Overview

To achieve instantaneous fault clearance for all line faults, the “Scheme communication logic for distance or overcurrent protection” is provided. All types of communication schemes for permissive underreaching, permissive overreaching, blocking, delta based blocking, unblocking and intertrip are available. The built-in communication module (LDCM) can be used for scheme communication signaling when included.

For more detailed information on “Scheme communication logic for distance or overcurrent protection” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Scheme communication logic for distance or overcurrent protection ZCPSCH 85

Signals & Setting Parameters


ZCPSCH function block

ZCPSCH function block

ZCPSCH Input signals

ZCPSCH Input signals
Name Type Default Description
I3P GROUP SIGNAL Current group connection
U3P GROUP SIGNAL Voltage group connection
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Signal for block of trip output from communication logic
BLKCS BOOLEAN 0 Block of carrier send in permissive OR and blocking schemes
CSBLK BOOLEAN 0 Reverse directed distance protection zone signal
CACC BOOLEAN 0 Permissive distance protection zone signal
CSOR BOOLEAN 0 Overreaching distance protection zone signal
CSUR BOOLEAN 0 Underreaching distance protection zone signal
CR BOOLEAN 0 Carrier Signal Received
CRG BOOLEAN 0 Carrier guard signal received
CBOPEN BOOLEAN 0 Indicates that the breaker is open

ZCPSCH Output signals

ZCPSCH Output signals
Name Type Description
TRIP BOOLEAN Trip output
CS BOOLEAN Carrier Send signal
CHSTOP BOOLEAN Stops the blocking signal to remote end
CRL BOOLEAN Carrier signal received or missing carrier guard signal
LCG BOOLEAN Loss of carrier guard signal

ZCPSCH Group settings (basic)

ZCPSCH Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
SchemeType Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
Permissive UR Scheme type
tCoord 0.000 – 60.000 s 0.001 0.035 Co-ordination time for blocking communication scheme
tSendMin 0.000 – 60.000 s 0.001 0.100 Minimum duration of a carrier send signal

ZCPSCH Group settings (advanced)

ZCPSCH Group settings (advanced)
Name Values (Range) Unit Step Default Description
Unblock Off
NoRestart
Restart
Off Operation mode of unblocking logic
DeltaI 0 – 200 %IB 1 10 Current change level in % of IBase for fault inception detection
DeltaU 0 – 100 %UB 1 5 Voltage change level in % of UB for fault inception detection
Delta3I0 0 – 200 %IB 1 10 Zero seq current change level in % of IBase
Delta3U0 0 – 100 %UB 1 5 Zero seq voltage change level in % of UBase
tSecurity 0.000 – 60.000 s 0.001 0.035 Security timer for loss of carrier guard detection

ZCPSCH Non group settings (advanced)

ZCPSCH Non group settings (advanced)
Name Values (Range) Unit Step Default Description
GlobalBaseSelector 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Basic logic for trip signal in blocking scheme

2-Basic logic for trip signal in blocking scheme

Basic logic for trip signal in delta blocking scheme

3-Basic logic for trip signal in delta blocking scheme

Logic for trip signal in permissive scheme

4-Logic for trip signal in permissive scheme

Logic for trip signal in permissive scheme

5-Logic for trip signal in permissive scheme

Guard signal logic with unblocking scheme and with setting Unblock = Restart

6-Guard signal logic with unblocking scheme and with setting Unblock = Restart

Guard signal logic with unblocking scheme and with setting Unblock = NoRestart

7-Guard signal logic with unblocking scheme and with setting Unblock = NoRestart