ABB / Synchrocheck, energizing check, and synchronizing (SESRSYN) _ Setting & highlights _ AB2072

Table of Contents

Overview

The Synchronizing function allows closing of asynchronous networks at the correct moment including the breaker closing time, which improves the network stability. “Synchrocheck, energizing check, and synchronizing (SESRSYN)” function checks that the voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead to ensure that closing can be done safely.

For more detailed information on “Synchrocheck, energizing check, and synchronizing (SESRSYN)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Synchrocheck, energizing check, and synchronizing SESRSYN sc/vc 25

Signals & Setting Parameters


SESRSYN function block

SESRSYN function block

SESRSYN Input signals

SESRSYN Input signals
Name Type Default Description
U3PBB1 GROUP SIGNAL Group signal for phase to earth voltage input L1, busbar 1
U3PBB2 GROUP SIGNAL Group signal for phase to earth voltage input L1, busbar 2
U3PLN1 GROUP SIGNAL Group signal for phase to earth voltage input L1, line 1
U3PLN2 GROUP SIGNAL Group signal for phase to earth voltage input L1, line 2
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus2
LN1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line1
LN1QCLD BOOLEAN 0 Close status for CB or disconnector connected to line1
LN2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line2
LN2QCLD BOOLEAN 0 Close status for CB or disconnector connected to line2
UB1OK BOOLEAN 0 Bus1 voltage transformer OK
UB1FF BOOLEAN 0 Bus1 voltage transformer fuse failure
UB2OK BOOLEAN 0 Bus2 voltage transformer OK
UB2FF BOOLEAN 0 Bus2 voltage transformer fuse failure
ULN1OK BOOLEAN 0 Line1 voltage transformer OK
ULN1FF BOOLEAN 0 Line1 voltage transformer fuse failure
ULN2OK BOOLEAN 0 Line2 voltage transformer OK
ULN2FF BOOLEAN 0 Line2 voltage transformer fuse failure
STARTSYN BOOLEAN 0 Start synchronizing
TSTSYNCH BOOLEAN 0 Set synchronizing in test mode
TSTSC BOOLEAN 0 Set synchro check in test mode
TSTENERG BOOLEAN 0 Set energizing check in test mode
AENMODE INTEGER 0 Input for setting of automatic energizing mode
MENMODE INTEGER 0 Input for setting of manual energizing mode

SESRSYN Output signals

SESRSYN Output signals
Name Type Description
SYNOK BOOLEAN Synchronizing OK output
AUTOSYOK BOOLEAN Auto synchro check OK
AUTOENOK BOOLEAN Automatic energizing check OK
MANSYOK BOOLEAN Manual synchro check OK
MANENOK BOOLEAN Manual energizing check OK
TSTSYNOK BOOLEAN Synchronizing OK test output
TSTAUTSY BOOLEAN Auto synchro check OK test output
TSTMANSY BOOLEAN Manual synchro check OK test output
TSTENOK BOOLEAN Energizing check OK test output
USELFAIL BOOLEAN Selected voltage transformer fuse failed
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
LN1SEL BOOLEAN Line1 selected
LN2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
UOKSYN BOOLEAN Voltage amplitudes for synchronizing above set limits
UDIFFSYN BOOLEAN Voltage difference out of limit for synchronizing
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDIFFOK BOOLEAN Frequency difference in band for synchronizing
FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
UOKSC BOOLEAN Voltage amplitudes above set limits
UDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual operation
PHDIFFM BOOLEAN Phase angle difference out of limit for Manual Operation
INADVCLS BOOLEAN Inadvertent circuit breaker closing
UDIFFME REAL Calculated difference of voltage in p.u of set voltage base value
FRDIFFME REAL Calculated difference of frequency
PHDIFFME REAL Calculated difference of phase angle
UBUS REAL Bus voltage
ULINE REAL Line voltage
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing

SESRSYN Group settings (basic)

SESRSYN Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
OperationSynch Off
On
Off Operation for synchronizing function Off/On
UHighBusSynch 50.0 – 120.0 %UBB 1.0 80.0 Voltage high limit bus for synchronizing in % of UBaseBus
UHighLineSynch 50.0 – 120.0 %UBL 1.0 80.0 Voltage high limit line for synchronizing in % of UBaseLine
UDiffSynch 0.02 – 0.50 pu 0.01 0.10 Voltage difference limit for synchronizing in p.u of set voltage base value
FreqDiffMin 0.003 – 0.250 Hz 0.001 0.010 Minimum frequency difference limit for synchronizing
FreqDiffMax 0.050 – 1.000 Hz 0.001 0.200 Maximum frequency difference limit for synchronizing
CloseAngleMax 15.0 – 30.0 Deg 1.0 15.0 Maximum closing angle between bus and line for synchronizing
FreqRateChange 0.000 – 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of change
tBreaker 0.000 – 1.000 s 0.001 0.080 Closing time of the breaker
tClosePulse 0.050 – 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 – 6000.00 s 0.01 600.00 Resets synch if no close has been made before set time
tMinSynch 0.000 – 60.000 s 0.001 2.000 Minimum time to accept synchronizing conditions
OperationSC Off
On
On Operation for synchronism check function Off/On
UHighBusSC 50.0 – 120.0 %UBB 1.0 80.0 Voltage high limit bus for synchrocheck in % of UBaseBus
UHighLineSC 50.0 – 120.0 %UBL 1.0 80.0 Voltage high limit line for synchrocheck in % of UBaseLine
UDiffSC 0.02 – 0.50 pu 0.01 0.15 Voltage difference limit for synchrocheck in p.u of set voltage base value
FreqDiffA 0.003 – 1.000 Hz 0.001 0.010 Frequency difference limit between bus and line Auto
FreqDiffM 0.003 – 1.000 Hz 0.001 0.010 Frequency difference limit between bus and line Manual
PhaseDiffA 5.0 – 90.0 Deg 1.0 25.0 Phase angle difference limit between bus and line Auto
PhaseDiffM 5.0 – 90.0 Deg 1.0 25.0 Phase angle difference limit between bus and line Manual
tSCA 0.000 – 60.000 s 0.001 0.100 Time delay output for synchrocheck Auto
tSCM 0.000 – 60.000 s 0.001 0.100 Time delay output for synchrocheck Manual
AutoEnerg Off
DLLB
DBLL
Both
DLLB Automatic energizing check mode
ManEnerg Off
DLLB
DBLL
Both
Both Manual energizing check mode
ManEnergDBDL Off
On
Off Manual dead bus, dead line energizing
UHighBusEnerg 50.0 – 120.0 %UBB 1.0 80.0 Voltage high limit bus for energizing check in % of UBaseBus
UHighLineEnerg 50.0 – 120.0 %UBL 1.0 80.0 Voltage high limit line for energizing check in % of UBaseLine
ULowBusEnerg 10.0 – 80.0 %UBB 1.0 40.0 Voltage low limit bus for energizing check in % of UBaseBus
ULowLineEnerg 10.0 – 80.0 %UBL 1.0 40.0 Voltage low limit line for energizing check in % of UBaseLine
UMaxEnerg 50.0 – 180.0 %UB 1.0 115.0 Maximum voltage for energizing in % of UBase, Line and/or Bus
tAutoEnerg 0.000 – 60.000 s 0.001 0.100 Time delay for automatic energizing check
tManEnerg 0.000 – 60.000 s 0.001 0.100 Time delay for manual energizing check

SESRSYN Non group settings (basic)

SESRSYN Non group settings (basic)
Name Values (Range) Unit Step Default Description
SelPhaseBus1 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1 Select phase for busbar1
GblBaseSelBus 1 – 12 1 1 Selection of one of the Global Base Value groups, Bus
GblBaseSelLine 1 – 12 1 1 Selection of one of the Global Base Value groups, Line
SelPhaseBus2 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1 Select phase for busbar2
SelPhaseLine1 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1 Select phase for line1
SelPhaseLine2 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
Phase L1 Select phase for line2
CBConfig No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
No voltage sel. Select CB configuration

SESRSYN Non group settings (advanced)

SESRSYN Non group settings (advanced)
Name Values (Range) Unit Step Default Description
PhaseShift -180 – 180 Deg 1 0 Additional phase angle for selected line voltage

SESRSYN Monitored data

SESRSYN Monitored data
Name Type Values (Range) Unit Description
UDIFFME REAL Calculated difference of voltage in p.u of set voltage base value
FRDIFFME REAL Hz Calculated difference of frequency
PHDIFFME REAL deg Calculated difference of phase angle
UBUS REAL kV Bus voltage
ULINE REAL kV Line voltage

Logics & highlights


Simplified logic diagram for the auto synchrocheck function

Simplified logic diagram for the auto synchrocheck function

Dependencies between tBreaker and SlipFrequency with different CloseAngleMax values

tBreaker [s] (max settable value)
with CloseAngleMax = 15 degrees [default value]
tBreaker [s] (max settable value)
with CloseAngleMax = 30 degrees [max value]
SlipFrequency [Hz]
(BusFrequency – LineFrequency)
0.040 0.080 1.000
0.050 0.100 0.800
0.080 0.160 0.500
0.200 0.400 0.200
0.400 0.810 0.100
  1.000 0.080
0.800   0.050
1.000   0.040

Simplified logic diagram for the synchronizing function

Simplified logic diagram for the synchronizing function

Manual energizing

Manual energizing

Automatic energizing

Automatic energizing

Open bays

Open bays

Logic diagram for the voltage selection function of a single circuit breaker with double busbars

Logic diagram for the voltage selection function of a single circuit breaker with double busbars

Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2 breaker arrangement

Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2 breaker arrangement

Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2 breaker arrangement

Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2 breaker arrangement