Siemens / Abnormal frequency protection (ANSI 81AF) _ Setting & highlights _ SI5091

Table of Contents

Overview

The “Abnormal frequency protection” function monitors the frequency of the generator. It supervises the duration of the generator in the set frequency band, and generates an alarm or a trip of the generator. The function only protects the turbines. If the turbines operate too long in the set frequency band, the function leads to a trip.

For more detailed information on “Abnormal frequency protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Logic Diagram of the Overcurrent Protection Group Indications

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:100 General:Dropout differ- ential   20 mHz to 2000 mHz 20 mHz

Setting parameters for Stage with Accumulative-Time Supervision

Addr. Parameter C Setting Options Default Setting
Accum. stage #
_:1 Accum. stage #:Mode   off
on
test
off
_:2 Accum. stage #:Operate & flt.rec. blocked   no
yes
no
_:100 Accum. stage
#:Frequency higher limit
  20.00 Hz to 80.00 Hz 1.00 Hz
_:101 Accum. stage
#:Frequency lower limit
  20.00 Hz to 80.00 Hz 1.00 Hz
_:102 Accum. stage #:Dead time   0.00 s to 200.00 s 0.20 s
_:103 Accum. stage #:Max. Accumulative time   0.00 min to 60000.00 min 180.00 min

Setting parameters for Stage with Duration-Time Supervision

Addr. Parameter C Setting Options Default Setting
Dur. stage #
_:1 Dur. stage #:Mode   off
on
test
off
_:2 Dur. stage #:Operate & flt.rec. blocked   no
yes
no
_:100 Dur. stage #:Frequency higher limit   20.00 Hz to 80.00 Hz 1.00 Hz
_:101 Dur. stage #:Frequency lower limit   20.00 Hz to 80.00 Hz 1.00 Hz
_:102 Dur. stage #:Duration time   0.00 s to 1000.00 s 180.00 s

Logic Diagrams & highlights


Suggested Setting Values of Abnormal Frequency Protection

Suggested Setting Values of Abnormal Frequency Protection

Logic Diagram of the Accumulative-Time Supervision Stage

Logic Diagram of the Accumulative-Time Supervision Stage

Logic Diagram of the Duration-Time Supervision Stage

Logic Diagram of the Duration-Time Supervision Stage