ABB / Accidental energizing protection for synchronous generator (AEGPVOC) _ Setting & highlights _ AB2131

Table of Contents

Overview

Inadvertent or accidental energizing of off-line generators has occurred often enough due to operating errors, breaker head flashovers, control circuit malfunctions, or a combination of these causes. Inadvertently energized generator operates as induction motor drawing a large current from the system. The voltage supervised overcurrent protection is used to detect the inadvertently energized generator. “Accidental energizing protection for synchronous generator” takes the maximum phase current input and maximum phase to phase voltage inputs from the terminal side.

For more detailed information on “Accidental energizing protection for synchronous generator” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Accidental energizing protection for synchronous generator AEGPVOC U < I > 50AE

Signals & Setting Parameters


AEGPVOC Function block

AEGPVOC Function block

AEGPVOC Input signals

AEGPVOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three Phase Current input
U3P GROUP SIGNAL Three Phase Voltage input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

AEGPVOC Output signals

AEGPVOC Output signals
Name Type Description
TRIP BOOLEAN Trip signal from accidental energizing of generator protection
START BOOLEAN Start signal from accidental energizing of generator protection
ARMED BOOLEAN True when accidental energizing of generator protection is armed

AEGPVOC Group settings (basic)

AEGPVOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
I> 5 – 900 %IB 1 120 Operate phase current level in % of IBase
tOC 0.000 – 60.000 s 0.001 0.030 Trip time delay for over current level
ArmU< 2 – 150 %UB 1 50 Under-voltage level to arm protection in % of UBase
tArm 0.000 – 60.000 s 0.001 5.000 Time delay to arm protection with U< level
DisarmU> 2 – 200 %UB 1 80 Over-voltage level to disarm protection in % of UBase
tDisarm 0.000 – 60.000 s 0.001 0.500 Time delay to disarm protection with U> level

AEGPVOC Non group settings (basic)

AEGPVOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

AEGPVOC Monitored data

AEGPVOC Monitored data
Name Type Values (Range) Unit Description
IMAX REAL A Maximum value of current
UMAX REAL kV Maximum value of phase to phase voltage

Logics & highlights


AEGPVOC logic diagram

AEGPVOC logic diagram