Overview

The “Current reversal and weak-end infeed logic for residual overcurrent protection (ECRWPSCH)” is a supplement to Scheme communication logic for residual overcurrent protection ECPSCH. To achieve fast fault clearing for all earth faults on the line, the directional earth fault protection function can be supported with logic that uses tele-protection channels.

For more detailed information on “Current reversal and weak-end infeed logic for residual overcurrent protection (ECRWPSCH)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH 85

Signals & Setting Parameters


ECRWPSCH function block

ECRWPSCH function block

ECRWPSCH Input signals

ECRWPSCH Input signals
Name Type Default Description
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI Logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

ECRWPSCH Output signals

ECRWPSCH Output signals
Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip signal from weak end infeed logic
ECHO BOOLEAN Permissive signal transmitted as echo signal or in case of weak end infeed

ECRWPSCH Group settings (basic)

ECRWPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
CurrRev Off
On
Off Operating mode of Current Reversal Logic
tPickUpRev 0.000 – 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 – 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and local trip
WEI Off
Echo
Echo & Trip
Off Operating mode of WEI logic
tPickUpWEI 0.000 – 60.000 s 0.001 0.000 Coordination time for the WEI logic
3U0> 5 – 70 %UB 1 25 Neutral voltage setting for fault conditions measurement

ECRWPSCH Non group settings (basic)

ECRWPSCH Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Simplified logic diagram for current reversal

Simplified logic diagram for current reversal

Simplified logic diagram for weak-end infeed logic – Echo

Simplified logic diagram for weak-end infeed logic - Echo

Simplified logic diagram for weak-end infeed logic – Echo & Trip

Simplified logic diagram for weak-end infeed logic - Echo & Trip