Siemens / “Auto transformer diff” function group _ Setting & highlights _ SI5208

Table of Contents

Overview

The individual function-group types are stored in the “Auto transformer diff” function group folder. The “Auto transf. Diff.” function group contains the differential protection function and protection function relevant measured values. In the “Auto transf. auto side” function group all functions required for protection and supervision of an auto transformer auto side can be used. In the “Auto transf. comp. side” all the functions required for protection and supervision of an auto transformer compensation side can be used. In the “Auto transf. ground side” function group all the functions required for protection and supervision of an auto transformer ground side can be used. In the “Auto transf. neutral point” function group all the necessary functions for protection and for supervision of an auto transformer, which are related to a neutral-point current, are used.

For more detailed information on “Auto transformer diff” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Function-Group Types Auto Transformer Diff.

Function-Group Types Auto Transformer Diff.

Function-Group Type Auto Transformer Differential Protection


Structure of the Auto Transf. Diff. Function Group

Structure of the Auto Transf. Diff. Function Group

Settings

Addr. Parameter C Setting Options Default Setting
General
_:91:149 General:Neutral point   grounded
isolated
grounded

Generation of Pickup Indication of the Auto Transformer Diff. Function Group

Generation of Pickup Indication of the Auto Transformer Diff. Function Group

Generation of Operate Indication of the Auto Transformer Diff. Function Group

Generation of Operate Indication of the Auto Transformer Diff. Function Group

Function-Group Type Auto Transformer Auto Side


Structure of the Auto Transf. Auto Side Function Group

Structure of the Auto Transf. Auto Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.40 kVto 800.00 kV 400.00 kV
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Auto Transformer Auto Side Function Group

Possible Operational Measured Values of the Auto Transformer Auto Side Function Group

Generation of Pickup Indication of the Auto Transformer Auto Side Function Group

Generation of Pickup Indication of the Auto Transformer Auto Side Function Group

Generation of Operate Indication of the Auto Transformer Auto Side Function Group

Generation of Operate Indication of the Auto Transformer Auto Side Function Group

Function-Group Type Auto Transformer Compensation Side


Structure of the Auto Transf. Comp. Side Function Group

Structure of the Auto Transf. Comp. Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:223 General:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.300 V to 340.000 V 40 000.000 V
Side data
_:91:149 General:Neutral point   grounded
isolated
isolated
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
D (Delta)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
1
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group

Possible Operational Measured Values of the Auto Transformer Comp. Side Function Group

Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group

Generation of Pickup Indication of the Auto Transformer Comp. Side Function Group

Generation of Operate Indication of the Auto Transformer Comp. Side Function Group

Generation of Operate Indication of the Auto Transformer Comp. Side Function Group

Function-Group Type Auto Transformer Ground Side


Structure of the Auto Transformer Ground Side Function Group

Structure of the Auto Transformer Ground Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000

Possible Operational Measured Values of the Auto Transformer Ground Side Function Group

Possible Operational Measured Values of the Auto Transformer Ground Side Function Group

Generation of Pickup Indication of the Auto Transformer Ground Side Function Group

Generation of Pickup Indication of the Auto Transformer Ground Side Function Group

Generation of Operate Indication of the Auto Transformer Ground Side Function Group

Generation of Operate Indication of the Auto Transformer Ground Side Function Group

Function-Group Type Auto Transformer Neutral Point


Structure of the Auto Transf. Neutral Point Function Group

Structure of the Auto Transf. Neutral Point Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:9421:101 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:102 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
_:9421:103 General:Rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA
_:9421:104 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:105 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
Power-system data
_:9421:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:9421:223 General:CT mismatch M I-1ph   0.00 to 100.00 0.000

Operational Measured Values of the Auto Transf. Neutral Point Function Group

Operational Measured Values of the Auto Transf. Neutral Point Function Group

Generation of Pickup Indication of the Auto Transf. Neutral Point Function Group

Generation of Pickup Indication of the Auto Transf. Neutral Point Function Group

Generation of Operate Indication of the Auto Transf. Neutral Point Function Group

Generation of Operate Indication of the Auto Transf. Neutral Point Function Group