Phase current unbalance (ANSI 60P, IEC PVCB/PTOC) _ Element settings & highlights _ GU8081


Overview

The “Phase current unbalance” element responds to a differential current signal measured via window-type CTs as a vectorial current difference between two parallel banks. With the two capacitors in the same phase identical, the said differential current is zero. Small differences between the capacitors of a given phase result in a small circulating current.

For more detailed information on “Phase current unbalance” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70 65B9 Phase Current Unbalance 1 Function 0 to 1 1 F102 0 (Disabled)
" 65BA Phase Current Unbalance 1 Differential Source 0 to 5 1 F167 0 (SRC 1)
" 65BB Phase Current Unbalance 1 Bank Source 0 to 5 1 F167 0 (SRC 1)
" 65BC Phase Current Unbalance 1 Inherent Factor A -0.1 to 0.1 0.000
1
F002 0
" 65BD Phase Current Unbalance 1 Inherent Factor B -0.1 to 0.1 0.000
1
F002 0
" 65BE Phase Current Unbalance 1 Inherent Factor C -0.1 to 0.1 0.000
1
F002 0
" 65BF Phase Current Unbalance 1 Stage 1A Pickup 0.001 to 5 pu 0.001 F001 20
" 65C0 Phase Current Unbalance 1 Stage 2A Pickup 0.001 to 5 pu 0.001 F001 30
" 65C1 Phase Current Unbalance 1 Stage 3A Pickup 0.001 to 5 pu 0.001 F001 40
" 65C2 Phase Current Unbalance 1 Stage 4A Pickup 0.001 to 5 pu 0.001 F001 50
" 65C3 Phase Current Unbalance 1 Stage 1B Pickup 0.001 to 5 pu 0.001 F001 20
" 65C4 Phase Current Unbalance 1 Stage 2B Pickup 0.001 to 5 pu 0.001 F001 30
" 65C5 Phase Current Unbalance 1 Stage 3B Pickup 0.001 to 5 pu 0.001 F001 40
" 65C6 Phase Current Unbalance 1 Stage 4B Pickup 0.001 to 5 pu 0.001 F001 50
" 65C7 Phase Current Unbalance 1 Stage 1C Pickup 0.001 to 5 pu 0.001 F001 20
" 65C8 Phase Current Unbalance 1 Stage 2C Pickup 0.001 to 5 pu 0.001 F001 30
" 65C9 Phase Current Unbalance 1 Stage 3C Pickup 0.001 to 5 pu 0.001 F001 40
" 65CA Phase Current Unbalance 1 Stage 4C Pickup 0.001 to 5 pu 0.001 F001 50
" 65CB Phase Current Unbalance 1 Stage 1 Pickup Delay 0 to 600 s 0.01 F001 3000
" 65CC Phase Current Unbalance 1 Stage 2 Pickup Delay 0 to 600 s 0.01 F001 1000
" 65CD Phase Current Unbalance 1 Stage 3 Pickup Delay 0 to 600 s 0.01 F001 100
" 65CE Phase Current Unbalance 1 Stage 4 Pickup Delay 0 to 600 s 0.01 F001 20
" 65CF Phase Current Unbalance 1 Dropout Delay 0 to 600 s 0.01 F001 25
" 65D0 Phase Current Unbalance 1 Stage 1 Block 0 to 4294967295 1 F300 0
" 65D2 Phase Current Unbalance 1 Stage 2 Block 0 to 4294967295 1 F300 0
" 65D4 Phase Current Unbalance 1 Stage 3 Block 0 to 4294967295 1 F300 0
" 65D6 Phase Current Unbalance 1 Stage 4 Block 0 to 4294967295 1 F300 0
" 65D8 Phase Current Unbalance 1 Target 0 to 2 1 F109 0 (Self-Reset)
" 65D9 Phase Current Unbalance 1 Events 0 to 1 1 F102 0 (Disabled)
" 65DA …Repeated for Phase Current Unbalance 2          
" 65FB …Repeated for Phase Current Unbalance 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Phase current unbalance basic connections


Phase current unbalance logic


Neutral voltage unbalance (ANSI 59NU, IEC PVCB/PTOV) _ Element settings & highlights _ GU8080


Overview

The “Neutral voltage unbalance” element responds to the voltage signal at the neutral point of the capacitor bank. The operating equations are properly compensated for both the system unbalance such as during close-in external faults, and the inherent bank unbalance.

For more detailed information on “Neutral voltage unbalance” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70 655F Neutral Voltage Unbalance 1 Function 0 to 1 1 F102 0 (Disabled)
" 6560 Neutral Voltage Unbalance 1 Neutral-Point Source 0 to 5 1 F167 0 (SRC 1)
" 6561 Neutral Voltage Unbalance 1 Bus Source 0 to 5 1 F167 0 (SRC 1)
" 6562 Neutral Voltage Unbalance 1 Bus 3V0 0 to 1 1 F241 0
(Calculated)
" 6563 Neutral Voltage Unbalance 1 Ground 0 to 1 1 F255 0 (VT
(ungrnd))
" 6564 Neutral Voltage Unbalance 1 AB Ratio 0.75 to 1.25 0.000
1
F001 10000
" 6565 Neutral Voltage Unbalance 1 AC Ratio 0.75 to 1.25 0.000
1
F001 10000
" 6566 Neutral Voltage Unbalance 1 Stage 1 Pickup 0.001 to 1 pu 0.001 F001 10
" 6567 Neutral Voltage Unbalance 1 Stage 1 Slope 0 to 10 % 0.1 F001 0
" 6568 Neutral Voltage Unbalance 1 Stage 2 Pickup 0.001 to 1 pu 0.001 F001 20
" 6569 Neutral Voltage Unbalance 1 Stage 2 Slope 0 to 10 % 0.1 F001 0
" 656A Neutral Voltage Unbalance 1 Stage 3 Pickup 0.001 to 1 pu 0.001 F001 20
" 656B Neutral Voltage Unbalance 1 Stage 3 Slope 0 to 10 % 0.1 F001 50
" 656C Neutral Voltage Unbalance 1 Stage 4 Pickup 0.001 to 1 pu 0.001 F001 30
" 656D Neutral Voltage Unbalance 1 Stage 4 Slope 0 to 10 % 0.1 F001 50
" 656E Neutral Voltage Unbalance 1 Stage 1 Pickup Delay 0 to 600 s 0.01 F001 3000
" 656F Neutral Voltage Unbalance 1 Stage 2 Pickup Delay 0 to 600 s 0.01 F001 1000
" 6570 Neutral Voltage Unbalance 1 Stage 3 Pickup Delay 0 to 600 s 0.01 F001 100
" 6571 Neutral Voltage Unbalance 1 Stage 4 Pickup Delay 0 to 600 s 0.01 F001 20
" 6572 Neutral Voltage Unbalance 1 Dropout Delay 0 to 600 s 0.01 F001 25
" 6573 Neutral Voltage Unbalance 1 Stage 1 Block 0 to 4294967295 1 F300 0
" 6575 Neutral Voltage Unbalance 1 Stage 2 Block 0 to 4294967295 1 F300 0
" 6577 Neutral Voltage Unbalance 1 Stage 3 Block 0 to 4294967295 1 F300 0
" 6579 Neutral Voltage Unbalance 1 Stage 4 Block 0 to 4294967295 1 F300 0
" 657B Neutral Voltage Unbalance 1 Target 0 to 2 1 F109 0 (Self-Reset)
" 657C Neutral Voltage Unbalance 1 Events 0 to 1 1 F102 0 (Disabled)
" 657D …Repeated for Neutral Voltage Unbalance 2          
" 659B …Repeated for Neutral Voltage Unbalance 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F241 0 = Calculated, 1 = Measured
F255 0 = VT (ungrnd) = ungrounded, 1 = CTxR (grnd) = grounded

Logics & highlights


Neutral voltage unbalance basic connection

Neutral voltage unbalance basic connection

Neutral voltage unbalance logic

Neutral voltage unbalance logic

Neutral current unbalance (ANSI 60N, IEC PVCB/PTOC) _ Element settings & highlights _ GU8079


Overview

The “Neutral current unbalance” element responds to a differential current signal measured as a vectorial current difference between neutral currents of parallel banks. In case of ungrounded banks, regular, preferably low-ratio CT can be used. In case of grounded banks, a window or core-balance CT shall be used for increased accuracy/sensitivity.

For more detailed information on “Neutral current unbalance” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70 650E Neutral Current Unbalance 1 Function 0 to 1 1 F102 0 (Disabled)
" 650F Neutral Current Unbalance 1 Bank Source 0 to 5 1 F167 0 (SRC 1)
" 6510 Neutral Current Unbalance 1 k Magnitude 0 to 0.15 0.000
1
F001 0
" 6511 Neutral Current Unbalance 1 k Angle 0 to 359 ° 1 F001 0
" 6512 Neutral Current Unbalance 1 Stage 1 Pickup 0 to 5 pu 0.001 F001 20
" 6513 Neutral Current Unbalance 1 Stage 1 Slope 0 to 10 % 0.1 F001 20
" 6514 Neutral Current Unbalance 1 Stage 2 Pickup 0 to 5 pu 0.001 F001 30
" 6515 Neutral Current Unbalance 1 Stage 2 Slope 0 to 10 % 0.1 F001 20
" 6516 Neutral Current Unbalance 1 Stage 3 Pickup 0 to 5 pu 0.001 F001 40
" 6517 Neutral Current Unbalance 1 Stage 3 Slope 0 to 10 % 0.1 F001 20
" 6518 Neutral Current Unbalance 1 Stage 4 Pickup 0 to 5 pu 0.001 F001 50
" 6519 Neutral Current Unbalance 1 Stage 4 Slope 0 to 10 % 0.1 F001 50
" 651A Neutral Current Unbalance 1 Stage 1 Pickup Delay 0 to 600 s 0.01 F001 3000
" 651B Neutral Current Unbalance 1 Stage 2 Pickup Delay 0 to 600 s 0.01 F001 1000
" 651C Neutral Current Unbalance 1 Stage 3 Pickup Delay 0 to 600 s 0.01 F001 100
" 651D Neutral Current Unbalance 1 Stage 4 Pickup Delay 0 to 600 s 0.01 F001 20
" 651E Neutral Current Unbalance 1 Dropout Delay 0 to 600 s 0.01 F001 25
" 651F Neutral Current Unbalance 1 Stage 1 Block 0 to 4294967295 1 F300 0
" 6521 Neutral Current Unbalance 1 Stage 2 Block 0 to 4294967295 1 F300 0
" 6523 Neutral Current Unbalance 1 Stage 3 Block 0 to 4294967295 1 F300 0
" 6525 Neutral Current Unbalance 1 Stage 4 Block 0 to 4294967295 1 F300 0
" 6527 Neutral Current Unbalance 1 Target 0 to 2 1 F109 0 (Self-Reset)
" 6528 Neutral Current Unbalance 1 Events 0 to 1 1 F102 0 (Disabled)
" 6529 …Repeated for Neutral Current Unbalance 2          
" 6544 …Repeated for Neutral Current Unbalance 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Neutral current unbalance connections

Neutral current unbalance connections

Neutral current unbalance logic

Neutral current unbalance logic

Automatic voltage regulator _ Element settings & highlights _ GU8250


Overview

The “Automatic voltage regulator” element (AVR) is intended to switch a static capacitor bank breaker open and closed to regulate system voltage, load voltage, power factor, or reactive power.

For more detailed information on “Automatic voltage regulator” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70 64D2 Automatic Voltage Regulator 1 Function 0 to 1 1 F102 0 (Disabled)
" 64D3 Automatic Voltage Regulator 1 Source 0 to 5 1 F167 0 (SRC 1)
" 64D4 Automatic Voltage Regulator 1 Minimum Voltage 0.5 to 1.5 pu 0.001 F001 500
" 64D5 Automatic Voltage Regulator 1 Control Mode 0 to 1 1 F536 0 (Voltage)
" 64D6 Automatic Voltage Regulator 1 Voltage Operating Signal 0 to 8 1 F535 4 (V1)
" 64D7 Automatic Voltage Regulator 1 Voltage Level to Close 0.75 to 1.5 pu 0.001 F001 950
" 64D8 Automatic Voltage Regulator 1 Voltage Level to Open 0.75 to 1.5 pu 0.001 F001 1050
" 64D9 AVR 1 Voltage Drop Compensation Impedance 0 to 250 ohms 0.01 F001 0
" 64DA AVR 1 Voltage Drop Compensation RCA 30 to 90 ° 1 F001 75
" 64DB Automatic Voltage Regulator 1 VAR Level to Close -1.5 to 1.5 pu 0.001 F002 950
" 64DC Automatic Voltage Regulator 1 VAR Level to Open -1.5 to 1.5 pu 0.001 F002 1050
" 64DD Automatic Voltage Regulator 1 Power Factor Limit 0.5 to 1 0.01 F001 100
" 64DE Automatic Voltage Regulator 1 VAR Open Mode 0 to 1 1 F537 1 (Minimize No. of Ops.)
" 64DF Automatic Voltage Regulator 1 Delay Before Close 0 to 65.535 s 0.001 F001 1000
" 64E0 Automatic Voltage Regulator 1 Delay Before Open 0 to 65.535 s 0.001 F001 1000
" 64E1 Automatic Voltage Regulator 1 Block 0 to 4294967295 1 F300 0
" 64E3 Automatic Voltage Regulator 1 Events 0 to 1 1 F102 0 (Disabled)
" 64E4 Automatic Voltage Regulator 1 Target 0 to 2 1 F109 0 (Self-Reset)
" 64E5 Reserved 0 to 0.001 0.001 F001 0
" 64E6 …Repeated for Automatic Voltage Regulator 2          
" 64FA …Repeated for Automatic Voltage Regulator 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F535 0 = Vab, 1 = Vbc, 2 = Vca, 3 = Vaver, 4 = V1, 5 = Vaux, 6 = Vag, 7 = Vbg, 8 = Vcg
F536 0 = Voltage, 1 = VAR
F537 0 = Minimize uptime, 1 = Minimize number of operations

Logics & highlights


Applications of the capacitor automatic voltage regulator function

Applications of the capacitor automatic voltage regulator function

Automatic voltage regulator pickup characteristics in “VAR” mode

Automatic voltage regulator pickup characteristics in "VAR" mode

Close and open levels when controlling voltage or VARs

Close and open levels when controlling voltage or VARs

Automatic voltage regulator logic

Automatic voltage regulator logic

Capacitor control _ Element settings & highlights _ GU8249


Overview

The “Capacitor control” element gathers on/off commands from various sources and executes them, while maintaining remote/local and auto/manual control rights. Local control refers to control from the front panel of the relay. Remote control refers to control via communications from outside of the relay, an on-site interface, and/or from an off-site control center.

For more detailed information on “Capacitor control” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C70 6415 Capacitor Control 1 Function 0 to 1 1 F102 0 (Disabled)
" 6416 Capacitor Control 1 Set Remote 1 0 to 4294967295 1 F300 0
" 6418 Capacitor Control 1 Set Remote 2 0 to 4294967295 1 F300 0
" 641A Capacitor Control 1 Set Local 1 0 to 4294967295 1 F300 0
" 641C Capacitor Control 1 Set Local 2 0 to 4294967295 1 F300 0
" 641E Capacitor Control 1 Remote Control Enable 0 to 4294967295 1 F300 0
" 6420 Capacitor Control 1 Local Control Enable 0 to 4294967295 1 F300 0
" 6422 Capacitor Control 1 Remote Set Automatic 0 to 4294967295 1 F300 0
" 6424 Capacitor Control 1 Local Set Automatic 0 to 4294967295 1 F300 0
" 6426 Capacitor Control 1 Remote Set Manual 0 to 4294967295 1 F300 0
" 6428 Capacitor Control 1 Local Set Manual 0 to 4294967295 1 F300 0
" 642A Capacitor Control 1 Trip 1 0 to 4294967295 1 F300 0
" 642C Capacitor Control 1 Trip 2 0 to 4294967295 1 F300 0
" 642E Capacitor Control 1 Trip 3 0 to 4294967295 1 F300 0
" 6430 Capacitor Control 1 Trip 4 0 to 4294967295 1 F300 0
" 6432 Capacitor Control 1 Trip 5 0 to 4294967295 1 F300 0
" 6434 Capacitor Control 1 Trip 6 0 to 4294967295 1 F300 0
" 6436 Capacitor Control Switch to Manual on Trip 0 to 1 1 F126 1 (Yes)
" 6437 Capacitor Control 1 Automatic Control Enable 0 to 4294967295 1 F300 0
" 6439 Capacitor Control 1 Manual Control Enable 0 to 4294967295 1 F300 0
" 643B Capacitor Control 1 Remote Open 0 to 4294967295 1 F300 0
" 643D Capacitor Control 1 Local Open 0 to 4294967295 1 F300 0
" 643F Capacitor Control 1 Automatic Open 0 to 4294967295 1 F300 0
" 6441 Capacitor Control 1 Breaker Open 52b 0 to 4294967295 1 F300 0
" 6443 Capacitor Control 1 Trip Seal-in Delay 0 to 60 s 0.001 F001 400
" 6444 Capacitor Control 1 Remote Close 0 to 4294967295 1 F300 0
" 6446 Capacitor Control 1 Local Close 0 to 4294967295 1 F300 0
" 6448 Capacitor Control 1 Automatic Close 0 to 4294967295 1 F300 0
" 644A Capacitor Control 1 Breaker Closed 52a 0 to 4294967295 1 F300 0
" 644C Capacitor Control 1 Close Discharge Time 0 to 3600 s 1 F001 300
" 644D Capacitor Control 1 Close Seal-in Delay 0 to 60 s 0.001 F001 400
" 644E Capacitor Control 1 Breaker Close Block 0 to 4294967295 1 F300 0
" 6450 Capacitor Control 1 Close Override 0 to 4294967295 1 F300 0
" 6452 Capacitor Control 1 Targets 0 to 2 1 F109 0 (Self-Reset)
" 6453 Capacitor Control 1 Events 0 to 1 1 F102 0 (Disabled)
" 6454 …Repeated for Capacitor Control Element 2          
" 6493 …Repeated for Capacitor Control Element 3          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F126 0 = No, 1 = Yes

Logics & highlights


Capacitor bank control logic

Capacitor bank control logic

Cross country _ Element settings & highlights _ GU8247


Overview

Cross-country fault means that two separate single-phase faults occur on a system together. For more detailed information on “Cross country” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D60, L90 DA00 Cross Country Function 0 to 2 1 F684 0 (Disabled)
" DA01 Cross Country Dist Reach Factor 1 to 20 0.1 F001 15
" DA02 Cross Country IN>Current Set 0.05 to 30 pu 0.001 F001 50
" DA03 Cross Country Slope 0 to 0.3 0.1 F001 1
" DA04 Cross Country VN>Voltage Set 0.004 to 3 pu 0.001 F001 75
" DA05 Cross Country 1P Mode 0 to 3 1 F687 0 (IN>)
" DA06 Cross Country 1P Time Delay 0 to 600 s 0.01 F001 5
" DA07 Cross Country Phase prio. 2pG 0 to 8 1 F688 0 (C(A) ACYCLIC)
F684 0 = Disabled, 1 = Solid Grounding, 2 = Is Comp Grounding
F687 0 = IN>, 1 = VN>, 2 = IN> AND VN>
F688 0 = C(A) ACYCLIC, 1 = A(C) ACYCLIC, 2 = B(A) ACYCLIC, 3 = A(B) ACYCLIC, 4 = C(B) ACYCLIC, 5 = B(C) ACYCLIC, 6 = C(A) CYCLIC, 7 = A(C) CYCLIc, 8 = ALL

Logics & highlights


Priority

Priority

Trip output _ Element settings & highlights _ GU8246


Overview

The “Trip output” element is primarily used to collect trip requests from protection elements and other inputs to generate output operands to initiate trip operations. Three pole trips only initiate reclosure if programmed to do so, whereas single pole trips always automatically initiate reclosure.

For more detailed information on “Trip output” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C60, C95, D60, L60, L90 D934 Trip Mode 0 to 2 1 F195 0 (Disabled)
" D935 Trip 3-Pole Input1 0 to 4294967295 1 F300 0
" D937 Trip 3-Pole Input2 0 to 4294967295 1 F300 0
" D939 Trip 3-Pole Input3 0 to 4294967295 1 F300 0
" D93B Trip 3-Pole Input4 0 to 4294967295 1 F300 0
" D93D Trip 3-Pole Input5 0 to 4294967295 1 F300 0
" D93F Trip 3-Pole Input6 0 to 4294967295 1 F300 0
" D941 Trip 1-Pole Input1 0 to 4294967295 1 F300 0
" D943 Trip 1-Pole Input2 0 to 4294967295 1 F300 0
" D945 Trip 1-Pole Input3 0 to 4294967295 1 F300 0
" D947 Trip 1-Pole Input4 0 to 4294967295 1 F300 0
" D949 Trip 1-Pole Input5 0 to 4294967295 1 F300 0
" D94B Trip 1-Pole Input6 0 to 4294967295 1 F300 0
" D94D Trip Reclose Input1 0 to 4294967295 1 F300 0
" D94F Trip Reclose Input2 0 to 4294967295 1 F300 0
" D951 Trip Reclose Input3 0 to 4294967295 1 F300 0
" D953 Trip Reclose Input4 0 to 4294967295 1 F300 0
" D955 Trip Reclose Input5 0 to 4294967295 1 F300 0
" D957 Trip Reclose Input6 0 to 4294967295 1 F300 0
" D959 Trip Seal-In Delay 0 to 65.535 s 0.001 F001 0
" D95A Trip Reset 0 to 2 1 F609 0 (Pole Curr OR Custom)
" D95B Phase Selector Reset Delay 0.5 to 3 s 0.001 F001 500
" D95C Phase Selector Reset 0 to 4294967295 1 F300 0
" D95E Breaker Phase A Open 0 to 4294967295 1 F300 0
" D960 Breaker Phase B Open 0 to 4294967295 1 F300 0
" D962 Breaker Phase C Open 0 to 4294967295 1 F300 0
" D964 Trip Force 3-Pole 0 to 4294967295 1 F300 0
" D966 Trip Pilot Priority 0 to 65.535 s 0.001 F001 0
" D967 Reverse Fault Operand 0 to 4294967295 1 F300 0
" D969 Trip Delay On Evolving Faults 0 to 65.535 s 0.001 F001 0
" D96A Trip Events 0 to 1 1 F102 0 (Disabled)
" D96B Start Timer Zone 2 Phase Input 1 0 to 4294967295 1 F300 0
" D96D Start Timer Zone 2 Phase Input 2 0 to 4294967295 1 F300 0
" D96F Start Timer Zone 2 Ground Input 1 0 to 4294967295 1 F300 0
" D971 Start Timer Zone 2 Ground Input 2 0 to 4294967295 1 F300 0
" D973 Start Timer Zone 3 Phase Input 1 0 to 4294967295 1 F300 0
" D975 Start Timer Zone 3 Phase Input 2 0 to 4294967295 1 F300 0
" D977 Start Timer Zone 3 Ground Input 1 0 to 4294967295 1 F300 0
" D979 Start Timer Zone 3 Ground Input 2 0 to 4294967295 1 F300 0
" D97B Start Timer Zone 4 Phase Input 1 0 to 4294967295 1 F300 0
" D97D Start Timer Zone 4 Phase Input 2 0 to 4294967295 1 F300 0
" D97F Start Timer Zone 4 Ground Input 1 0 to 4294967295 1 F300 0
" D981 Start Timer Zone 4 Ground Input 2 0 to 4294967295 1 F300 0
" D983 Start Timer Zone 5 Phase Input 1 0 to 4294967295 1 F300 0
" D985 Start Timer Zone 5 Phase Input 2 0 to 4294967295 1 F300 0
" D987 Start Timer Zone 5 Ground Input 1 0 to 4294967295 1 F300 0
" D989 Start Timer Zone 5 Ground Input 2 0 to 4294967295 1 F300 0
" D98B Start Timer Zone 6 Phase Input 1 0 to 4294967295 1 F300 0
" D98D Start Timer Zone 6 Phase Input 2 0 to 4294967295 1 F300 0
" D98F Start Timer Zone 6 Ground Input 1 0 to 4294967295 1 F300 0
" D991 Start Timer Zone 6 Ground Input 2 0 to 4294967295 1 F300 0
" D993 Reserved (4 items) 0 to 1 1 F001 0
F102 0 = Disabled, 1 = Enabled
F195 0 = Disabled, 1 = 3 Pole Only, 2 = 3 Pole & 1 Pole
F609 0 = Pole Curr OR Custom, 1 = CBaux OR Custom, 2 = Custom

Logics & highlights


Trip output logic (Sheet 1 of 3)

Trip output logic (Sheet 1 of 3)

Trip output logic (Sheet 2 of 3)

Trip output logic (Sheet 2 of 3)

Trip output logic (Sheet 3 of 3)

Trip output logic (Sheet 3 of 3)

Selector switch _ Element settings & highlights _ GU8244


Overview

The “Selector switch” element is intended to replace a mechanical selector switch. Typical applications include setting group control or control of multiple logic sub-circuits in user-programmable logic.

For more detailed information on “Selector switch” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except B90 6848 Selector 1 Function 0 to 1 1 F102 0 (Disabled)
" 6849 Selector 1 Range 1 to 7 1 F001 7
" 684A Selector 1 Timeout 3 to 60 s 0.1 F001 50
" 684B Selector 1 Step Up 0 to 4294967295 1 F300 0
" 684D Selector 1 Step Mode 0 to 1 1 F083 0 (Time-out)
" 684E Selector 1 Acknowledge 0 to 4294967295 1 F300 0
" 6850 Selector 1 Bit0 0 to 4294967295 1 F300 0
" 6852 Selector 1 Bit1 0 to 4294967295 1 F300 0
" 6854 Selector 1 Bit2 0 to 4294967295 1 F300 0
" 6856 Selector 1 Bit Mode 0 to 1 1 F083 0 (Time-out)
" 6857 Selector 1 Bit Acknowledge 0 to 4294967295 1 F300 0
" 6859 Selector 1 Power Up Mode 0 to 2 1 F084 0 (Restore)
" 685A Selector 1 Target 0 to 2 1 F109 0 (Self-reset)
" 685B Selector 1 Events 0 to 1 1 F102 0 (Disabled)
" 685C Reserved (10 items) 1 F001 0
" 6866 …Repeated for Selector 2          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F083 0 = Time-out, 1 = Acknowledge
F084 0 = Restore, 1 = Synchronize, 2 = Sync/Restore

Logics & highlights


The three-bit control word

The three-bit control word

Selector 1 events (if enabled)

SELECTOR 1 EVENTS (if enabled)

Time-out mode

Time-out mode

Acknowledge mode

Acknowledge mode

Application example

Application example

Selector switch logic

Selector switch logic

Setting groups _ Element settings & highlights _ GU8243


Overview

The “Setting groups” menu controls the activation and deactivation of up to six groups of settings in the GROUPED ELEMENTS settings menu. On a setting group change, protection elements are blocked temporarily to allow the relay to re-initialize with the new settings. The duration of the block depends on relay configuration and can last up to four cycles.

For more detailed information on “Setting groups”, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except C30 3D60 Setting Group for Modbus Comms (0 means group 1) 0 to 5 1 F001 0
" 3D61 Setting Groups Block 0 to 4294967295 1 F300 0
" 3D63 FlexLogic Operands to Activate Groups 2 through 6 (5 items) 0 to 4294967295 1 F300 0
" 3D6D Setting Group Function 0 to 1 1 F102 0 (Disabled)
" 3D6E Setting Group Events 0 to 1 1 F102 0 (Disabled)
" 3D6F Setting Groups Control Mode 0 to 1 1 F283 0 (Local)
All except C30 3D70 Setting Group 1 Name F203 (none)
" 3D78 Setting Group 2 Name F203 (none)
" 3D80 Setting Group 3 Name F203 (none)
" 3D88 Setting Group 4 Name F203 (none)
" 3D90 Setting Group 5 Name F203 (none)
" 3D98 Setting Group 6 Name F203 (none)
F102 0 = Disabled, 1 = Enabled
F283 0 = Local, 1 = IEC61850 Client

Logics & highlights


Logic diagram for Control Mode setting

Logic diagram for Control Mode setting

Example of FlexLogic control of a setting group

Example of FlexLogic control of a setting group

Trip bus _ Element settings & highlights _ GU8242


Overview

The “Trip bus” element allows aggregating outputs of protection and control elements without using FlexLogic and assigning them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning such as latch, delay, and seal-in delay are available.

For more detailed information on “Trip bus” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All 5B3D Trip Bus 1 Function 0 to 1 1 F102 0 (Disabled)
" 5B3E Trip Bus 1 Block 0 to 4294967295 1 F300 0
" 5B40 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
" 5B41 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
" 5B42 Trip Bus 1 Input (16 items) 0 to 4294967295 1 F300 0
" 5B62 Trip Bus 1 Latching 0 to 1 1 F102 0 (Disabled)
" 5B63 Trip Bus 1 Reset 0 to 4294967295 1 F300 0
" 5B65 Trip Bus 1 Target 0 to 2 1 F109 0 (Self-reset)
" 5B66 Trip Bus 1 Events 0 to 1 1 F102 0 (Disabled)
" 5B67 Reserved (8 items) 0 to 1 1 F001 0
" 5B6F …Repeated for Trip Bus 2          
" 5BA1 …Repeated for Trip Bus 3          
" 5BD3 …Repeated for Trip Bus 4          
" 5C05 …Repeated for Trip Bus 5          
" 5C37 …Repeated for Trip Bus 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Trip bus fields in the protection summary

Trip bus fields in the protection summary

Trip bus logic

Trip bus logic

error: Content is protected !!