Table of Contents

Siemens / “Capacitor bank diff” function group _ Setting & highlights _ SI5219

Table of Contents

Overview

The individual function-group types are stored in the “Capacitor bank diff” function group folder and can be selected. The “Capacitor bank diff.” function group contains the differential protection function and protection-function relevant measured values. In the “Capacitor bank side” function group, all of the functions that are necessary for protecting and supervising a capacitor bank side can be used.

For more detailed information on “Capacitor bank diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of Function-Group Types Capacitor Bank Diff

Function-Group Types Capacitor Bank Diff

Function-Group Type Capacitor Bank Diff


Structure of the Capacitor Bank Diff. Function Group

Structure of the Capacitor Bank Diff. Function Group

Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

Generation of Pickup Indication of the Capacitor Bank Diff. Function Group

Generation of Operate Indication of the Capacitor Bank Diff. Function Group

Generation of Operate Indication of the Capacitor Bank Diff. Function Group

Function-Group Type Capacitor-Bank Side


Structure of the Capacitor Bank Side Function Group

Structure of the Capacitor Bank Side Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:1781:15571:103 Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
Side data
_:1781:14611:130 Side number   not assigned
Side 1
Side 2
Side 3
Side 2
_:1781:14611:210 MI3ph1 usesMeasP with ID   0 to 100 8
_:1781:14611:215 CT mismatch M I-3ph 1   0.010 to 100.000 1.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:1781:15571:101 General:Capacitor reference curr.   1.00 A to 100000.00 A 1000.00 A
_:1781:15571:102 General:Capacitor reference volt.   0.20 kV to 1200.00 kV 400.00 kV
Side data
_:1781:15571:149 General:Neutral point   grounded
isolated
isolated
_:1781:15571:104 General:Winding configuration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:1781:15571:100 General:Vector group numeral   0 to 11 0
Measurements
_:1781:14611:158 Further settings:P, Q sign   not reversed
reversed
not reversed

Phase-angle rotation & Vector group numeral

Phase-angle rotation & Vector group numeral

Possible Operational Measured Values of the Capacitor Bank Side Function Group

Possible Operational Measured Values of the Capacitor Bank Side Function Group

Generation of Pickup Indication of the Capacitor Bank Side Function Group

Generation of Pickup Indication of the Capacitor Bank Side Function Group

Generation of Operate Indication of the Capacitor Bank Side Function Group

Generation of Operate Indication of the Capacitor Bank Side Function Group

error: Content is protected !!