Siemens / Bus Coupler Differential Protection _ Setting & highlights _ SI5107

Table of Contents

Overview

The “Bus coupler differential protection” uses the currents measured by the two current transformers that are present in the bay. The trip command of the bus coupler differential protection acts on the circuit breaker that is present in the bay.

For more detailed information on “Bus Coupler Differential Protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Setting Parameters


Setting parameters for Bus Coupler Differential Protection

Addr. Parameter C Setting Options Default Setting
Coupler zone
_:1 Coupler zone:Mode   off
on
on
_:101 Coupler zone:Thres.1- ph.f.CT overl   0.1 I/IrObj to 25.0 I/IrObj; ∞ 4.0 I/IrObj
_:102 Coupler zone:Thresh.mul-ph.f.CT overl.   0.1 I/IrObj to 25.0 I/IrObj; ∞ 4.0 I/IrObj

Logic Diagrams & highlights


Fault in the Dead Zone of the Bus Coupler with 2 Current Transformers

Fault in the Dead Zone of the Bus Coupler with 2 Current Transformers

Bus Coupler Differential Protection Logic Diagram

Bus Coupler Differential Protection Logic Diagram

Application Example Thres.1-ph.f.CT overl and Thresh.mul-ph.f.CT overl.

Application Example Thres.1-ph.f.CT overl and Thresh.mul-ph.f.CT overl.

Fault in the Coupler Bay

Fault in the Coupler Bay

Currents with Fault in the Bus Coupler Bay without Switchover to Current Transformer Overlapping

Currents with Fault in the Bus Coupler Bay without Switchover to Current Transformer Overlapping
(1) The end-fault protection sets the bus coupler bay current to 0. This causes a differential current in busbar section 1