.0 % to 300.0 %
180.0 %
Possible Operational Measured Values of Generator Stator Function Group
Additional Measured Values
Generation of Pickup Indication of the Generator Stator Function Group
Generation of Operate Indication of the Generator Stator Function Group
The individual function-group types are stored in the “Motor diff” function group folder. The “Motor differential” function group contains the differential protection function and protection-function-relevant measured values. In the “Motor side” function group, all of the functions that are necessary for protecting and supervising a motor side can be used.
For more detailed information on “Motor diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Function-Group Types Motor differential
Function-Group Type Motor Differential
Structure of the Motor Differential Protection Function Group
Generation of Pickup Indication of the Motor Differential Protection Function Group
Generation of Operate Indication of the Motor Differential Protection Function Group
Function-Group Type Motor Side
Structure of the Motor Side Function Group
Write-Protected Settings
Addr.
Parameter
C
Range of Values
Default Setting
Rated values
_:1781:14671:101
Motor rated current
1 A to 100 000 A
1000 A
Side data
_:1781:14611:130
Side number
not assigned
Side 1
Side 2
Side 3
not assigned
_:1781:14611:210
MI3ph1 usesMeasP with ID
0 to 100
0
_:1781:14611:211
MI3ph2 usesMeasP with ID
0 to 100
0
_:1781:14611:212
MI3ph3 usesMeasP with ID
0 to 100
0
_:1781:14611:213
MI3ph4 usesMeasP with ID
0 to 100
0
_:1781:14611:215
CT mismatch M I-3ph 1
0.010 to 100.000
0.000
_:1781:14611:216
CT mismatch M I-3ph 1 IN
0.010 to 100.000
0.000
_:1781:14611:217
CT mismatch M I-3ph 2
0.010 to 100.000
0.000
_:1781:14611:218
CT mismatch M I-3ph 2 IN
0.010 to 100.000
0.000
_:1781:14611:219
CT mismatch M I-3ph 3
0.010 to 100.000
0.000
_:1781:14611:220
CT mismatch M I-3ph 3 IN
0.010 to 100.000
0.000
_:1781:14611:221
CT mismatch M I-3ph 4
0.010 to 100.000
0.000
_:1781:14611:222
CT mismatch M I-3ph 4 IN
0.010 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:1781:14671:103
General:Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
_:1781:14671:102
General:Motor rated voltage
0.40 kVto 800.00 kV
400.00 kV
Measurements
_:1781:14611:158
Further settings:P, Q sign
not reversed
reversed
not reversed
Possible Operational Measured Values of the Motor Side Function Group
Generation of Pickup Indication of the Motor Side Function Group
Generation of Operate Indication of the Motor Side Function Group
The individual function-group types are stored in the “Auto transformer diff” function group folder. The “Auto transf. Diff.” function group contains the differential protection function and protection function relevant measured values. In the “Auto transf. auto side” function group all functions required for protection and supervision of an auto transformer auto side can be used. In the “Auto transf. comp. side” all the functions required for protection and supervision of an auto transformer compensation side can be used. In the “Auto transf. ground side” function group all the functions required for protection and supervision of an auto transformer ground side can be used. In the “Auto transf. neutral point” function group all the necessary functions for protection and for supervision of an auto transformer, which are related to a neutral-point current, are used.
For more detailed information on “Auto transformer diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Function-Group Types Auto Transformer Diff.
Function-Group Type Auto Transformer Differential Protection
Structure of the Auto Transf. Diff. Function Group
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:91:149
General:Neutral point
grounded
isolated
grounded
Generation of Pickup Indication of the Auto Transformer Diff. Function Group
Generation of Operate Indication of the Auto Transformer Diff. Function Group
Function-Group Type Auto Transformer Auto Side
Structure of the Auto Transf. Auto Side Function Group
Write-Protected Settings
Addr.
Parameters
C
Range of Values
Default Setting
Rated values
_:91:101
General:Rated current
1 A to 100 000 A
1 000 A
Side data
_:91:130
General:Side number
not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210
General:MI3ph1 uses- MeasP with ID
0 to 100
0
_:91:211
General:MI3ph2 uses- MeasP with ID
0 to 100
0
_:91:212
General:MI3ph3 uses- MeasP with ID
0 to 100
0
_:91:213
General:MI3ph4 uses- MeasP with ID
0 to 100
0
_:91:215
General:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:91:216
General:CT mismatch M I-3ph 1 IN
0.000 to 100.000
0.000
_:91:217
General:CT mismatch M I-3ph 2
0.000 to 100.000
0.000
_:91:218
General:CT mismatch M I-3ph 2 IN
0.000 to 100.000
0.000
_:91:219
General:CT mismatch M I-3ph 3
0.000 to 100.000
0.000
_:91:220
General:CT mismatch M I-3ph 3 IN
0.000 to 100.000
0.000
_:91:221
General:CT mismatch M I-3ph 4
0.000 to 100.000
0.000
_:91:222
General:CT mismatch M I-3ph 4 IN
0.000 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:91:103
General:Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
_:91:102
General:Rated voltage
0.40 kVto 800.00 kV
400.00 kV
Measurements
_:91:158
General:P, Q sign
not reversed
reversed
not reversed
Possible Operational Measured Values of the Auto Transformer Auto Side Function Group
Generation of Pickup Indication of the Auto Transformer Auto Side Function Group
Generation of Operate Indication of the Auto Transformer Auto Side Function Group
Function-Group Type Auto Transformer Compensation Side
Structure of the Auto Transf. Comp. Side Function Group
Write-Protected Settings
Addr.
Parameters
C
Range of Values
Default Setting
Rated values
_:91:101
General:Rated current
1 A to 100 000 A
1 000 A
Side data
_:91:130
General:Side number
not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210
General:MI3ph1 uses- MeasP with ID
0 to 100
0
_:91:211
General:MI3ph2 uses- MeasP with ID
0 to 100
0
_:91:212
General:MI3ph3 uses- MeasP with ID
0 to 100
0
_:91:213
General:MI3ph4 uses- MeasP with ID
0 to 100
0
_:91:214
General:M I-1ph uses MeasP with ID
0 to 100
0
_:91:215
General:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:91:216
General:CT mismatch M I-3ph 1 IN
0.000 to 100.000
0.000
_:91:217
General:CT mismatch M I-3ph 2
0.000 to 100.000
0.000
_:91:218
General:CT mismatch M I-3ph 2 IN
0.000 to 100.000
0.000
_:91:219
General:CT mismatch M I-3ph 3
0.000 to 100.000
0.000
_:91:220
General:CT mismatch M I-3ph 3 IN
0.000 to 100.000
0.000
_:91:221
General:CT mismatch M I-3ph 4
0.000 to 100.000
0.000
_:91:222
General:CT mismatch M I-3ph 3 IN
0.000 to 100.000
0.000
_:91:223
General:CT mismatch M I-1ph
0.000 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:91:103
General:Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
_:91:102
General:Rated voltage
0.300 V to 340.000 V
40 000.000 V
Side data
_:91:149
General:Neutral point
grounded
isolated
isolated
_:91:104
General:Winding config- uration
Y (Wye)
D (Delta)
Z (Zig-Zag)
D (Delta)
_:91:163
General:Vector group numeral
0
1
2
3
4
5
6
7
8
9
10
11
user-defined
1
Measurements
_:91:158
General:P, Q sign
not reversed
reversed
not reversed
Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group
Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group
Generation of Operate Indication of the Auto Transformer Comp. Side Function Group
Function-Group Type Auto Transformer Ground Side
Structure of the Auto Transformer Ground Side Function Group
Write-Protected Settings
Addr.
Parameters
C
Range of Values
Default Setting
Rated values
_:91:101
General:Rated current
1 A to 100 000 A
1 000 A
Side data
_:91:130
General:Side number
not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210
General:MI3ph1 uses- MeasP with ID
0 to 100
0
_:91:215
General:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:91:216
General:CT mismatch M I-3ph 1 IN
0.000 to 100.000
0.000
Possible Operational Measured Values of the Auto Transformer Ground Side Function Group
Generation of Pickup Indication of the Auto Transformer Ground Side Function Group
Generation of Operate Indication of the Auto Transformer Ground Side Function Group
Function-Group Type Auto Transformer Neutral Point
Structure of the Auto Transf. Neutral Point Function Group
Write-Protected Settings
Addr.
Parameter
C
Range of Values
Default Setting
Rated values
_:9421:101
General:Rated current
1 A to 100 000 A
1 000 A
_:9421:102
General:Rated voltage
0.20 kV to 1 200.00 kV
400 kV
_:9421:103
General:Rated apparent power
0.20 MVA to 5 000.00 MVA
692.82 MVA
_:9421:104
General:Rated current
1 A to 100 000 A
1 000 A
_:9421:105
General:Rated voltage
0.20 kV to 1 200.00 kV
400 kV
Power-system data
_:9421:214
General:M I-1ph uses MeasP with ID
0 to 100
0
_:9421:223
General:CT mismatch M I-1ph
0.00 to 100.00
0.000
Operational Measured Values of the Auto Transf. Neutral Point Function Group
Generation of Pickup Indication of the Auto Transf. Neutral Point Function Group
Generation of Operate Indication of the Auto Transf. Neutral Point Function Group
The individual function group types are stored in the “Transformer diff” function group folder. The “Transf. diff.” function group contains the differential protection function and protection function relevant measured values. In the “Transformer side” function group, all of the functions that are necessary for protecting and monitoring a transformer side can be used. In the “Transf. neutral point” function group all the necessary functions for protection and for supervision of a transformer which are related to a neutral-point current, are used
For more detailed information on “Transformer differential” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Transformer Diff Function-Group Types
Function-Group Type Transformer Differential Protection
Structure of the Transformer Differential Function Group
Generation of Pickup Indication of the Transf. Diff. Function Group
Generation of Operate Indication of the Transf. Diff. Function Group
Function-Group Type Transformer Side
Structure of the Transformer Side Function Group
Write-Protected Settings
Addr.
Parameters
C
Range of Values
Default Setting
Rated values
_:91:101
General:Rated current
1 A to 100 000 A
1 000 A
Side data
_:91:130
General:Side number
not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210
General:MI3ph1 uses- MeasP with ID
0 to 100
0
_:91:211
General:MI3ph2 uses- MeasP with ID
0 to 100
0
_:91:212
General:MI3ph3 uses- MeasP with ID
0 to 100
0
_:91:213
General:MI3ph4 uses- MeasP with ID
0 to 100
0
_:91:214
General:M I-1ph uses MeasP with ID
0 to 100
0
_:91:215
General:CT mismatch M I-3ph 1
0.000 to 100.000
0.000
_:91:216
General:CT mismatch M I-3ph 1 IN
0.000 to 100.000
0.000
Rated values
_:91:217
General:CT mismatch M I-3ph 2
0.000 to 100.000
0.000
_:91:218
General:CT mismatch M I-3ph 2 IN
0.000 to 100.000
0.000
_:91:219
General:CT mismatch M I-3ph 3
0.000 to 100.000
0.000
_:91:220
General:CT mismatch M I-3ph 3 IN
0.000 to 100.000
0.000
_:91:221
General:CT mismatch M I-3ph 4
0.000 to 100.000
0.000
_:91:222
General:CT mismatch M I-3ph 4 IN
0.000 to 100.000
0.000
_:91:223
General:CT mismatch M I-1ph
0.000 to 100.000
0.000
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:91:103
General:Rated apparent power
0.20 MVA to 5000.00 MVA
692.82 MVA
_:91:102
General:Rated voltage
0.300 V to 340.000 V
40 000.000 V
Side data
_:91:149
General:Neutral point
grounded
isolated
grounded
_:91:104
General:Winding config- uration
Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:91:163
General:Vector group numeral
0
1
2
3
4
5
6
7
8
9
10
11
user-defined
0
Measurements
_:91:158
General:P, Q sign
not reversed
reversed
not reversed
Possible Operational Measured Values of the Transformer Side Function Group
Generation of Pickup Indication of the Transformer Side Function Group
Generation of an Operate Indication of the Transformer Side Function Group
Function-Group Type Transformer Neutral Point
Structure of the Transf. Neutral Point Function Group
Write-Protected Settings
Addr.
Parameter
C
Range of Values
Default Setting
Rated values
_:9421:103
General:Rated apparent power
0.20 MVA to 5 000.00 MVA
692.82 MVA
_:9421:104
General:Rated current
1 A to 100 000 A
1 000 A
_:9421:105
General:Rated voltage
0.20 kV to 1 200.00 kV
400 kV
Power-system data
_:9421:214
General:M I-1ph uses MeasP with ID
0 to 100
0
_:9421:223
General:CT mismatch M I-1ph
0.00 to 100.00
0.000
Operational Measured Values of the Transformer Neutral Point Function Group
Generation of Pickup Indication of the Transf. Neutral Point Function Group
Generation of Operate Indication of the Transf. Neutral Point Function Group
The “Circuit breaker” function group combines all the user functions that relate to a circuit breaker. It contains all of the protection, control, and supervision functions that you can use for this device type.
For more detailed information on “Circuit breaker” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Circuit-Breaker Function Group
Setting Parameters
General setting parameters
Addr.
Parameter
C
Setting Options
Default Setting
Ref. for %-values
_:2311:101
General:Rated normal current
0.20 A to 100000.00 A
1000.00 A
_:2311:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Breaker settings
_:2311:112
General:Current thresh. CB open
1 A @ 100 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 100 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:2311:136
General:Op. mode BFP
unbalancing
I> query
unbalancing
Setting parameters for Trip logic
Addr.
Parameter
C
Setting Options
Default Setting
Trip logic
_:103
Trip logic:Reset of trip command
with I<
with I< & aux.contact
with dropout
with I<
Setting parameters for Circuit breaker auxiliary contacts
Addr.
Parameter
C
Setting Options
Default Setting
Circuit break.
_:101
Circuit break.:Output time
0.02 s to 1800.00 s
0.10 s
_:105
Circuit break.:Indicat. of breaking
values
with trip
always
always
Setting parameters for Manual close detection
Addr.
Parameter
C
Setting Options
Default Setting
Manual close
_:101
Manual close:Action time
0.01 s to 60.00 s
0.30 s
_:102
Manual close:CB open dropout delay
0.00 s to 60.00 s
0.00 s
Logic Diagrams & highlights
Trip Command
Trip-Command Reset
Tripping, Opening, and Closing the Circuit Breaker
Detection of the Circuit-Breaker Information
Definitive Tripping and Circuit-Breaker Tripping Alarm Suppression
Breaking Information
Statistics Information About the Circuit Breaker
Routings for Activation of the Circuit Breaker
Routing for Analysis of the Circuit-Breaker Switch Position
Circuit-Breaker Tripping Alarm Suppression
The Circuit-Breaker Condition Position Function
Logic for Manual Closure Detection
Connection of the Input Signal to the Control Circuit of the Circuit-Breaker Closing Coil
In the “Voltage 3 phase” function group, all functions can be used for protecting and for monitoring a protected object or equipment which allows a 3-phase voltage measurement. The function group also contains the operational measurement for the protected object or equipment.
For more detailed information on “Voltage 3 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Voltage 3-Phase Function Group
Setting Parameters
Setting parameters for Voltage 3-Phase Function Group
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9421:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Logic Diagrams & highlights
Operational Measured Values of the Voltage 3-Phase Function Group
In the “Line” function group, all of the functions that are necessary for protecting and monitoring a line can be used. The Line function group also contains the measuring functions.
For more detailed information on “Line” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Line Function Group
Structure/Embedding of the Process Monitor (FG Line)
Setting Parameters
Setting parameters for Line Function Group
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9001:101
General:Rated current
1 A to 100000 A
1000 A
_:9001:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Line data
_:9001:149
General:Neutral point
grounded
suppress. coil grounded
isolated
grounded
_:9001:112
General:C1 per length unit
1 A
0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A
0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:148
General:C0 per length unit
1 A
0.000 °F/km to 100000.000
°F/km
0.010 °F/km
5 A
0.000 °F/km to 500000.000
°F/km
0.050 °F/km
_:9001:113
General:X per length unit
1 A
0.0010 Ω/km to 9.5000 Ω/km
0.0525 Ω/km
5 A
0.0002 Ω/km to 1.9000 Ω/km
0.0105 Ω/km
_:9001:114
General:Line length
0.10 km to 1000.00 km
60.00 km
_:9001:108
General:Line angle
10.00 ° to 89.00 °
85.00 °
_:9001:104
General:Kr
-0.33 to 11.00
1.00
_:9001:105
General:Kx
-0.33 to 11.00
1.00
_:9001:118
General:K0
0.000 to 11.000
1.000
_:9001:150
General:Angle (K0)
-180.00 ° to 180.00 °
0.00 °
_:9001:106
General:KmR
0.00 to 8.00
1.00
_:9001:107
General:KmX
0.00 to 8.00
1.00
_:9001:124
General:Km0
0.000 to 8.000
1.000
_:9001:125
General:Angle (Km0)
-180.00 ° to 180.00 °
0.00 °
_:9001:109
General:Gnd.curr.ratio(Mut Comp)
50 % to 95 %
85 %
_:9001:119
General:CT saturation detection
no
yes
no
_:9001:120
General:CT saturation threshold
1 A
0.030 A to 125.000 A
10.000 A
5 A
0.150 A to 625.000 A
50.000 A
_:9001:111
General:Series compensa- tion
no
yes
no
_:9001:110
General:Series capacit. reactance
1 A
0.000 Ω to 600.000 Ω
0.000 Ω
5 A
0.000 Ω to 120.000 Ω
0.000 Ω
Closure detec.
_:1131:4681:10 1
Closure detec.:Operating mode
Manual close only
I open and V open
CB and I open
I open
Manual close only
_:1131:4681:10 2
Closure detec.:Action time after
closure
0.01 s to 60.00 s
0.05 s
_:1131:4681:10 3
Closure detec.:Min. time feeder open
0.05 s to 60.00 s
0.25 s
1pol.open det.
_:1131:4711:10 1
1pol.open det.:Operating mode
off
with measurement
CB and I open
with measurement
Setting parameters for Process Monitor: Current-Flow Criterion
Addr.
Parameter
C
Setting Options
Default Setting
Breaker settings
_:2311:112
General:Current thresh. CB open
1 A @ 100 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 100 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 50 Irated
0.030 A to 10.000 A
0.100 A
5 A @ 50 Irated
0.15 A to 50.00 A
0.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.100 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.500 A
_:2311:136
General:Op. mode BFP
unbalancing
I> query
unbalancing
Setting parameters for Process Monitor: Closure Detection
Addr.
Parameter
C
Setting Options
Default Setting
Closure detec.
_:4681:101
Closure detec.:Operating mode
Manual close only
Iopen,Vopen,ManCl
CB, Iopen, ManCl
Iopen, ManCl
Manual close only
_:4681:102
Closure detec.:Action time after
closure
0.01 s to 60.00 s
0.05 s
_:4681:103
Closure detec.:Min. time feeder open
0.05 s to 60.00 s
0.25 s
Setting parameters for Process Monitor: Voltage Criterion (Optional)
Addr.
Parameter
C
Setting Options
Default Setting
Volt.criterion
_:101
Volt.criterion:Threshold U open
0.300 V to 170.000 V
51.960 V
Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)
Addr.
Parameter
C
Setting Options
Default Setting
Cold-load PU
_:1
Cold-load PU:Mode
off
on
test
off
_:101
Cold-load PU:Operating mode
I open
CB and I open
I open
_:102
Cold-load PU:Dropout threshold current
1 A @ 100 Irated
0.030 A to 10.000 A
1.000 A
5 A @ 100 Irated
0.15 A to 50.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 10.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 50.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
_:103
Cold-load PU:Dropout delay curr.crit.
1sto600 s
600s
_:104
Cold-load PU:Dropout delay CB closed
1 s to 21600 s
3600 s
_:105
Cold-load PU:Min. CB- open time
0 s to 21600 s
3600 s
Setting parameters for Process Monitor:Closure detec.
Addr.
Parameter
C
Setting Options
Default Setting
Closure detec.
_:4681:101
Closure detec.:Operating mode
Manual close only
CB and I open
I open and V open
I open
Manual close only
_:4681:102
Closure detec.:Action time after
closure
0.01 s to 60.00 s
0.05 s
_:4681:103
Closure detec.:Min. time feeder open
0.05 s to 60.00 s
0.25 s
Logic Diagrams & highlights
Operational Measured Values of the Function Group Line
Generation of a Pickup Indication of the Line Function Group
Generation of an Operate Indication of the Line Function Group
Logic Diagram of the Overall Function Process Monitor
Logic Diagram of the Current-Flow Criterion Function Block
Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block
Logic Diagram of the Closure-Detection Function Block
Logic Diagram of the 1-Pole Open Detector Function Block
Logic Diagram of the Voltage-Criterion Function Block
Logic Diagram of the Cold-Load Pickup Detection Function Block
In the “Voltage current 3 phase” function group, you can use all the functions for protection and supervision of a protected object or equipment that allows 3-phase current and voltage measurement. The function group also contains the operational measurement for the protected object or equipment.
For more detailed information on “Voltage current 3 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Voltage-Current 3-Phase Function Group
Structure/Embedding of the Process Monitor Function
Setting Parameters
Write-Protected Settings for Voltage-Current 3-Phase Function Group
Addr.
Parameters
C
Range of Values
Default Setting
Network data
_:103
General:rated apparent power
0.20 MVA to 5 000.00 MVA
692.82 MVA
Setting parameters for Voltage-Current 3-Phase Function Group
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9451:101
General:Rated current
1.00 A to 100000.00 A
1000.00 A
_:9451:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
Power-system data
_:9451:149
General:Power-sys. neutral point
grounded
suppress. coil grounded
isolated
grounded
Measurements
_:9451:158
General:P, Q sign
not reversed
reversed
not reversed
Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)
Addr.
Parameter
C
Setting Options
Default Setting
Cold-load PU
_:1
Cold-load PU:Mode
off
on
test
off
_:101
Cold-load PU:Operating mode
I open
CB and I open
I open
_:102
Cold-load PU:Dropout threshold current
1 A @ 100 Irated
0.030 A to 10.000 A
1.000 A
5 A @ 100 Irated
0.15 A to 50.00 A
5.00 A
1 A @ 50 Irated
0.030 A to 10.000 A
1.000 A
5 A @ 50 Irated
0.15 A to 50.00 A
5.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
5.000 A
_:103
Cold-load PU:Dropout delay curr.crit.
1 s to 600 s
600 s
_:104
Cold-load PU:Dropout delay CB closed
1 s to 21600 s
3600 s
_:105
Cold-load PU:Min. CB- open time
0 s to 21600 s
3600 s
Logic Diagrams & highlights
Operational Measured Values of the Voltage-Current 3-Phase Function Group
Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group
Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group
Logic Diagram of the Overall Function Process Monitor
Logic Diagram of the Current-Flow Criterion Function Block
Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block
Logic Diagram of Closure Detection
Logic Diagram of the Cold-Load Pickup Detection Function Block