The “Aging factor” element detects transformer aging in per-unit normal insulation aging. The element can be set to alarm or trip whenever the computed aging factor is greater than the user-defined pickup setting for the specified time delay.

For more detailed information on “Aging factor” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, T35, T60 3E45 Transformer Aging Factor Function 0 to 1 1 F102 0 (Disabled)
" 3E46 Transformer Aging Factor Pickup 1 to 10 PU 0.1 F001 20
" 3E47 Transformer Aging Factor Delay 0 to 30000 min 1 F001 10
" 3E48 Transformer Aging Factor Block 0 to 4294967295 1 F300 0
" 3E4A Transformer Aging Factor Target 0 to 2 1 F109 0 (Self-reset)
" 3E4B Transformer Aging Factor Events 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Transformer aging factor logic

Transformer aging factor logic