Overview
The individual function-group types are stored in the “Capacitor bank diff” function group folder and can be selected. The “Capacitor bank diff.” function group contains the differential protection function and protection-function relevant measured values. In the “Capacitor bank side” function group, all of the functions that are necessary for protecting and supervising a capacitor bank side can be used.
For more detailed information on “Capacitor bank diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Structure of Function-Group Types Capacitor Bank Diff

Function-Group Type Capacitor Bank Diff
Structure of the Capacitor Bank Diff. Function Group

Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

Generation of Operate Indication of the Capacitor Bank Diff. Function Group

Function-Group Type Capacitor-Bank Side
Structure of the Capacitor Bank Side Function Group

Write-Protected Settings
Addr. | Parameter | C | Range of Values | Default Setting |
Rated values | ||||
_:1781:15571:103 | Rated apparent power | 0.20 MVA to 5000.00 MVA | 692.82 MVA | |
Side data | ||||
_:1781:14611:130 | Side number | not assigned Side 1 Side 2 Side 3 |
Side 2 | |
_:1781:14611:210 | MI3ph1 usesMeasP with ID | 0 to 100 | 8 | |
_:1781:14611:215 | CT mismatch M I-3ph 1 | 0.010 to 100.000 | 1.000 | |
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:1781:15571:101 | General:Capacitor reference curr. | 1.00 A to 100000.00 A | 1000.00 A | |
_:1781:15571:102 | General:Capacitor reference volt. | 0.20 kV to 1200.00 kV | 400.00 kV | |
Side data | ||||
_:1781:15571:149 | General:Neutral point | grounded isolated |
isolated | |
_:1781:15571:104 | General:Winding configuration | Y (Wye) D (Delta) Z (Zig-Zag) |
Y (Wye) | |
_:1781:15571:100 | General:Vector group numeral | 0 to 11 | 0 | |
Measurements | ||||
_:1781:14611:158 | Further settings:P, Q sign | not reversed reversed |
not reversed | |
Phase-angle rotation & Vector group numeral

Possible Operational Measured Values of the Capacitor Bank Side Function Group

Generation of Pickup Indication of the Capacitor Bank Side Function Group

Generation of Operate Indication of the Capacitor Bank Side Function Group