Overview

The “Interlocking for line bay (ABC_LINE)” function is used for a line connected to a double busbar arrangement with a transfer busbar according to the below Switchyard layout. The function can also be used for a double busbar arrangement without transfer busbar or a single busbar arrangement with/without transfer busbar.

Switchyard layout ABC_LINE

For more detailed information on “Interlocking for line bay (ABC_LINE)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for line bay ABC_LINE 3

Signals


ABC_LINE function block

ABC_LINE function block

ABC_LINE Input signals

ABC_LINE Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB9_OP BOOLEAN 0 QB9 is in open position
QB9_CL BOOLEAN 0 QB9 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC9_OP BOOLEAN 0 QC9 is in open position
QC9_CL BOOLEAN 0 QC9 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed position
BB7_D_OP BOOLEAN 0 Disconnectors on busbar WA7 except in the own bay are open
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA2
BC_17_OP BOOLEAN 0 No bus coupler connection exists between busbar WA1 and WA7
BC_17_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA7
BC_27_OP BOOLEAN 0 No bus coupler connection exists between busbar WA2 and WA7
BC_27_CL BOOLEAN 0 A bus coupler connection exists between busbar WA2 and WA7
VOLT_OFF BOOLEAN 0 There is no voltage on the line and not VT (fuse) failure
VOLT_ON BOOLEAN 0 There is voltage on the line or there is a VT (fuse) failure
VP_BB7_D BOOLEAN 0 Switch status of the disconnectors on busbar WA7 are valid
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are valid
VP_BC_17 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA7 are valid
VP_BC_27 BOOLEAN 0 Status of the bus coupler app. between WA2 and WA7 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_BPB BOOLEAN 0 No transm error from any bay with disconnectors on WA7
EXDU_BC BOOLEAN 0 No transmission error from any bus coupler bay
QB9_EX1 BOOLEAN 0 External condition for apparatus QB9
QB9_EX2 BOOLEAN 0 External condition for apparatus QB9
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7
QB7_EX3 BOOLEAN 0 External condition for apparatus QB7
QB7_EX4 BOOLEAN 0 External condition for apparatus QB7

ABC_LINE Output signals

ABC_LINE Output signals
Name Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB9REL BOOLEAN Switching of QB9 is allowed
QB9ITL BOOLEAN Switching of QB9 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QC9REL BOOLEAN Switching of QC9 is allowed
QC9ITL BOOLEAN Switching of QC9 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB2OPTR BOOLEAN QB2 is in open position
QB2CLTR BOOLEAN QB2 is in closed position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VPQB2TR BOOLEAN Switch status of QB2 is valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)

Logics & highlights


Logic diagram

Logic diagram - 3
Logic diagram - 4
Logic diagram - 5
Logic diagram - 6
Logic diagram - 7
Logic diagram - 8