Overview
The individual function-group types are stored in the “Auto transformer diff” function group folder. The “Auto transf. Diff.” function group contains the differential protection function and protection function relevant measured values. In the “Auto transf. auto side” function group all functions required for protection and supervision of an auto transformer auto side can be used. In the “Auto transf. comp. side” all the functions required for protection and supervision of an auto transformer compensation side can be used. In the “Auto transf. ground side” function group all the functions required for protection and supervision of an auto transformer ground side can be used. In the “Auto transf. neutral point” function group all the necessary functions for protection and for supervision of an auto transformer, which are related to a neutral-point current, are used.
For more detailed information on “Auto transformer diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Function-Group Types Auto Transformer Diff.
Function-Group Type Auto Transformer Differential Protection
Structure of the Auto Transf. Diff. Function Group
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:91:149 | General:Neutral point | grounded isolated |
grounded | |
Generation of Pickup Indication of the Auto Transformer Diff. Function Group
Generation of Operate Indication of the Auto Transformer Diff. Function Group
Function-Group Type Auto Transformer Auto Side
Structure of the Auto Transf. Auto Side Function Group
Write-Protected Settings
Addr. | Parameters | C | Range of Values | Default Setting |
Rated values | ||||
_:91:101 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
Side data | ||||
_:91:130 | General:Side number | not assigned Side 1 Side 2 Side 3 Side 4 Side 5 |
not assigned | |
_:91:210 | General:MI3ph1 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:211 | General:MI3ph2 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:212 | General:MI3ph3 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:213 | General:MI3ph4 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:215 | General:CT mismatch M I-3ph 1 | 0.000 to 100.000 | 0.000 | |
_:91:216 | General:CT mismatch M I-3ph 1 IN | 0.000 to 100.000 | 0.000 | |
_:91:217 | General:CT mismatch M I-3ph 2 | 0.000 to 100.000 | 0.000 | |
_:91:218 | General:CT mismatch M I-3ph 2 IN | 0.000 to 100.000 | 0.000 | |
_:91:219 | General:CT mismatch M I-3ph 3 | 0.000 to 100.000 | 0.000 | |
_:91:220 | General:CT mismatch M I-3ph 3 IN | 0.000 to 100.000 | 0.000 | |
_:91:221 | General:CT mismatch M I-3ph 4 | 0.000 to 100.000 | 0.000 | |
_:91:222 | General:CT mismatch M I-3ph 4 IN | 0.000 to 100.000 | 0.000 | |
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:91:103 | General:Rated apparent power | 0.20 MVA to 5000.00 MVA | 692.82 MVA | |
_:91:102 | General:Rated voltage | 0.40 kVto 800.00 kV | 400.00 kV | |
Measurements | ||||
_:91:158 | General:P, Q sign | not reversed reversed |
not reversed | |
Possible Operational Measured Values of the Auto Transformer Auto Side Function Group
Generation of Pickup Indication of the Auto Transformer Auto Side Function Group
Generation of Operate Indication of the Auto Transformer Auto Side Function Group
Function-Group Type Auto Transformer Compensation Side
Structure of the Auto Transf. Comp. Side Function Group
Write-Protected Settings
Addr. | Parameters | C | Range of Values | Default Setting |
Rated values | ||||
_:91:101 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
Side data | ||||
_:91:130 | General:Side number | not assigned Side 1 Side 2 Side 3 Side 4 Side 5 |
not assigned | |
_:91:210 | General:MI3ph1 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:211 | General:MI3ph2 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:212 | General:MI3ph3 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:213 | General:MI3ph4 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:214 | General:M I-1ph uses MeasP with ID | 0 to 100 | 0 | |
_:91:215 | General:CT mismatch M I-3ph 1 | 0.000 to 100.000 | 0.000 | |
_:91:216 | General:CT mismatch M I-3ph 1 IN | 0.000 to 100.000 | 0.000 | |
_:91:217 | General:CT mismatch M I-3ph 2 | 0.000 to 100.000 | 0.000 | |
_:91:218 | General:CT mismatch M I-3ph 2 IN | 0.000 to 100.000 | 0.000 | |
_:91:219 | General:CT mismatch M I-3ph 3 | 0.000 to 100.000 | 0.000 | |
_:91:220 | General:CT mismatch M I-3ph 3 IN | 0.000 to 100.000 | 0.000 | |
_:91:221 | General:CT mismatch M I-3ph 4 | 0.000 to 100.000 | 0.000 | |
_:91:222 | General:CT mismatch M I-3ph 3 IN | 0.000 to 100.000 | 0.000 | |
_:91:223 | General:CT mismatch M I-1ph | 0.000 to 100.000 | 0.000 | |
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:91:103 | General:Rated apparent power | 0.20 MVA to 5000.00 MVA | 692.82 MVA | |
_:91:102 | General:Rated voltage | 0.300 V to 340.000 V | 40 000.000 V | |
Side data | ||||
_:91:149 | General:Neutral point | grounded isolated |
isolated | |
_:91:104 | General:Winding config- uration | Y (Wye) D (Delta) Z (Zig-Zag) |
D (Delta) | |
_:91:163 | General:Vector group numeral | 0 1 2 3 4 5 6 7 8 9 10 11 user-defined |
1 | |
Measurements | ||||
_:91:158 | General:P, Q sign | not reversed reversed |
not reversed | |
Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group
Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group
Generation of Operate Indication of the Auto Transformer Comp. Side Function Group
Function-Group Type Auto Transformer Ground Side
Structure of the Auto Transformer Ground Side Function Group
Write-Protected Settings
Addr. | Parameters | C | Range of Values | Default Setting |
Rated values | ||||
_:91:101 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
Side data | ||||
_:91:130 | General:Side number | not assigned Side 1 Side 2 Side 3 Side 4 Side 5 |
not assigned | |
_:91:210 | General:MI3ph1 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:215 | General:CT mismatch M I-3ph 1 | 0.000 to 100.000 | 0.000 | |
_:91:216 | General:CT mismatch M I-3ph 1 IN | 0.000 to 100.000 | 0.000 | |
Possible Operational Measured Values of the Auto Transformer Ground Side Function Group
Generation of Pickup Indication of the Auto Transformer Ground Side Function Group
Generation of Operate Indication of the Auto Transformer Ground Side Function Group
Function-Group Type Auto Transformer Neutral Point
Structure of the Auto Transf. Neutral Point Function Group
Write-Protected Settings
Addr. | Parameter | C | Range of Values | Default Setting |
Rated values | ||||
_:9421:101 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
_:9421:102 | General:Rated voltage | 0.20 kV to 1 200.00 kV | 400 kV | |
_:9421:103 | General:Rated apparent power | 0.20 MVA to 5 000.00 MVA | 692.82 MVA | |
_:9421:104 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
_:9421:105 | General:Rated voltage | 0.20 kV to 1 200.00 kV | 400 kV | |
Power-system data | ||||
_:9421:214 | General:M I-1ph uses MeasP with ID | 0 to 100 | 0 | |
_:9421:223 | General:CT mismatch M I-1ph | 0.00 to 100.00 | 0.000 | |