Overview
The “Abnormal frequency protection” function monitors the frequency of the generator. It supervises the duration of the generator in the set frequency band, and generates an alarm or a trip of the generator. The function only protects the turbines. If the turbines operate too long in the set frequency band, the function leads to a trip.
For more detailed information on “Abnormal frequency protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
General setting parameters
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:100 | General:Dropout differ- ential | 20 mHz to 2000 mHz | 20 mHz | |
Setting parameters for Stage with Accumulative-Time Supervision
Addr. | Parameter | C | Setting Options | Default Setting |
Accum. stage # | ||||
_:1 | Accum. stage #:Mode | off on test |
off | |
_:2 | Accum. stage #:Operate & flt.rec. blocked | no yes |
no | |
_:100 | Accum. stage #:Frequency higher limit |
20.00 Hz to 80.00 Hz | 1.00 Hz | |
_:101 | Accum. stage #:Frequency lower limit |
20.00 Hz to 80.00 Hz | 1.00 Hz | |
_:102 | Accum. stage #:Dead time | 0.00 s to 200.00 s | 0.20 s | |
_:103 | Accum. stage #:Max. Accumulative time | 0.00 min to 60000.00 min | 180.00 min | |
Setting parameters for Stage with Duration-Time Supervision
Addr. | Parameter | C | Setting Options | Default Setting |
Dur. stage # | ||||
_:1 | Dur. stage #:Mode | off on test |
off | |
_:2 | Dur. stage #:Operate & flt.rec. blocked | no yes |
no | |
_:100 | Dur. stage #:Frequency higher limit | 20.00 Hz to 80.00 Hz | 1.00 Hz | |
_:101 | Dur. stage #:Frequency lower limit | 20.00 Hz to 80.00 Hz | 1.00 Hz | |
_:102 | Dur. stage #:Duration time | 0.00 s to 1000.00 s | 180.00 s | |