Siemens / Busbar differential protection for single busbar (ANSI 87B) _ Setting & highlights _ SI5086

Table of Contents

Overview

The “Busbar differential protection” function detects busbar short circuits. It is stable in the event of external short-circuits with current-transformer saturation through intelligent saturation-detection methods, and is used for the single busbar.

For more detailed information on “Busbar differential protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Busbar differential protection

Addr. Parameter C Setting Options Default Setting
I-DIFF fast
_:1 I-DIFF unrestr:Mode   off
on
test
off
_:3 I-DIFF unrestr:Threshold   0.5 I/IrObj to 35.0 I/IrObj 10.0 I/IrObj
_:6 I-DIFF unrestr:Operate delay   0.00 s to 60.00 s 0.00 s
_:100 I-DIFF unrestr:Operate & flt.rec. blocked   no
yes
no
I-DIFF unrestr
_:1 I-DIFF unrestr:Mode   off
on
test
off
_:3 I-DIFF unrestr:Threshold   0.5 I/IrObj to 35.0 I/IrObj 10.0 I/IrObj
_:6 I-DIFF unrestr:Operate delay   0.00 s to 60.00 s 0.00 s
_:100 I-DIFF unrestr:Operate & flt.rec. blocked   no
yes
no
I-DIFF: General
_:1 I-DIFF:Mode   off
on
test
off
_:2 I-DIFF:Operate & flt.rec. blocked   no
yes
no
_:6 I-DIFF:Operate delay   0.00 s to 60.00 s 0.00 s
I-DIFF: Operate curve
_:3 I-DIFF:Threshold   0.05 I/IrObj to 2.00 I/IrObj 0.20 I/IrObj
_:100 I-DIFF:Slope 1   0.00 to 0.80 0.30
_:101 I-DIFF:Intersection 1 Irest   0.00 I/IrObj to 5.00 I/IrObj 0.67 I/IrObj
_:102 I-DIFF:Slope 2   0.25 to 0.95 0.70
_:103 I-DIFF:Intersection 2 Irest   1.00 I/IrObj to 20.00 I/IrObj 2.50 I/IrObj
I-DIFF: Starting detection
_:106 I-DIFF:Starting detection   no
yes
no
_:107 I-DIFF:Thresh. startup detection   0.1 I/IrObj to 2.0 I/IrObj 0.1 I/IrObj
_:108 I-DIFF:Factor increasing char.   1.0 to 5.0 2.0
_:109 I-DIFF:Max. perm. Start. time   0.1 s to 180.0 s 5.0 s
I-DIFF: DC offset detection
_:110 I-DIFF:Factor increasing char. DC   1.0 to 5.0 2.3
_:125 I-DIFF:5th harmonics content   10 % to 80 % 30 %
_:126 I-DIFF:Crossblock. time 5th har.   0.00 s to 200.00 s; ∞ 0.00 s
_:127 I-DIFF:Limit Idiff 3., 5. harmonics   0.5 I/IrObj to 20.0 I/IrObj 1.5 I/IrObj
I-DIFF: Ext. fault detection
_:128 I-DIFF:Threshold add-on stabiliz.   1.00 I/IrObj to 20.00 I/IrObj 2.00 I/IrObj
_:129 I-DIFF:Time of add-on stabiliz.   0.00 s to 5.00 s; ∞ 0.30 s
_:130 I-DIFF:Crossblk. time add-on st.   0.00 s to 2.00 s; ∞ 0.30 s

Logic Diagrams & highlights


Basic Principle of Differential Protection Using the Example of 2 Sides

Basic Principle of Differential Protection Using the Example of 2 Sides

Current Stabilization

Current Stabilization

Principle Current Course in External Short Circuit and Temporary Current-Transformer Saturation on One Side

Principle Current Course in External Short Circuit and Temporary Current-Transformer Saturation on One Side

Logic Diagram of the Differential Protection Function

Logic Diagram of the Differential Protection Function

Operate Curve of the Differential Protection Function

Operate Curve of the Differential Protection Function

Amount Correction

Amount Correction

Currents calculation

I-DIFF Differential Protection Function - Currents calculation

Pickup Characteristic of the Differential Protection

Pickup Characteristic of the Differential Protection

Increasing the Characteristic Curve after DC Detection

Increasing the Characteristic Curve after DC Detection

Logic DC Detection

Logic DC Detection

Logic Startup Detection

Logic Startup Detection

Characteristic-Curve Increase at Startup

Characteristic-Curve Increase at Startup

Trip Logic of I-DIFF

Trip Logic of I-DIFF

Instantaneous-Value Method calculations

Instantaneous-Value Method calculations

I-DIFF Fast Characteristic Curve

I-DIFF Fast Characteristic Curve

Curve Plot for Internal Fault with Transformer Saturation (k= 0.65)

Curve Plot for Internal Fault with Transformer Saturation (k= 0.65)

Curve Plot for External Fault with Transformer Saturation (k= 0.65)

Curve Plot for External Fault with Transformer Saturation (k= 0.65)

Logic of the I-DIFF Fast Differential Protection Function

Logic of the I-DIFF Fast Differential Protection Function

I-DIFF Unrestrained Characteristic Curve

I-DIFF Unrestrained Characteristic Curve

Logic of the I-DIFF Unrestrained Differential Protection Function

Logic of the I-DIFF Unrestrained Differential Protection Function

Overall Trip Logic

Overall Trip Logic

Connection Example

Connection Example