Overview
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and three pole modes, in one or two breaker arrangements. The “Autoreclose” element provides four programs with different operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts. The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.
For more detailed information on “Autoreclose” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
C60, C95, D60, L60, L90 | CB80 | Autoreclose Mode | 0 to 3 | — | 1 | F622 | 0 (Mode 1 (1 & 3 Pole)) |
" | CB81 | Autoreclose Maximum Number of Shots | 1 to 4 | — | 1 | F001 | 2 |
" | CB82 | Autoreclose Block Breaker 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB84 | Autoreclose Close Time Breaker 1 | 0.1 to 655.35 | s | 0.01 | F001 | 10 |
" | CB85 | Autoreclose Breaker Manual Close | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB87 | Autoreclose Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | CB88 | Autoreclose Block Time Manual Close | 0 to 655.35 | s | 0.01 | F001 | 1000 |
" | CB89 | Autoreclose 1P Initiate | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB8B | Autoreclose 3P Initiate | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB8D | Autoreclose 3P TD Initiate | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB8F | Autoreclose Multi-Phase Fault | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB91 | Autoreclose Breaker 1 Pole Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | B93 | Autoreclose Breaker 3 Pole Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB95 | Autoreclose 3-Pole Dead Time 1 | 0 to 655.35 | s | 0.01 | F001 | 50 |
" | CB96 | Autoreclose 3-Pole Dead Time 2 | 0 to 655.35 | s | 0.01 | F001 | 120 |
" | CB97 | Autoreclose Extend Dead T1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB99 | Autoreclose Dead T1 Extension | 0 to 655.35 | s | 0.01 | F001 | 50 |
" | CB9A | Autoreclose Reset | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB9C | Autoreclose Reset Time | 0 to 655.35 | s | 0.01 | F001 | 6000 |
" | CB9D | Autoreclose Breaker Closed | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CB9F | Autoreclose Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBA1 | Autoreclose Pause | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBA3 | Autoreclose Incomplete Sequence Time | 0 to 655.35 | s | 0.01 | F001 | 500 |
" | CBA4 | Autoreclose Block Breaker 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBA6 | Autoreclose Close Time Breaker 2 | 0.1 to 655.35 | s | 0.01 | F001 | 10 |
" | CBA7 | Autoreclose Transfer 1 to 2 | 0 to 1 | — | 1 | F126 | 0 (No) |
" | CBA8 | Autoreclose Transfer 2 to 1 | 0 to 1 | — | 1 | F126 | 0 (No) |
" | CBA9 | Autoreclose Breaker 1 Fail Option | 0 to 1 | — | 1 | F081 | 0 (Continue) |
" | CBAA | Autoreclose Breaker 2 Fail Option | 0 to 1 | — | 1 | F081 | 0 (Continue) |
" | CBAB | Autoreclose 1P Dead Time | 0 to 655.35 | s | 0.01 | F001 | 100 |
" | CBAC | Autoreclose Breaker Sequence | 0 to 4 | — | 1 | F082 | 3 (1 – 2) |
" | CBAD | Autoreclose Transfer Time | 0 to 655.35 | s | 0.01 | F001 | 400 |
" | CBAE | Autoreclose Event | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | CBAF | Autoreclose 3P Dead Time 3 | 0 to 655.35 | s | 0.01 | F001 | 200 |
" | CBB0 | Autoreclose 3P Dead Time 4 | 0 to 655.35 | s | 0.01 | F001 | 400 |
" | CBB1 | Autoreclose Bus Fault Initiate | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBB3 | Autoreclose Initiate Mode | 0 to 1 | — | 1 | F610 | 0 (Protection AND CB) |
" | CBB4 | Autoreclose Mode Aut | 0 to 3 | — | 1 | F622 | 0 (Mode 1 (1 & 3 Pole)) |
" | CBB5 | Autoreclose Mode 1 Activation | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBB7 | Autoreclose Mode 2 Activation | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBB9 | Autoreclose Mode 3 Activation | 0 to 4294967295 | — | 1 | F300 | 0 |
" | CBBB | Autoreclose Mode 4 Activation | 0 to 4294967295 | — | 1 | F300 | 0 |
F081 | 0 = Continue, 1 = Lockout | ||||||
F082 | 0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1 | ||||||
F102 | 0 = Disabled, 1 = Enabled | ||||||
F126 | 0 = No, 1 = Yes | ||||||
F610 | 0 = Protection AND CB, 1 = Protection only | ||||||
F622 | 0 = Mode 1 (1 & 3 Pole), 1 = Mode 2 (1 Pole), 2 = Mode 3 (3 Pole – A), 3 = Mode 4 (3 Pole – B) | ||||||
Logics & highlights
Autoreclose states

Autoreclose programs

Single-pole autoreclose logic (Sheet 1 of 3)

Mode control logic

Single-pole autoreclose logic (Sheet 2 of 3)

Single-pole autoreclose logic (Sheet 3 of 3)

Example of reclosing sequence