Overview

To achieve fast clearing of faults on the whole line, when no communication channel is available, the “Local acceleration logic (ZCLCPSCH)” can be used. This logic enables fast fault clearing and reclosing during certain conditions, but naturally, it can not fully replace a communication channel.

For more detailed information on “Local acceleration logic (ZCLCPSCH)”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local acceleration logic ZCLCPSCH

Signals & Setting Parameters


ZCLCPSCH function block

ZCLCPSCH function block

ZCLCPSCH Input signals

ZCLCPSCH Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
BLOCK BOOLEAN 0 Block of function
ARREADY BOOLEAN 0 Autoreclosure ready, releases function used for fast trip
NDST BOOLEAN 0 Non directional criteria used to prevent instantaneous trip
EXACC BOOLEAN 0 Connected to function used for tripping at zone extension
BC BOOLEAN 0 Breaker Close
LLACC BOOLEAN 0 Connected to function used for tripping at loss of load

ZCLCPSCH Output signals

ZCLCPSCH Output signals
Name Type Description
TRZE BOOLEAN Trip by zone extension
TRLL BOOLEAN Trip by loss of load

ZCLCPSCH Group settings (basic)

ZCLCPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
LoadCurr 1 – 100 %IB 1 10 Load current before disturbance in % of IBase
LossOfLoad Off
On
Off Enable/Disable operation of Loss of load.
ZoneExtension Off
On
Off Enable/Disable operation of Zone extension
MinCurr 1 – 100 %IB 1 5 Lev taken as curr loss due to remote CB trip in % of IBase
tLowCurr 0.000 – 60.000 s 0.001 0.200 Time delay on pick-up for MINCURR value
tLoadOn 0.000 – 60.000 s 0.001 0.000 Time delay on pick-up for load current release
tLoadOff 0.000 – 60.000 s 0.001 0.300 Time delay on drop off for load current release

ZCLCPSCH Non group settings (basic)

ZCLCPSCH Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Simplified logic diagram for local acceleration logic

Simplified logic diagram for local acceleration logic

Loss-of-load acceleration – simplified logic diagram

Loss-of-load acceleration - simplified logic diagram