Overview
The “Automatic reclosing” function automatically closes overhead lines after arc short-circuits. It is only permissible for overhead lines, because only the possibility of self-activated extinguishing of an arc short-circuit exists here. It can be controlled by integrated protection functions and by external protection devices. The automatic reclosing can occur through an external automatic reclosing function via binary inputs.
Process Diagram of a Two-Time Reclosing With Action Time (2nd Reclosing Successful)
For more detailed information on “Automatic reclosing” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Structure/Embedding of the Cyclic Automatic Reclosing Function
Structure/Embedding of the Automatic Reclosing Function With Adaptive Dead Time (ADT)
Structure/Embedding of the Operating Function With External Automatic Reclosing Function
Function Control for the Automatic Reclosing Function
Setting Parameters
Setting Parameters for Cyclic Automatic Reclosing Function
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:6601:1 | General:Mode | off on test |
on | |
_:6601:101 | General:79 operating mode | with op., w/o act. time with op., with act. time w.pickup, w/o act. time w.pickup, w. action time |
with op., with act. time | |
_:6601:102 | General:CB ready check bef. start | no yes |
no | |
_:6601:103 | General:Reclai. time aft.succ.cyc. | 0.50 s to 300.00 s | 3.00 s | |
_:6601:104 | General:Block. time aft. man.close | 0.00 s to 300.00 s | 1.00 s | |
_:6601:105 | General:Start signal supervis.time | 0.01 s to 300.00 s | 0.13 s | |
_:6601:106 | General:CB ready superv. time | 0.01 s to 300.00 s | 3.00 s | |
_:6601:107 | General:3-pole operate by 79 | no yes |
yes | |
_:6601:108 | General:Evolving-fault detection | with trip with pickup |
with trip | |
_:6601:109 | General:Response to evolv. faults | strt. evol.flt.dead time blocks 79 |
blocks 79 | |
_:6601:110 | General:Max. dead-time delay | 0.01 s to 300.00 s | 0.50 s | |
_:6601:111 | General:Max. dead-time extension | 0.00 s to 300.00 s; ∞ | 1.20 s | |
_:6601:112 | General:Send delay f. remot. close | 0.00 s to 300.00 s; ∞ | ∞ | |
DLC, RDT | ||||
_:6601:113 | General:Dead-line check/ reduc.d.t | without Reduced dead t. RDT Dead-line check DLC |
without | |
_:6601:114 | General:Voltage supervi- sion time | 0.10 s to 30.00 s | 0.10 s | |
_:6601:115 | General:Volt. thres.f. live line/bus | 0.300 V to 340.000 V | 48.000 V | |
_:6601:116 | General:Volt.thres. f. dead line/bus | 0.300 V to 340.000 V | 30.000 V | |
Cycle 1 | ||||
_:6571:102 | Cycle 1:Start from idle state allow. | no yes |
yes | |
_:6571:103 | Cycle 1:Action time | 0.00 s to 300.00 s; ∞ | 0.20 s | |
_:6571:108 | Cycle 1:Dead time aft. 3- pole trip | 0.00 s to 1800.00 s; ∞ | 0.50 s | |
_:6571:107 | Cycle 1:Dead time aft. 1- pole trip | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:104 | Cycle 1:Dead time aft.1ph. pickup | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:105 | Cycle 1:Dead time aft.2ph. pickup | 0.00 s to 1800.00 s; ∞ | 1.20 s | |
_:6571:106 | Cycle 1:Dead time aft.3ph. pickup | 0.00 s to 1800.00 s; ∞ | 0.50 s | |
_:6571:109 | Cycle 1:Dead time aft. evolv. fault | 0.01 s to 1800.00 s | 1.20 s | |
_:6571:111 | Cycle 1:CB ready check bef.close | no yes |
no | |
_:6571:110 | Cycle 1:Synchroch. aft. 3-pole d.t. | none internal external |
none | |
_:6571:112 | Cycle 1:Intern. synchro- check with | Setting options depend on configuration | ||
Setting Parameters for Automatic Reclosing Function with Adaptive Dead Time (ADT)
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:6601:1 | General:Mode | off on test |
on | |
_:6601:101 | General:79 operating mode | with op., w/o act. time with op., with act. time w.pickup, w/o act. time w.pickup, w. action time |
with op., with act. time | |
_:6601:102 | General:CB ready check bef. start | no yes |
no | |
_:6601:103 | General:Reclai. time aft.succ.cyc. | 0.50 s to 300.00 s | 3.00 s | |
_:6601:104 | General:Block. time aft. man.close | 0.00 s to 300.00 s | 1.00 s | |
_:6601:105 | General:Start signal supervis.time | 0.01 s to 300.00 s | 0.13 s | |
_:6601:106 | General:CB ready superv. time | 0.01 s to 300.00 s | 3.00 s | |
_:6601:107 | General:3-pole operate by 79 | no yes |
yes | |
_:6601:111 | General:Max. dead-time extension | 0.00 s to 300.00 s; ∞ | 1.20 s | |
_:6601:114 | General:Voltage supervi- sion time | 0.10 s to 30.00 s | 0.10 s | |
_:6601:115 | General:Volt. thres.f. live line/bus | 0.300 V to 340.000 V | 48.000 V | |
ADT | ||||
_:6631:101 | ADT:1-pole trip allowed | no yes |
no | |
_:6631:104 | ADT:Action time | 0.00 s to 300.00 s; ∞ | 0.20 s | |
_:6631:105 | ADT:Maximum dead time | 0.50 s to 3000.00 s | 5.00 s | |
_:6631:102 | ADT:CB ready check bef.close | no yes |
no | |
_:6631:103 | ADT:Synchroch. aft. 3-pole d.t. | none internal external |
none | |
_:6631:106 | ADT:Intern. synchrocheck with | Setting options depend on configuration | ||