Overview

The “Busbar differential protection” function is a selective, safe, and quick protection if busbar short circuits should occur and if circuit breakers fail. The protection can be utilized for a variety of busbar configurations in medium, high, and extra-high voltage systems. It is suitable for switchgear with closed iron core or linearized current transformers, and employs a phase-selective method of measurement.

For more detailed information on “Busbar differential protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Embedding the Busbar Protection Function

Embedding the Busbar Protection Function

Interaction Check Zone and Busbar Section with Busbar Differential Protection

Interaction Check Zone and Busbar Section with Busbar Differential Protection

Setting Parameters


Setting parameters for Busbar protection

Addr. Parameter C Setting Options Default Setting
Diff.Prot. general
_:11821:101 Diff.Prot. general:Rated object current IrObj   100 A to 50000 A 1000 A
_:11821:102 Diff.Prot. general:Add. trip criterion (p. ph.)   nonexistent
existent
nonexistent
_:11821:103 Diff.Prot. general:Trip release supervision   off
alarm w/o prot. block.
protection blocking
off
_:11821:104 Diff.Prot. general:Superv. add. trip criterion   off
alarm w/o prot. block.
protection blocking
off
_:11821:105 Diff.Prot. general:Sens. characteristic   nonexistent
existent
nonexistent
_:11821:106 Diff.Prot. general:Superv.t. BI sens.char.   off
on
off
_:11821:107 Diff.Prot. general:Measure- ment repetition 1 of 1 Alg.   off
on
off
Check zone
_:11911:100 Check zone:Threshold Idiff   0.20 I/IrObj to 4.00 I/IrObj 1.00 I/IrObj
_:11911:101 Check zone:Threshold Id / sens.char.   0.05 I/IrObj to 4.00 I/IrObj 0.25 I/IrObj
_:11911:102 Check zone:Threshold Is / sens.char.   0.00 I/IrObj to 25.00 I/IrObj 4.50 I/IrObj
_:11911:103 Check zone:Thresh. Is / sens.char/BFP   0.00 I/IrObj to 25.00 I/IrObj 5.00 I/IrObj
_:11911:104 Check zone:Stabilization factor k   0.10 to 0.80 0.50
_:11911:110 Check zone:Delay perma- nent release   no
yes
no
Bus zone gen.
_:12091:100 Bus zone gen.:Threshold Idiff   0.20 I/IrObj to 4.00 I/IrObj 1.00 I/IrObj
_:12091:101 Bus zone gen.:Threshold Id /sens.char.   0.05 I/IrObj to 4.00 I/IrObj 0.25 I/IrObj
_:12091:102 Bus zone gen.:Threshold Is / sens.char.   0.00 I/IrObj to 25.00 I/IrObj 5.00 I/IrObj
_:12091:103 Bus zone gen.:Thresh. Is / sens.char/BFP   0.00 I/IrObj to 25.00 I/IrObj 5.00 I/IrObj
_:12091:104 Bus zone gen.:Stabilization factor k   0.10 to 0.80 0.65
Ext. trip BZ
_:11971:100 Ext. trip BZ:Superv.t. Rel. ext. trip BZ   0.06 s to 1.00 s 0.06 s
Cross stab.
_:1 Cross stab.:Mode   off
on
off
_:100 Cross stab.:Cross.stab. factor BZ   0.00 to 1.00 0.40
_:101 Cross stab.:Cross.stab. factor CZ   0.00 to 1.00 0.40

Logic Diagrams & highlights


Formation of the Restraint Current Irest,mod

Formation of the Restraint Current Irest,mod

Standard Characteristic Curve

Standard Characteristic Curve

Sensitive Characteristic Curve

Sensitive Characteristic Curve

Qualitative Representation of the Primary and Secondary Current in a Transformer Approaching Saturation in the Event of a Fault (Direct-Current Component with a Time Constant of Approx. 50 ms)

Qualitative Representation of the Primary and Secondary Current in a Transformer Approaching Saturation in the Event of a Fault (Direct-Current Component with a Time Constant of Approx. 50 ms)

Differential and Restraint Current in the Event of an External Short Circuit and Transformer Saturation

Differential and Restraint Current in the Event of an External Short Circuit and Transformer Saturation

Differential and Restraint Current in the Event of an External Short Circuit – Restraint Current Smoothed

Differential and Restraint Current in the Event of an External Short Circuit - Restraint Current Smoothed

Differential and Smoothed Restraint Current in the Event of an Internal Short Circuit

Differential and Smoothed Restraint Current in the Event of an Internal Short Circuit

Busbar Differential Protection Trip Logic

Busbar Differential Protection Trip Logic

Logic Diagram for the Phase-Selective Release Signal

Logic Diagram for the Phase-Selective Release Signal

Logic Diagram for the Zone-Specific Release Signal

Logic Diagram for the Zone-Specific Release Signal

Disconnector Position Indication

Disconnector Position Indication

Treatment of the Restraint Current for the Check Zone

Treatment of the Restraint Current for the Check Zone

error: Content is protected !!