Siemens / Arc protection _ Setting & highlights _ SI5071

Table of Contents

Overview

The “Arc protection” function detects arcs in air-insulated switchgear parts without delay and in a fail-safe way, limits system damage through instantaneous high-speed tripping, protects systems from thermal overload, increases safety of personnel, trips in a 3-pole way, and is suitable for use in all voltage levels.

For more detailed information on “Arc protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions click here.


Structure/Embedding of the Function

Structure/Embedding of the Arc protection Function

Setting Parameters


Setting parameters for Arc protection Function

Addr. Parameter C Setting Options Default Setting
General
_:2311:1 General:Mode   off
on
test
on
_:2311:2 General:Sensor supervi- sion   no
yes
yes
_:2311:3 General:Threshold I> 1 A @ 100 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 10.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 2.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 10.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 10.000 A
_:2311:4 General:Threshold 3I0> 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
Stage 1
_:14551:1 Stage 1:Mode   off
on
test
off
_:14551:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:14551:9 Stage 1:External trip initiation   no
light
current
no
_:14551:8 Stage 1:Operating mode   light only
current and light
current and light
_:14551:11 Stage 1:Sensor   point sensor
line sensor
custom
point sensor
_:14551:7 Stage 1:Threshold light   -34.00 dB to -10.00 dB -20.00 dB
_:14551:10 Stage 1:Channel   Setting options depend on configuration  
Stage 2
_:14552:1 Stage 2:Mode   off
on
test
off
_:14552:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:14552:9 Stage 2:External trip initiation   no
light
current
no
_:14552:8 Stage 2:Operating mode   light only
current and light
current and light
_:14552:11 Stage 2:Sensor   point sensor
line sensor
custom
point sensor
_:14552:7 Stage 2:Threshold light   -34.00 dB to -10.00 dB -20.00 dB
_:14552:10 Stage 2:Channel   Setting options depend on configuration  
Stage 3
_:14553:1 Stage 3:Mode   off
on
test
off
_:14553:2 Stage 3:Operate & flt.rec. blocked   no
yes
no
_:14553:9 Stage 3:External trip initiation   no
light
current
no
_:14553:8 Stage 3:Operating mode   light only
current and light
 
_:14553:11 Stage 3:Sensor   point sensor
line sensor
custom
point sensor
_:14553:7 Stage 3:Threshold light   -34.00 dB to -10.00 dB -20.00 dB
_:14553:10 Stage 3:Channel   Setting options depend on configuration  

Logic Diagrams & highlights


General Logic Diagram of the Function Block

General Logic Diagram of the Function Block

Logic Diagram of the Stage

Logic Diagram of the Stage

Layout and Connection of the Optical Point Sensors (Operating Mode = Light only)

Layout and Connection of the Optical Point Sensors (Operating Mode = Light only)

Layout and Connection of the Optical Point Sensors (Operating Mode = Current and Light)


Arc Protection with External Trip Initiation

Arc Protection with External Trip Initiation

Layout and Connection of the Optical Line Sensors (Operating Mode = Current and Light)

Layout and Connection of the Optical Line Sensors (Operating Mode = Current and Light)