ABB / Interlocking for bus-coupler bay (ABC_BC) _ Signals & highlights _ AB2079

Table of Contents

Overview

The “Interlocking for bus-coupler bay (ABC_BC)” function is used for a bus-coupler bay connected to a double busbar arrangement according to the below Switchyard layout. The function can also be used for a single busbar arrangement with transfer busbar or double busbar arrangement without transfer busbar.

Switchyard layout ABC_BC

For more detailed information on “Interlocking for bus-coupler bay (ABC_BC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-coupler bay ABC_BC 3

Signals


ABC_BC function block

Interlocking for bus-coupler bay ABC_BC function block

ABC_BC Input signals

ABC_BC Input signals
Name Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB2_OP BOOLEAN 0 QB2 is in open position
QB2_CL BOOLEAN 0 QB2 is in closed position
QB7_OP BOOLEAN 0 QB7 is in open position
QB7_CL BOOLEAN 0 QB7 is in closed position
QB20_OP BOOLEAN 0 QB20 is in open position
QB20_CL BOOLEAN 0 QB20 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed position
QC21_OP BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in open position
QC21_CL BOOLEAN 0 Earthing switch QC21 on busbar WA2 is in closed position
QC71_OP BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in open position
QC71_CL BOOLEAN 0 Earthing switch QC71 on busbar WA7 is in closed position
BBTR_OP BOOLEAN 0 No busbar transfer is in progress
BC_12_CL BOOLEAN 0 A bus coupler connection exists between busbar WA1 and WA2
VP_BBTR BOOLEAN 0 Status are valid for app. involved in the busbar transfer
VP_BC_12 BOOLEAN 0 Status of the bus coupler app. between WA1 and WA2 are valid
EXDU_ES BOOLEAN 0 No transm error from any bay containing earthing switches
EXDU_12 BOOLEAN 0 No transm error from any bay connected to WA1/WA2 busbars
EXDU_BC BOOLEAN 0 No transmission error from any other bus coupler bay
QA1O_EX1 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX2 BOOLEAN 0 External open condition for apparatus QA1
QA1O_EX3 BOOLEAN 0 External open condition for apparatus QA1
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
QB1_EX3 BOOLEAN 0 External condition for apparatus QB1
QB2_EX1 BOOLEAN 0 External condition for apparatus QB2
QB2_EX2 BOOLEAN 0 External condition for apparatus QB2
QB2_EX3 BOOLEAN 0 External condition for apparatus QB2
QB20_EX1 BOOLEAN 0 External condition for apparatus QB20
QB20_EX2 BOOLEAN 0 External condition for apparatus QB20
QB7_EX1 BOOLEAN 0 External condition for apparatus QB7
QB7_EX2 BOOLEAN 0 External condition for apparatus QB7

ABC_BC Output signals

ABC_BC Output signals
Name Type Description
QA1OPREL BOOLEAN Opening of QA1 is allowed
QA1OPITL BOOLEAN Opening of QA1 is forbidden
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QB2REL BOOLEAN Switching of QB2 is allowed
QB2ITL BOOLEAN Switching of QB2 is forbidden
QB7REL BOOLEAN Switching of QB7 is allowed
QB7ITL BOOLEAN Switching of QB7 is forbidden
QB20REL BOOLEAN Switching of QB20 is allowed
QB20ITL BOOLEAN Switching of QB20 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
QB220OTR BOOLEAN QB2 and QB20 are in open position
QB220CTR BOOLEAN QB2 or QB20 or both are not in open position
QB7OPTR BOOLEAN QB7 is in open position
QB7CLTR BOOLEAN QB7 is in closed position
QB12OPTR BOOLEAN QB1 or QB2 or both are in open position
QB12CLTR BOOLEAN QB1 and QB2 are not in open position
BC12OPTR BOOLEAN No connection via the own bus coupler between WA1 and WA2
BC12CLTR BOOLEAN Conn. exists via the own bus coupler between WA1 and WA2
BC17OPTR BOOLEAN No connection via the own bus coupler between WA1 and WA7
BC17CLTR BOOLEAN Conn. exists via the own bus coupler between WA1 and WA7
BC27OPTR BOOLEAN No connection via the own bus coupler between WA2 and WA7
BC27CLTR BOOLEAN Conn. exists via the own bus coupler between WA2 and WA7
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)
VQB220TR BOOLEAN Switch status of QB2 and QB20 are valid (open or closed)
VPQB7TR BOOLEAN Switch status of QB7 is valid (open or closed)
VPQB12TR BOOLEAN Switch status of QB1 and QB2 are valid (open or closed)
VPBC12TR BOOLEAN Status of the bus coupler app. between WA1 and WA2 are valid
VPBC17TR BOOLEAN Status of the bus coupler app. between WA1 and WA7 are valid
VPBC27TR BOOLEAN Status of the bus coupler app. between WA2 and WA7 are valid

Logics & highlights


ABC_BC Logic diagram

ABC_BC Logic diagram - 1
ABC_BC Logic diagram - 2
ABC_BC Logic diagram - 3
ABC_BC Logic diagram - 4
ABC_BC Logic diagram - 5