Overview
The “Automatic reclosing” function automatically closes overhead lines after arc short-circuits. It is only permissible for overhead lines, because only the possibility of self-activated extinguishing of an arc short-circuit exists here. It can be controlled by integrated protection functions and by external protection devices. The automatic reclosing can occur through an external automatic reclosing function via binary inputs.
Process Diagram of a Two-Time Reclosing With Action Time (2nd Reclosing Successful)

For more detailed information on “Automatic reclosing” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function

Structure/Embedding of the Cyclic Automatic Reclosing Function

Structure/Embedding of the Automatic Reclosing Function With Adaptive Dead Time (ADT)

Structure/Embedding of the Operating Function With External Automatic Reclosing Function

Function Control for the Automatic Reclosing Function

Setting Parameters
Setting Parameters for Cyclic Automatic Reclosing Function
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:6601:1 | General:Mode | off on test |
on | |
_:6601:101 | General:79 operating mode | with op., w/o act. time with op., with act. time w.pickup, w/o act. time w.pickup, w. action time |
with op., with act. time | |
_:6601:102 | General:CB ready check bef. start | no yes |
no | |
_:6601:103 | General:Reclai. time aft.succ.cyc. | 0.50 s to 300.00 s | 3.00 s | |
_:6601:104 | General:Block. time aft. man.close | 0.00 s to 300.00 s | 1.00 s | |
_:6601:105 | General:Start signal supervis.time | 0.01 s to 300.00 s | 0.13 s | |
_:6601:106 | General:CB ready superv. time | 0.01 s to 300.00 s | 3.00 s | |
_:6601:107 | General:3-pole operate by 79 | no yes |
yes | |
_:6601:108 | General:Evolving-fault detection | with trip with pickup |
with trip | |
_:6601:109 | General:Response to evolv. faults | strt. evol.flt.dead time blocks 79 |
blocks 79 | |
_:6601:110 | General:Max. dead-time delay | 0.01 s to 300.00 s | 0.50 s | |
_:6601:111 | General:Max. dead-time extension | 0.00 s to 300.00 s; ∞ | 1.20 s | |
_:6601:112 | General:Send delay f. remot. close | 0.00 s to 300.00 s; ∞ | ∞ | |
DLC, RDT | ||||
_:6601:113 | General:Dead-line check/ reduc.d.t | without Reduced dead t. RDT Dead-line check DLC |
without | |
_:6601:114 | General:Voltage supervi- sion time | 0.10 s to 30.00 s | 0.10 s | |
_:6601:115 | General:Volt. thres.f. live line/bus | 0.300 V to 340.000 V | 48.000 V | |
_:6601:116 | General:Volt.thres. f. dead line/bus | 0.300 V to 340.000 V | 30.000 V | |
Cycle 1 | ||||
_:6571:102 | Cycle 1:Start from idle state allow. | no yes |
yes | |
_:6571:103 | Cycle 1:Action time | 0.00 s to 300.00 s; ∞ | 0.20 s | |
_:6571:108 | Cycle 1:Dead time aft. 3- pole trip | 0.00 s to 1800.00 s; ∞ | 0.50 s | |
_:6571:107 | Cycle 1:Dead time aft. 1- pole trip | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:104 | Cycle 1:Dead time aft.1ph. pickup | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:105 | Cycle 1:Dead time aft.2ph. pickup | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:106 | Cycle 1:Dead time aft.3ph. pickup | 0.00 s to 1800.00 s; ∞ | 0.50 s | |
_:6571:109 | Cycle 1:Dead time aft. evolv. fault | 0.01 s to 1800.00 s | 1.20 s | |
_:6571:111 | Cycle 1:CB ready check bef.close | no yes |
no | |
_:6571:110 | Cycle 1:Synchroch. aft. 3-pole d.t. | none internal external |
none | |
_:6571:112 | Cycle 1:Intern. synchro- check with | Setting options depend on configuration | ||
Setting Parameters for Automatic Reclosing Function with Adaptive Dead Time (ADT)
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:6601:1 | General:Mode | off on test |
on | |
_:6601:101 | General:79 operating mode | with op., w/o act. time with op., with act. time w.pickup, w/o act. time w.pickup, w. action time |
with op., with act. time | |
_:6601:102 | General:CB ready check bef. start | no yes |
no | |
_:6601:103 | General:Reclai. time aft.succ.cyc. | 0.50 s to 300.00 s | 3.00 s | |
_:6601:104 | General:Block. time aft. man.close | 0.00 s to 300.00 s | 1.00 s | |
_:6601:105 | General:Start signal supervis.time | 0.01 s to 300.00 s | 0.13 s | |
_:6601:106 | General:CB ready superv. time | 0.01 s to 300.00 s | 3.00 s | |
_:6601:107 | General:3-pole operate by 79 | no yes |
yes | |
_:6601:111 | General:Max. dead-time extension | 0.00 s to 300.00 s; ∞ | 1.20 s | |
_:6601:114 | General:Voltage supervi- sion time | 0.10 s to 30.00 s | 0.10 s | |
_:6601:115 | General:Volt. thres.f. live line/bus | 0.300 V to 340.000 V | 48.000 V | |
ADT | ||||
_:6631:101 | ADT:1-pole trip allowed | no yes |
no | |
_:6631:104 | ADT:Action time | 0.00 s to 300.00 s; ∞ | 0.20 s | |
_:6631:105 | ADT:Maximum dead time | 0.50 s to 3000.00 s | 5.00 s | |
_:6631:102 | ADT:CB ready check bef.close | no yes |
no | |
_:6631:103 | ADT:Synchroch. aft. 3-pole d.t. | none internal external |
none | |
_:6631:106 | ADT:Intern. synchrocheck with | Setting options depend on configuration | ||
Logic Diagrams & highlights
Signals between Protection Functions and Automatic Reclosing Functions

Operating-Mode Signal Examples: With Tripping/With Action Time

Operating-Mode Signal Examples: With Pickup/With Action Time

Operating-Mode Signal Examples: With Tripping/Without Action Time

Operating-Mode Signal Examples: With Pickup/Without Action Time

Input Logic for Operating Modes: With Tripping

Input Logic for Operating Modes: With Pickup

Logic for Function Block Start

Cycle Control with Operating Mode: With Tripping/With Action Time

Cycle Control with Operating Mode: With Pickup/With Action Time

Cycle Control with Operating Mode: With Tripping/Without Action Time

Cycle Control with Operating Mode: With Pickup/Without Action Time

Stage Release for Protection Functions in the 1st Automatic Reclosing Cycle

Stage Release for Protection Functions Starting With the 2nd Automatic Reclosing Cycle

Cyclic Automatic Reclosing Function – Logic of the Dead Time for the Operating Modes: With Tripping

Cyclic Automatic Reclosing Function – Logic of the Dead Time for the Operating Modes: With Pickup

Cyclic Automatic Reclosing Function – Example for an Evolving Fault

Cyclic Automatic Reclosing Function – Logic of Evolving-Fault Detection

Cyclic Reclosing Function: Logic for the Closing Indication

Cyclic Reclosing Function: Logic for the Query of the Circuit-Breaker Readiness Directly before Closing

Cyclic Reclosing Function: Logic for the Inquiry of the Synchronism

Cyclic Reclosing Function: Logic for the reclaim time

Cyclic Automatic Reclosing: Logic for the Circuit-Breaker Readiness

Cyclic Automatic Reclosing: Logic for Circuit-Breaker Position and Supervision

Cyclic Reclosing Function: Blocking Logic in the Example for a 1-Pole Cycle (Static and Dynamic Blocking)

Cyclic Reclosing Function: Logic for the Functions of Reduced Dead Time and Dead-Line Check

Example for Adaptive Dead Time (ADT)

Connection of an External Automatic Reclosing Function