GE / Autoreclose (ANSI 79) _ Element settings & highlights _ GU8240

Table of Contents

Overview

The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and three pole modes, in one or two breaker arrangements. The “Autoreclose” element provides four programs with different operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts. The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.

For more detailed information on “Autoreclose” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
C60, C95, D60, L60, L90 CB80 Autoreclose Mode 0 to 3 1 F622 0 (Mode 1 (1
& 3 Pole))
" CB81 Autoreclose Maximum Number of Shots 1 to 4 1 F001 2
" CB82 Autoreclose Block Breaker 1 0 to 4294967295 1 F300 0
" CB84 Autoreclose Close Time Breaker 1 0.1 to 655.35 s 0.01 F001 10
" CB85 Autoreclose Breaker Manual Close 0 to 4294967295 1 F300 0
" CB87 Autoreclose Function 0 to 1 1 F102 0 (Disabled)
" CB88 Autoreclose Block Time Manual Close 0 to 655.35 s 0.01 F001 1000
" CB89 Autoreclose 1P Initiate 0 to 4294967295 1 F300 0
" CB8B Autoreclose 3P Initiate 0 to 4294967295 1 F300 0
" CB8D Autoreclose 3P TD Initiate 0 to 4294967295 1 F300 0
" CB8F Autoreclose Multi-Phase Fault 0 to 4294967295 1 F300 0
" CB91 Autoreclose Breaker 1 Pole Open 0 to 4294967295 1 F300 0
" B93 Autoreclose Breaker 3 Pole Open 0 to 4294967295 1 F300 0
" CB95 Autoreclose 3-Pole Dead Time 1 0 to 655.35 s 0.01 F001 50
" CB96 Autoreclose 3-Pole Dead Time 2 0 to 655.35 s 0.01 F001 120
" CB97 Autoreclose Extend Dead T1 0 to 4294967295 1 F300 0
" CB99 Autoreclose Dead T1 Extension 0 to 655.35 s 0.01 F001 50
" CB9A Autoreclose Reset 0 to 4294967295 1 F300 0
" CB9C Autoreclose Reset Time 0 to 655.35 s 0.01 F001 6000
" CB9D Autoreclose Breaker Closed 0 to 4294967295 1 F300 0
" CB9F Autoreclose Block 0 to 4294967295 1 F300 0
" CBA1 Autoreclose Pause 0 to 4294967295 1 F300 0
" CBA3 Autoreclose Incomplete Sequence Time 0 to 655.35 s 0.01 F001 500
" CBA4 Autoreclose Block Breaker 2 0 to 4294967295 1 F300 0
" CBA6 Autoreclose Close Time Breaker 2 0.1 to 655.35 s 0.01 F001 10
" CBA7 Autoreclose Transfer 1 to 2 0 to 1 1 F126 0 (No)
" CBA8 Autoreclose Transfer 2 to 1 0 to 1 1 F126 0 (No)
" CBA9 Autoreclose Breaker 1 Fail Option 0 to 1 1 F081 0 (Continue)
" CBAA Autoreclose Breaker 2 Fail Option 0 to 1 1 F081 0 (Continue)
" CBAB Autoreclose 1P Dead Time 0 to 655.35 s 0.01 F001 100
" CBAC Autoreclose Breaker Sequence 0 to 4 1 F082 3 (1 – 2)
" CBAD Autoreclose Transfer Time 0 to 655.35 s 0.01 F001 400
" CBAE Autoreclose Event 0 to 1 1 F102 0 (Disabled)
" CBAF Autoreclose 3P Dead Time 3 0 to 655.35 s 0.01 F001 200
" CBB0 Autoreclose 3P Dead Time 4 0 to 655.35 s 0.01 F001 400
" CBB1 Autoreclose Bus Fault Initiate 0 to 4294967295 1 F300 0
" CBB3 Autoreclose Initiate Mode 0 to 1 1 F610 0 (Protection AND CB)
" CBB4 Autoreclose Mode Aut 0 to 3 1 F622 0 (Mode 1 (1
& 3 Pole))
" CBB5 Autoreclose Mode 1 Activation 0 to 4294967295 1 F300 0
" CBB7 Autoreclose Mode 2 Activation 0 to 4294967295 1 F300 0
" CBB9 Autoreclose Mode 3 Activation 0 to 4294967295 1 F300 0
" CBBB Autoreclose Mode 4 Activation 0 to 4294967295 1 F300 0
F081 0 = Continue, 1 = Lockout
F082 0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1
F102 0 = Disabled, 1 = Enabled
F126 0 = No, 1 = Yes
F610 0 = Protection AND CB, 1 = Protection only
F622 0 = Mode 1 (1 & 3 Pole), 1 = Mode 2 (1 Pole), 2 = Mode 3 (3 Pole – A), 3 = Mode 4 (3 Pole – B)

Logics & highlights


Autoreclose states

Autoreclose states

Autoreclose programs

Autoreclose programs

Single-pole autoreclose logic (Sheet 1 of 3)

Single-pole autoreclose logic (Sheet 1 of 3)

Mode control logic

Mode control logic

Single-pole autoreclose logic (Sheet 2 of 3)

Single-pole autoreclose logic (Sheet 2 of 3)

Single-pole autoreclose logic (Sheet 3 of 3)

Single-pole autoreclose logic (Sheet 3 of 3)

Example of reclosing sequence

Example of reclosing sequence