Overview

“Analog inputs” (input channels) must be configured and set properly in order to get correct measurement results and correct protection operations. For power measuring, all directional and differential functions, the directions of the input currents must be defined in order to reflect the way the current transformers are installed/connected in the field ( primary and secondary connections ). Measuring and protection algorithms in the IED use primary system quantities. Setting values are in primary quantities as well and it is important to set the data about the connected current and voltage transformers properly.

For more detailed information on “Analog inputs”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Signals & Setting Parameters


TRM_12I Output signals

TRM_12I Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(I) STRING Analogue current input 10
CH11(I) STRING Analogue current input 11
CH12(I) STRING Analogue current input 12

TRM_6I_6U Output signals

TRM_6I_6U Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(U) STRING Analogue voltage input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

TRM_6I Output signals

TRM_6I Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6

TRM_7I_5U Output signals

TRM_7I_5U Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

TRM_9I_3U Output signals

TRM_9I_3U Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

TRM_10I_2U Output signals

TRM_10I_2U Output signals
Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(I) STRING Analogue current input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

AISVBAS Non group settings (basic)

AISVBAS Non group settings (basic)
Name Values (Range) Unit Step Default Description
PhaseAngleRef TRM40-Ch1 – Ch12
TRM41-Ch1 – Ch12
MU1-L1I – L4I
MU1-L1U – L4U
MU2-L1I – L4I
MU2-L1U – L4U
MU3-L1I – L4I
MU3-L1U – L4U
MU4-L1I – L4I
MU4-L1U – L4U
MU5-L1I – L4I
MU5-L1U – L4U
MU6-L1I – L4I
MU6-L1U – L4U
MU7-L1I – L4I
MU7-L1U – L4U
MU8-L1I – L4I
MU8-L1U – L4U
MU9-L1I – L4I
MU9-L1U – L4U
MU10-L1I – L4I
MU10-L1U – L4U
MU11-L1I – L4I
MU11-L1U – L4U
MU12-L1I – L4I
MU12-L1U – L4U
TRM40-Ch1 Reference channel for phase angle presentation

TRM_12I Non group settings (basic)

TRM_12I Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec7 1 – 10 A 1 1 Rated CT secondary current
CTprim7 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec8 1 – 10 A 1 1 Rated CT secondary current
CTprim8 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec9 1 – 10 A 1 1 Rated CT secondary current
CTprim9 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec10 1 – 10 A 1 1 Rated CT secondary current
CTprim10 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint11 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec11 1 – 10 A 1 1 Rated CT secondary current
CTprim11 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint12 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec12 1 – 10 A 1 1 Rated CT secondary current
CTprim12 1 – 99999 A 1 3000 Rated CT primary current

TRM_6I_6U Non group settings (basic)

TRM_6I_6U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current
VTsec7 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim7 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec8 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage

TRM_6I Non group settings (basic)

TRM_6I Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current

TRM_7I_5U Non group settings (basic)

TRM_7I_5U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec7 1 – 10 A 1 1 Rated CT secondary current
CTprim7 1 – 99999 A 1 3000 Rated CT primary current
VTsec8 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage

TRM_9I_3U Non group settings (basic)

TRM_9I_3U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec7 1 – 10 A 1 1 Rated CT secondary current
CTprim7 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec8 1 – 10 A 1 1 Rated CT secondary current
CTprim8 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec9 1 – 10 A 1 1 Rated CT secondary current
CTprim9 1 – 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage

TRM_10I_2U Non group settings (basic)

TRM_10I_2U Non group settings (basic)
Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec1 1 – 10 A 1 1 Rated CT secondary current
CTprim1 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec2 1 – 10 A 1 1 Rated CT secondary current
CTprim2 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec3 1 – 10 A 1 1 Rated CT secondary current
CTprim3 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec4 1 – 10 A 1 1 Rated CT secondary current
CTprim4 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec5 1 – 10 A 1 1 Rated CT secondary current
CTprim5 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec6 1 – 10 A 1 1 Rated CT secondary current
CTprim6 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec7 1 – 10 A 1 1 Rated CT secondary current
CTprim7 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec8 1 – 10 A 1 1 Rated CT secondary current
CTprim8 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec9 1 – 10 A 1 1 Rated CT secondary current
CTprim9 1 – 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject
ToObject
ToObject ToObject= towards protected object, FromObject= the opposite
CTsec10 1 – 10 A 1 1 Rated CT secondary current
CTprim10 1 – 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 – 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 – 2000.00 kV 0.05 400.00 Rated VT primary voltage

AISVBAS Monitored data

AISVBAS Monitored data
Name Type Values (Range) Unit Description
Status INTEGER 0=Ok
1=Error
2=AngRefLow
3=Uncorrelated
Service value status

TRM_12I Monitored data

TRM_12I Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

TRM_6I_6U Monitored data

TRM_6I_6U Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

TRM_6I Monitored data

TRM_6I Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

TRM_7I_5U Monitored data

TRM_7I_5U Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

TRM_9I_3U Monitored data

TRM_9I_3U Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

TRM_10I_2U Monitored data

TRM_10I_2U Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
Analogue input module status

highlights


Current channels


Internal convention of the directionality in the IED

Internal convention of the directionality in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Example how to set CTStarPoint parameters in the IED

Commonly used markings of CT terminals

Commonly used markings of CT terminals

Star connected three-phase CT set with star point towards the protected object

Star connected three-phase CT set with star point towards the protected object

Star connected three-phase CT set with its star point away from the protected object

Star connected three-phase CT set with its star point away from the protected object

Star connected three-phase CT set with its star point away from the protected object and the residual/neutral current connected to the IED

Star connected three-phase CT set with its star point away from the protected object and the residual/neutral current connected to the IED

Delta DAB connected three-phase CT set

Delta DAB connected three-phase CT set

Delta DAC connected three-phase CT set

Delta DAC connected three-phase CT set

Connections for single-phase CT input

Connections for single-phase CT input

Voltage channels


Commonly used markings of VT terminals

Commonly used markings of VT terminals

A Three phase-to-earth connected VT

A Three phase-to-earth connected VT

A two phase-to-earth connected VT

A two phase-to-earth connected VT

A Two phase-to-phase connected VT

A Two phase-to-phase connected VT

Open delta connected VT in high impedance earthed power system

Open delta connected VT in high impedance earthed power system

Open delta connected VT in low impedance or solidly earthed power system

Open delta connected VT in low impedance or solidly earthed power system

Neutral point connected VT

Neutral point connected VT

Technical Data


TRM – Energizing quantities, rated values and limits for protection transformer

TRM - Energizing quantities, rated values and limits for protection transformer

TRM – Energizing quantities, rated values and limits for measuring transformer

TRM - Energizing quantities, rated values and limits for measuring transformer

CT and VT circuit connectors

CT and VT circuit connectors