ABB / Phase segregated scheme communication logic for distance protection (ZC1PPSCH) _ Setting & highlights _ AB2102

Table of Contents

Overview

The main purpose of the “Phase segregated scheme communication logic for distance protection (ZC1PPSCH)” function is to supplement the distance protection function such that fast clearance of faults is also achieved at the line end for which the faults are on the part of the line not covered by its underreaching zone, and correct phase selection can be maintained to support single-pole tripping for faults occurring anywhere on the entire length of a double circuit line.

For more detailed information on “Phase segregated scheme communication logic for distance protection (ZC1PPSCH)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase segregated Scheme communication logic for distance protection ZC1PPSCH 85

Signals & Setting Parameters


ZC1PPSCH function block

ZC1PPSCH function block

ZC1PPSCH Input signals

ZC1PPSCH Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Common signal for block of trip output from communication logic in all phases
BLKTRL1 BOOLEAN 0 Signal for block of trip output from communication logic in Phase L1
BLKTRL2 BOOLEAN 0 Signal for block of trip output from communication logic in Phase L2
BLKTRL3 BOOLEAN 0 Signal for block of trip output from communication logic in Phase L3
CACCL1 BOOLEAN 0 Accelerated Distance protection zone start in Phase L1
CACCL2 BOOLEAN 0 Accelerated Distance protection zone signal in Phase L2
CACCL3 BOOLEAN 0 Accelerated Distance protection zone signal in Phase L3
CSURL1 BOOLEAN 0 Underreaching distance protection zone signal in Phase L1
CSURL2 BOOLEAN 0 Underreaching distance protection zone signal in Phase L2
CSURL3 BOOLEAN 0 Underreaching distance protection zone signal in Phase L3
CSORL1 BOOLEAN 0 Overreaching distance protection zone signal in Phase L1
CSORL2 BOOLEAN 0 Overreaching distance protection zone signal in Phase L2
CSORL3 BOOLEAN 0 Overreaching distance protection zone signal in Phase L3
CSBLKL1 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L1
CSBLKL2 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L2
CSBLKL3 BOOLEAN 0 Reverse directed distance protection zone signal in Phase L3
BLKCSL1 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase L1
BLKCSL2 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase L2
BLKCSL3 BOOLEAN 0 Block of carrier send in POR and Blocking schemes in Phase L3
CRL1 BOOLEAN 0 Carrier signal received in Phase L1
CRL2 BOOLEAN 0 Carrier signal received in Phase L2
CRL3 BOOLEAN 0 Carrier signal received in Phase L3
CRMPH BOOLEAN 0 Carrier Signal received for multiphase fault

ZC1PPSCH Output signals

ZC1PPSCH Output signals
Name Type Description
TRIP BOOLEAN Common trip output in any of the phase
TRL1 BOOLEAN Trip output in Phase L1
TRL2 BOOLEAN Trip output in Phase L2
TRL3 BOOLEAN Trip output in Phase L3
CSL1 BOOLEAN Carrier Send in phase L1
CSL2 BOOLEAN Carrier Send in phase L2
CSL3 BOOLEAN Carrier Send in phase L3
CSMPH BOOLEAN carrier Send for multi phase fault
CRLL1 BOOLEAN Carrier signal received in Phase L1
CRLL2 BOOLEAN Carrier signal received in Phase L2
CRLL3 BOOLEAN Carrier signal received in Phase L3

ZC1PPSCH Group settings (basic)

ZC1PPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation On / Off
Scheme Type Off
Intertrip
Permissive UR
Permissive OR
Blocking
Permissive UR Scheme type
tCoord 0.000 – 60.000 s 0.001 0.000 Trip coordinate time
tSendMin 0.000 – 60.000 s 0.001 0.100 Minimum duration of Carrier Send signal

Logics & highlights


Basic logic for trip carrier in one phase of a blocking scheme

Basic logic for trip carrier in one phase of a blocking scheme

Basic logic for trip carrier in one phase of a permissive underreach scheme

Basic logic for trip carrier in one phase of a permissive underreach scheme

Simplified logic diagram for one phase

Simplified logic diagram for one phase