Overview
The “Interlocking for line bay (ABC_LINE)” function is used for a line connected to a double busbar arrangement with a transfer busbar according to the below Switchyard layout. The function can also be used for a double busbar arrangement without transfer busbar or a single busbar arrangement with/without transfer busbar.
For more detailed information on “Interlocking for line bay (ABC_LINE)” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Interlocking for line bay | ABC_LINE | – | 3 |
Signals
ABC_LINE function block
ABC_LINE Input signals
ABC_LINE Input signals | |||
Name | Type | Default | Description |
QA1_OP | BOOLEAN | 0 | QA1 is in open position |
QA1_CL | BOOLEAN | 0 | QA1 is in closed position |
QB9_OP | BOOLEAN | 0 | QB9 is in open position |
QB9_CL | BOOLEAN | 0 | QB9 is in closed position |
QB1_OP | BOOLEAN | 0 | QB1 is in open position |
QB1_CL | BOOLEAN | 0 | QB1 is in closed position |
QB2_OP | BOOLEAN | 0 | QB2 is in open position |
QB2_CL | BOOLEAN | 0 | QB2 is in closed position |
QB7_OP | BOOLEAN | 0 | QB7 is in open position |
QB7_CL | BOOLEAN | 0 | QB7 is in closed position |
QC1_OP | BOOLEAN | 0 | QC1 is in open position |
QC1_CL | BOOLEAN | 0 | QC1 is in closed position |
QC2_OP | BOOLEAN | 0 | QC2 is in open position |
QC2_CL | BOOLEAN | 0 | QC2 is in closed position |
QC9_OP | BOOLEAN | 0 | QC9 is in open position |
QC9_CL | BOOLEAN | 0 | QC9 is in closed position |
QC11_OP | BOOLEAN | 0 | Earthing switch QC11 on busbar WA1 is in open position |
QC11_CL | BOOLEAN | 0 | Earthing switch QC11 on busbar WA1 is in closed position |
QC21_OP | BOOLEAN | 0 | Earthing switch QC21 on busbar WA2 is in open position |
QC21_CL | BOOLEAN | 0 | Earthing switch QC21 on busbar WA2 is in closed position |
QC71_OP | BOOLEAN | 0 | Earthing switch QC71 on busbar WA7 is in open position |
QC71_CL | BOOLEAN | 0 | Earthing switch QC71 on busbar WA7 is in closed position |
BB7_D_OP | BOOLEAN | 0 | Disconnectors on busbar WA7 except in the own bay are open |
BC_12_CL | BOOLEAN | 0 | A bus coupler connection exists between busbar WA1 and WA2 |
BC_17_OP | BOOLEAN | 0 | No bus coupler connection exists between busbar WA1 and WA7 |
BC_17_CL | BOOLEAN | 0 | A bus coupler connection exists between busbar WA1 and WA7 |
BC_27_OP | BOOLEAN | 0 | No bus coupler connection exists between busbar WA2 and WA7 |
BC_27_CL | BOOLEAN | 0 | A bus coupler connection exists between busbar WA2 and WA7 |
VOLT_OFF | BOOLEAN | 0 | There is no voltage on the line and not VT (fuse) failure |
VOLT_ON | BOOLEAN | 0 | There is voltage on the line or there is a VT (fuse) failure |
VP_BB7_D | BOOLEAN | 0 | Switch status of the disconnectors on busbar WA7 are valid |
VP_BC_12 | BOOLEAN | 0 | Status of the bus coupler app. between WA1 and WA2 are valid |
VP_BC_17 | BOOLEAN | 0 | Status of the bus coupler app. between WA1 and WA7 are valid |
VP_BC_27 | BOOLEAN | 0 | Status of the bus coupler app. between WA2 and WA7 are valid |
EXDU_ES | BOOLEAN | 0 | No transm error from any bay containing earthing switches |
EXDU_BPB | BOOLEAN | 0 | No transm error from any bay with disconnectors on WA7 |
EXDU_BC | BOOLEAN | 0 | No transmission error from any bus coupler bay |
QB9_EX1 | BOOLEAN | 0 | External condition for apparatus QB9 |
QB9_EX2 | BOOLEAN | 0 | External condition for apparatus QB9 |
QB1_EX1 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB1_EX2 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB1_EX3 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB2_EX1 | BOOLEAN | 0 | External condition for apparatus QB2 |
QB2_EX2 | BOOLEAN | 0 | External condition for apparatus QB2 |
QB2_EX3 | BOOLEAN | 0 | External condition for apparatus QB2 |
QB7_EX1 | BOOLEAN | 0 | External condition for apparatus QB7 |
QB7_EX2 | BOOLEAN | 0 | External condition for apparatus QB7 |
QB7_EX3 | BOOLEAN | 0 | External condition for apparatus QB7 |
QB7_EX4 | BOOLEAN | 0 | External condition for apparatus QB7 |
ABC_LINE Output signals
ABC_LINE Output signals | |||
Name | Type | Description | |
QA1CLREL | BOOLEAN | Closing of QA1 is allowed | |
QA1CLITL | BOOLEAN | Closing of QA1 is forbidden | |
QB9REL | BOOLEAN | Switching of QB9 is allowed | |
QB9ITL | BOOLEAN | Switching of QB9 is forbidden | |
QB1REL | BOOLEAN | Switching of QB1 is allowed | |
QB1ITL | BOOLEAN | Switching of QB1 is forbidden | |
QB2REL | BOOLEAN | Switching of QB2 is allowed | |
QB2ITL | BOOLEAN | Switching of QB2 is forbidden | |
QB7REL | BOOLEAN | Switching of QB7 is allowed | |
QB7ITL | BOOLEAN | Switching of QB7 is forbidden | |
QC1REL | BOOLEAN | Switching of QC1 is allowed | |
QC1ITL | BOOLEAN | Switching of QC1 is forbidden | |
QC2REL | BOOLEAN | Switching of QC2 is allowed | |
QC2ITL | BOOLEAN | Switching of QC2 is forbidden | |
QC9REL | BOOLEAN | Switching of QC9 is allowed | |
QC9ITL | BOOLEAN | Switching of QC9 is forbidden | |
QB1OPTR | BOOLEAN | QB1 is in open position | |
QB1CLTR | BOOLEAN | QB1 is in closed position | |
QB2OPTR | BOOLEAN | QB2 is in open position | |
QB2CLTR | BOOLEAN | QB2 is in closed position | |
QB7OPTR | BOOLEAN | QB7 is in open position | |
QB7CLTR | BOOLEAN | QB7 is in closed position | |
QB12OPTR | BOOLEAN | QB1 or QB2 or both are in open position | |
QB12CLTR | BOOLEAN | QB1 and QB2 are not in open position | |
VPQB1TR | BOOLEAN | Switch status of QB1 is valid (open or closed) | |
VPQB2TR | BOOLEAN | Switch status of QB2 is valid (open or closed) | |
VPQB7TR | BOOLEAN | Switch status of QB7 is valid (open or closed) | |
VPQB12TR | BOOLEAN | Switch status of QB1 and QB2 are valid (open or closed) | |