Table of Contents

ABB / Interlocking for busbar earthing switch (BB_ES) _ Signals & highlights _ AB2076

Table of Contents

Overview

The “Interlocking for busbar earthing switch (BB_ES)” function is used for one busbar earthing switch on any busbar parts according to this Switchyard layout:

Switchyard layout BB_ES

For more detailed information on “Interlocking for busbar earthing switch (BB_ES)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for busbar earthing switch BB_ES 3

Signals


BB_ES function block

Interlocking for busbar earthing switch BB_ES function block

BB_ES Input signals

BB_ES Input signals
Name Type Default Description
QC_OP BOOLEAN 0 Busbar earthing switch QC is in open position
QC_CL BOOLEAN 0 Busbar earthing switch QC is in closed position
BB_DC_OP BOOLEAN 0 All disconnectors on this busbar part are open
VP_BB_DC BOOLEAN 0 Status for all disconnectors on this busbar part are valid
EXDU_BB BOOLEAN 0 No transm error from bays with disc on this busbar part

BB_ES Output signals

BB_ES Output signals
Name Type Description
QCREL BOOLEAN Switching of QC is allowed
QCITL BOOLEAN Switching of QC is forbidden
BBESOPTR BOOLEAN QC on this busbar part is in open position
BBESCLTR BOOLEAN QC on this busbar part is in closed position

Logics & highlights


BB_ES Logic diagram

BB_ES Logic diagram

error: Content is protected !!