Overview
The “Interlocking for transformer bay (AB_TRAFO)” function is used for a transformer bay connected to a double busbar arrangement according to the below Switchyard layout. The function is used when there is no disconnector between circuit breaker and transformer. Otherwise, the interlocking for line bay (ABC_LINE) function can be used. This function can also be used in single busbar arrangements.
For more detailed information on “Interlocking for transformer bay (AB_TRAFO)” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Interlocking for transformer bay | AB_TRAFO | – | 3 |
Signals
AB_TRAFO function block
AB_TRAFO Input signals
AB_TRAFO Input signals | |||
Name | Type | Default | Description |
QA1_OP | BOOLEAN | 0 | QA1 is in open position |
QA1_CL | BOOLEAN | 0 | QA1 is in closed position |
QB1_OP | BOOLEAN | 0 | QB1 is in open position |
QB1_CL | BOOLEAN | 0 | QB1 is in closed position |
QB2_OP | BOOLEAN | 0 | QB2 is in open position |
QB2_CL | BOOLEAN | 0 | QB2 is in closed position |
QC1_OP | BOOLEAN | 0 | QC1 is in open position |
QC1_CL | BOOLEAN | 0 | QC1 is in closed position |
QC2_OP | BOOLEAN | 0 | QC2 is in open position |
QC2_CL | BOOLEAN | 0 | QC2 is in closed position |
QB3_OP | BOOLEAN | 0 | QB3 is in open position |
QB3_CL | BOOLEAN | 0 | QB3 is in closed position |
QB4_OP | BOOLEAN | 0 | QB4 is in open position |
QB4_CL | BOOLEAN | 0 | QB4 is in closed position |
QC3_OP | BOOLEAN | 0 | QC3 is in open position |
QC3_CL | BOOLEAN | 0 | QC3 is in closed position |
QC11_OP | BOOLEAN | 0 | QC11 on busbar WA1 is in open position |
QC11_CL | BOOLEAN | 0 | QC11 on busbar WA1 is in closed position |
QC21_OP | BOOLEAN | 0 | QC21 on busbar WA2 is in open position |
QC21_CL | BOOLEAN | 0 | QC21 on busbar WA2 is in closed position |
BC_12_CL | BOOLEAN | 0 | A bus coupler connection exists between busbar WA1 and WA2 |
VP_BC_12 | BOOLEAN | 0 | Status of the bus coupler app. between WA1 and WA2 are valid |
EXDU_ES | BOOLEAN | 0 | No transm error from any bay containing earthing switches |
EXDU_BC | BOOLEAN | 0 | No transmission error from any bus coupler bay |
QA1_EX1 | BOOLEAN | 0 | External condition for apparatus QA1 |
QA1_EX2 | BOOLEAN | 0 | External condition for apparatus QA1 |
QA1_EX3 | BOOLEAN | 0 | External condition for apparatus QA1 |
QB1_EX1 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB1_EX2 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB1_EX3 | BOOLEAN | 0 | External condition for apparatus QB1 |
QB2_EX1 | BOOLEAN | 0 | External condition for apparatus QB2 |
QB2_EX2 | BOOLEAN | 0 | External condition for apparatus QB2 |
QB2_EX3 | BOOLEAN | 0 | External condition for apparatus QB2 |
AB_TRAFO Output signals
AB_TRAFO Output signals | |||
Name | Type | Description | |
QA1CLREL | BOOLEAN | Closing of QA1 is allowed | |
QA1CLITL | BOOLEAN | Closing of QA1 is forbidden | |
QB1REL | BOOLEAN | Switching of QB1 is allowed | |
QB1ITL | BOOLEAN | Switching of QB1 is forbidden | |
QB2REL | BOOLEAN | Switching of QB2 is allowed | |
QB2ITL | BOOLEAN | Switching of QB2 is forbidden | |
QC1REL | BOOLEAN | Switching of QC1 is allowed | |
QC1ITL | BOOLEAN | Switching of QC1 is forbidden | |
QC2REL | BOOLEAN | Switching of QC2 is allowed | |
QC2ITL | BOOLEAN | Switching of QC2 is forbidden | |
QB1OPTR | BOOLEAN | QB1 is in open position | |
QB1CLTR | BOOLEAN | QB1 is in closed position | |
QB2OPTR | BOOLEAN | QB2 is in open position | |
QB2CLTR | BOOLEAN | QB2 is in closed position | |
QB12OPTR | BOOLEAN | QB1 or QB2 or both are in open position | |
QB12CLTR | BOOLEAN | QB1 and QB2 are not in open position | |
VPQB1TR | BOOLEAN | Switch status of QB1 is valid (open or closed) | |
VPQB2TR | BOOLEAN | Switch status of QB2 is valid (open or closed) | |
VPQB12TR | BOOLEAN | Switch status of QB1 and QB2 are valid (open or closed) | |