ABB / Interlocking for bus-section disconnector (A1A2_DC) _ Signals & highlights _ AB2078

Table of Contents

Overview

The “Interlocking for bus-section disconnector (A1A2_DC)” function is used for one bus-section disconnector between section 1 and 2 according to below Switchyard layout. A1A2_DC function can be used for different busbars, which includes a bus-section disconnector.

Switchyard layout A1A2_DC

For more detailed information on “Interlocking for bus-section disconnector (A1A2_DC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-section disconnector A1A2_DC 3

Signals


A1A2_DC function block

Interlocking for bus-section disconnector A1A2_DC function block

A1A2_DC Input signals

A1A2_DC Input signals
Name Type Default Description
QB_OP BOOLEAN 0 QB is in open position
QB_CL BOOLEAN 0 QB is in closed position
S1QC1_OP BOOLEAN 0 QC1 on bus section 1 is in open position
S1QC1_CL BOOLEAN 0 QC1 on bus section 1 is in closed position
S2QC2_OP BOOLEAN 0 QC2 on bus section 2 is in open position
S2QC2_CL BOOLEAN 0 QC2 on bus section 2 is in closed position
S1DC_OP BOOLEAN 0 All disconnectors on bus section 1 are in open position
S2DC_OP BOOLEAN 0 All disconnectors on bus section 2 are in open position
VPS1_DC BOOLEAN 0 Switch status of disconnectors on bus section 1 are valid
VPS2_DC BOOLEAN 0 Switch status of disconnectors on bus section 2 are valid
EXDU_ES BOOLEAN 0 No transm error from bays containing earth. sw. QC1 or QC2
EXDU_BB BOOLEAN 0 No transm error from bays with disc conn to section 1 and 2
QBCL_EX1 BOOLEAN 0 External close condition for section disconnector QB
QBCL_EX2 BOOLEAN 0 External close condition for section disconnector QB
QBOP_EX1 BOOLEAN 0 External open condition for section disconnector QB
QBOP_EX2 BOOLEAN 0 External open condition for section disconnector QB
QBOP_EX3 BOOLEAN 0 External open condition for section disconnector QB

A1A2_DC Output signals

A1A2_DC Output signals
Name Type Description
QBOPREL BOOLEAN Opening of QB is allowed
QBOPITL BOOLEAN Opening of QB is forbidden
QBCLREL BOOLEAN Closing of QB is allowed
QBCLITL BOOLEAN Closing of QB is forbidden
DCOPTR BOOLEAN The bus section disconnector is in open position
DCCLTR BOOLEAN The bus section disconnector is in closed position
VPDCTR BOOLEAN Switch status of QB is valid (open or closed)

Logics & highlights


A1A2_DC Logic diagram

A1A2_DC Logic diagram - 1
A1A2_DC Logic diagram - 2