Overview
The “Capacitor control” element gathers on/off commands from various sources and executes them, while maintaining remote/local and auto/manual control rights. Local control refers to control from the front panel of the relay. Remote control refers to control via communications from outside of the relay, an on-site interface, and/or from an off-site control center.
For more detailed information on “Capacitor control” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
C70 | 6415 | Capacitor Control 1 Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 6416 | Capacitor Control 1 Set Remote 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6418 | Capacitor Control 1 Set Remote 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 641A | Capacitor Control 1 Set Local 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 641C | Capacitor Control 1 Set Local 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 641E | Capacitor Control 1 Remote Control Enable | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6420 | Capacitor Control 1 Local Control Enable | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6422 | Capacitor Control 1 Remote Set Automatic | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6424 | Capacitor Control 1 Local Set Automatic | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6426 | Capacitor Control 1 Remote Set Manual | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6428 | Capacitor Control 1 Local Set Manual | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 642A | Capacitor Control 1 Trip 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 642C | Capacitor Control 1 Trip 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 642E | Capacitor Control 1 Trip 3 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6430 | Capacitor Control 1 Trip 4 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6432 | Capacitor Control 1 Trip 5 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6434 | Capacitor Control 1 Trip 6 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6436 | Capacitor Control Switch to Manual on Trip | 0 to 1 | — | 1 | F126 | 1 (Yes) |
" | 6437 | Capacitor Control 1 Automatic Control Enable | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6439 | Capacitor Control 1 Manual Control Enable | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 643B | Capacitor Control 1 Remote Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 643D | Capacitor Control 1 Local Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 643F | Capacitor Control 1 Automatic Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6441 | Capacitor Control 1 Breaker Open 52b | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6443 | Capacitor Control 1 Trip Seal-in Delay | 0 to 60 | s | 0.001 | F001 | 400 |
" | 6444 | Capacitor Control 1 Remote Close | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6446 | Capacitor Control 1 Local Close | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6448 | Capacitor Control 1 Automatic Close | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 644A | Capacitor Control 1 Breaker Closed 52a | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 644C | Capacitor Control 1 Close Discharge Time | 0 to 3600 | s | 1 | F001 | 300 |
" | 644D | Capacitor Control 1 Close Seal-in Delay | 0 to 60 | s | 0.001 | F001 | 400 |
" | 644E | Capacitor Control 1 Breaker Close Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6450 | Capacitor Control 1 Close Override | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 6452 | Capacitor Control 1 Targets | 0 to 2 | — | 1 | F109 | 0 (Self-Reset) |
" | 6453 | Capacitor Control 1 Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 6454 | …Repeated for Capacitor Control Element 2 | |||||
" | 6493 | …Repeated for Capacitor Control Element 3 | |||||
F102 | 0 = Disabled, 1 = Enabled | ||||||
F109 | 0 = Self-reset, 1 = Latched, 2 = Disabled | ||||||
F126 | 0 = No, 1 = Yes | ||||||