Overview
In the “Capacitor bank” function group, all the functions that are necessary for protecting and monitoring a capacitor bank can be used. Some of these functions are exclusively used for protecting capacitor banks, and others are universal standard functions which can be used for other protected objects as well.
For more detailed information on “Capacitor bank” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of the Capacitor Bank Function Group

Setting Parameters
Write-Protected Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:14641:103 | General:Rated apparent power | -1.00 MVA to -1.00 MVA | 0.00 MVA | |
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:14641:101 | General:Capacitor reference curr. | 1.00 A to 100000.00 A | 1000.00 A | |
_:14641:102 | General:Capacitor reference volt. | 0.20 kV to 1200.00 kV | 400.00 kV | |
Cap.bank data | ||||
_:14641:106 | General:Capacitor element type | fused unfused |
fused | |
_:14641:107 | General:Blk.cls.cmd.dur. discharge | off on |
off | |
_:14641:108 | General:Discharge time | 1 s to 1200 s | 300 s | |
_:14641:109 | General:Cap.-bank neutral point | grounded isolated |
isolated | |
Measurements | ||||
_:14611:158 | Further settings:P, Q sign | not reversed reversed |
not reversed | |
Logic Diagrams & highlights
Logic Diagram of Capacitor Bank Device Status and Blocking of Circuit- breaker Closing during Discharging

Logic Diagram of Processing the Blocked by Discharge Signal

Operational Measured Values (True RMS) of the Function Group Capacitor Bank

Fundamental and Symmetrical Components Measurement Values of the Function Group Capacitor Bank

Generation of the Pickup Indication of the Capacitor Bank Function Group

Generation of the Operate Indication of the Capacitor Bank Function Group