Overview

The ZCRWPSCH function provides the “Current reversal and weak end infeed logic” functions that supplement the standard scheme communication logic. It is not suitable for standalone use as it requires inputs from the distance protection functions and the scheme communications function included within the terminal.

For more detailed information on “Current reversal and weak end infeed logic” functions, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed logic for distance protection 3-phase ZCRWPSCH 85

Signals & Setting Parameters


ZCRWPSCH function block

ZCRWPSCH function block

ZCRWPSCH Input signals

ZCRWPSCH Input signals
Name Type Default Description
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
IRVBLK BOOLEAN 0 Block of current reversal function
IRV BOOLEAN 0 Activation of current reversal logic
WEIBLK1 BOOLEAN 0 Block of WEI logic
WEIBLK2 BOOLEAN 0 Block of WEI logic due to operation of other protections
VTSZ BOOLEAN 0 Block of trip from WEI logic through fuse-failure function
CBOPEN BOOLEAN 0 Block of trip from WEI logic by an open breaker
CRL BOOLEAN 0 POR Carrier receive for WEI logic

ZCRWPSCH Output signals

ZCRWPSCH Output signals
Name Type Description
IRVL BOOLEAN Operation of current reversal logic
TRWEI BOOLEAN Trip signal from weak end infeed logic
TRWEIL1 BOOLEAN Trip signal from weak end infeed logic in phase L1
TRWEIL2 BOOLEAN Trip signal from weak end infeed logic in phase L2
TRWEIL3 BOOLEAN Trip signal from weak end infeed logic in phase L3
ECHO BOOLEAN Carrier send by WEI logic

ZCRWPSCH Group settings (basic)

ZCRWPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
CurrRev Off
On
Off Operating mode of Current Reversal Logic
tPickUpRev 0.000 – 60.000 s 0.001 0.020 Pickup time for current reversal logic
tDelayRev 0.000 – 60.000 s 0.001 0.060 Time Delay to prevent Carrier send and local trip
WEI Off
Echo
Echo & Trip
Off Operating mode of WEI logic
tPickUpWEI 0.000 – 60.000 s 0.001 0.010 Coordination time for the WEI logic
UPP< 10 – 90 %UB 1 70 Phase to Phase voltage for detection of fault condition
UPN< 10 – 90 %UB 1 70 Phase to Neutral voltage for detection of fault condition

ZCRWPSCH Non group settings (basic)

ZCRWPSCH Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Simplified logic diagram for current reversal

Simplified logic diagram for current reversal

Simplified logic diagram for weak-end infeed logic — Echo

Simplified logic diagram for weak-end infeed logic — Echo

Simplified logic diagram for weak-end infeed logic — Echo&Trip

Simplified logic diagram for weak-end infeed logic — Echo&Trip