Table of Contents

Overview

The “Autorecloser (SMBRREC)” function provides: high-speed and/or delayed auto reclosing, single and/or three phase auto reclosing, support for single or multi-breaker applications.

For more detailed information on “Autorecloser (SMBRREC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autorecloser for 1 phase, 2 phase and/or 3 phase SMBRREC 5(0 -->1) 79

Signals & Setting Parameters


SMBRREC function block

SMBRREC function block

SMBRREC Input signals

SMBRREC Input signals
Name Type Default Description
ON BOOLEAN 0 Switch AR On (at ExternalCtrl = On)
OFF BOOLEAN 0 Switch AR Off (at ExternalCtrl = On)
BLKON BOOLEAN 0 Set AR in blocked state
BLKOFF BOOLEAN 0 Release AR from blocked state
RESET BOOLEAN 0 Reset AR to initial conditions
INHIBIT BOOLEAN 0 Interrupt and inhibit reclosing sequence
START BOOLEAN 0 Start reclosing sequence
STARTHS BOOLEAN 0 Start high-speed reclosing without synchrocheck
TRSOTF BOOLEAN 0 Continue to shots 2-5 at a trip from switch-on-to-fault
SKIPHS BOOLEAN 0 Skip high speed shot and continue with delayed shots
ZONESTEP BOOLEAN 0 Coordinate local AR with down stream devices
TR2P BOOLEAN 0 Two phase trip occurred
TR3P BOOLEAN 0 Three phase trip occurred
THOLHOLD BOOLEAN 0 Hold AR in wait state
CBREADY BOOLEAN 0 Circuit breaker is ready
CBCLOSED BOOLEAN 0 Circuit breaker status
PLCLOST BOOLEAN 0 Power line carrier or other form of permissive signal is lost
SYNC BOOLEAN 0 Synchrocheck conditions are fulfilled
WAIT BOOLEAN 0 Wait for master
RSTCOUNT BOOLEAN 0 Reset counters
MODEINT INTEGER 0 Integer input used to set reclosing mode (alternative to setting)

SMBRREC Output signals

SMBRREC Output signals
Name Type Description
BLOCKED BOOLEAN AR is blocked
SETON BOOLEAN AR is operative
READY BOOLEAN AR is ready for a new sequence
ACTIVE BOOLEAN Reclosing sequence in progress
SUCCL BOOLEAN Reclosing is successful
UNSUCCL BOOLEAN Reclosing is unsuccessful
INPROGR BOOLEAN Reclosing in progress, inactive during reclaim time
1PT1 BOOLEAN Single-phase reclosing is in progress for shot 1
2PT1 BOOLEAN Two-phase reclosing is in progress for shot 1
3PT1 BOOLEAN Three-phase reclosing is in progress for shot 1
3PT2 BOOLEAN Three-phase reclosing is in progress for shot 2
3PT3 BOOLEAN Three-phase reclosing is in progress for shot 3
3PT4 BOOLEAN Three-phase reclosing is in progress for shot 4
3PT5 BOOLEAN Three-phase reclosing is in progress for shot 5
PERMIT1P BOOLEAN Single-phase trip is permitted
PREP3P BOOLEAN Three-phase trip is prepared
CLOSECB BOOLEAN Close command for circuit breaker
WFMASTER BOOLEAN Wait signal to slave issued by master for sequential reclosing
COUNT1P INTEGER Number of single-phase reclosing shots
COUNT2P INTEGER Number of two-phase reclosing shots
COUNT3P1 INTEGER Number of three-phase shot 1 reclosings
COUNT3P2 INTEGER Number of three-phase shot 2 reclosings
COUNT3P3 INTEGER Number of three-phase shot 3 reclosings
COUNT3P4 INTEGER Number of three-phase shot 4 reclosings
COUNT3P5 INTEGER Number of three-phase shot 5 reclosings
COUNTAR INTEGER Number of total reclosing shots
MODE INTEGER Integer output for reclosing mode
ABORTED BOOLEAN General abort
SYNCFAIL BOOLEAN AR sequence is aborted by synchrocheck conditions not fulfilled
INHIBOUT BOOLEAN AR sequence is aborted via INHIBIT input

SMBRREC Group settings (basic)

SMBRREC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
ExternalCtrl Off
On
Off To be set On if AR is to be used with external control
ARMode 3 phase
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
1/2/3ph AR mode selection
t1 1Ph 0.000 – 120.000 s 0.001 1.000 Dead time for shot 1, single-phase reclosing
t1 3Ph 0.000 – 120.000 s 0.001 6.000 Dead time for shot 1, delayed three- phase reclosing with synchrocheck conditions
t1 3PhHS 0.000 – 120.000 s 0.001 0.400 Dead time for shot 1, high speed three-phase reclosing
tReclaim 0.00 – 6000.00 s 0.01 60.00 Reclaim time
tSync 0.00 – 6000.00 s 0.01 30.00 Maximum wait time for fulfilled synchrocheck conditions
tLongStartInh 0.000 – 60.000 s 0.001 0.200 Maximum allowed start pulse duration
tPulse 0.000 – 60.000 s 0.001 0.200 Circuit breaker closing pulse duration
tCBClosedMin 0.00 – 6000.00 s 0.01 5.00 Minimum time that circuit breaker must be closed before new sequence is allowed
tUnsucCl 0.00 – 6000.00 s 0.01 30.00 Maximun wait time for circuit breaker closing before indicating unsuccessful
Priority None
Low
High
None Priority selection between adjacent terminals
tWaitForMaster 0.00 – 6000.00 s 0.01 60.00 Maximum wait time for release from master
LongStartInhib Off
On
On To be set ON if AR is to be used with maximum allowed start pulse duration check

SMBRREC Group settings (advanced)

SMBRREC Group settings (advanced)
Name Values (Range) Unit Step Default Description
NoOfShots 1
2
3
4
5
1 Max number of reclosing shots
StartByCBOpen Off
On
Off To be set ON if AR is to be started by circuit breaker open position
CBReadyType CO
OCO
CO Circuit breaker ready signal type
t1 2Ph 0.000 – 120.000 s 0.001 1.000 Dead time for shot 1, two-phase reclosing
t2 3Ph 0.00 – 6000.00 s 0.01 30.00 Dead time for shot 2, three-phase reclosing
t3 3Ph 0.00 – 6000.00 s 0.01 30.00 Dead time for shot 3, three-phase reclosing
t4 3Ph 0.00 – 6000.00 s 0.01 30.00 Dead time for shot 4, three-phase reclosing
t5 3Ph 0.00 – 6000.00 s 0.01 30.00 Dead time for shot 5, three-phase reclosing
Extended t1 Off
On
Off Extend dead time at loss of permissive channel
tExtended t1 0.000 – 60.000 s 0.001 0.500 Extend three-phase dead time duration
tInhibit 0.000 – 60.000 s 0.001 5.000 Reset time for reclosing inhibit
CutPulse Off
On
Off Shorten circuit breaker closing pulse at a new start
Follow CB Off
On
Off Advance to next shot if circuit breaker has been closed during dead time
AutoContinue Off
On
Off Continue with next reclosing shot if circuit breaker did not close
tAutoContWait 0.000 – 60.000 s 0.001 2.000 Wait time after close command before proceeding to next shot
UnsucClByCBChk NoCBCheck
CB check
NoCBCheck Unsuccessful closing signal obtained by checking circuit breaker position
BlockByUnsucCl Off
On
Off Block AR at unsuccessful reclosing
ZoneSeqCoord Off
On
Off Coordination of down stream devices to local protection unit’s AR
tSuccessful 0.000 – 60.000 s 0.001 1.000 Delay time before indicating successful reclosing
tSlaveDeadTime 0.100 – 60.000 s 0.001 0.400 Wait time for the slave to close when WAIT input has reset

Status transition matrix

To →
From ↓
inactive ready in progress (dead time) reclaim time blocked
inactive   activate CBCLOSED and CBREADY     activate BLKON
ready deactivate CBCLOSED or CBREADY or
activate INHIBIT or RESET
  activate START or activate STARTHS   activate BLKON
in progress (dead time) activate INHIBIT or RESET     when CBCLOSED
issued
activate BLKON
reclaim time activate RESET or INHIBIT   activate START and the last shot has not been reached yet   activate BLKON
blocked deactivate CBCLOSED or CBREADY and activate BLKOFF activate BLKOFF and CBCLOSED and CBREADY      

Logics & highlights


Simplified logic for Operation Off/On and starting

Simplified logic for Operation Off/On and starting

Type of reclosing shots at different settings of “ARMode” or integer inputs to “MODEINT”

MODEINT (Integer) ARMode Type of fault 1st shot 2nd – 5th shot
1 3ph 1ph 3ph 3ph
2ph 3ph 3ph
3ph 3ph 3ph
2 1/2/3ph 1ph 1ph 3ph
2ph 2ph 3ph
3ph 3ph 3ph
3 1/2ph 1ph 1ph 3ph
2ph 2ph 3ph
3ph
4 1ph+1x2ph 1ph 1ph 3ph
2ph 2ph
3ph
5 1/2ph+1x3ph 1ph 1ph 3ph
2ph 2ph 3ph
3ph 3ph
6 1ph+1×2/3ph 1ph 1ph 3ph
2ph 2ph
3ph 3ph

Control of extended dead time

Control of extended dead time

Control of long start pulse duration

Control of long start pulse duration

Automatic proceeding of shots

Automatic proceeding of shots

BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in “ready” status

Output →
Input ↓
READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL
None of below inputs activated True False False False False False
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True False False
SYNC True False False False False False

BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in “in progress” status

Output →
Input ↓
READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL
None of below inputs activated False True False False False False
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True True False
No SYNC False False False False True True

Successful/Unsuccessful


Auto reclosing sequence

Auto reclosing sequence

Auto reclosing status reported by IEC 61850 in priority order

Data object AutoRecSt value Description for mapped signals Mapped output signals / Comments Description in IEC61850 Ed2
1 Ready READY Ready
2 In Progress INPROGR In Progress
3 Successful SUCCL Successful
4     Waiting for trip
5     Trip issued by protection
6     Fault disappeared
7 Wait to complete CLOSECB Wait to complete
8     Circuit breaker closed
9 Cycle unsuccessful UNSUCCL  
10      
-1 Aborted by synchrocheck fail SYNCFAIL  
11 Aborted ABORTED Aborted
-2 Set On, Not Ready SETON = 1, READY = 0,
ACTIVE = 0, SUCCL = 0,
UNSUCC = 0, INPROG = 0
 
-3 Set Off, Not Ready SETON = 0  
-99 Others Means that auto recloser is in transitional state, that should not be visible in steady state situation  

Thermal protection hold

Thermal protection hold

Master-Slave

Master-Slave

Transient single-phase fault, single-phase reclosing

Transient single-phase fault, single-phase reclosing

Permanent fault, three-phase trip, two-shot reclosing

Permanent fault, three-phase trip, two-shot reclosing

Permanent single-phase fault, single-phase trip, single-shot reclosing, ARMode=1/2/3ph

Permanent single-phase fault, single-phase trip, single-shot reclosing, ARMode=1/2/3ph

Permanent single-phase fault, single-phase trip, two-shot reclosing, ARMode=1ph + 1*2ph

Permanent single-phase fault, single-phase trip, two-shot reclosing, ARMode=1ph + 1*2ph