Overview

Delta supervision functions are used to quickly detect (sudden) changes in the power system. “Delta supervision of real input (DELSPVC)” function is a general delta function. It is used to detect the change measured qualities over a settable time period.

For more detailed information on “Delta supervision of real input (DELSPVC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Delta supervision of real input DELSPVC

Signals & Setting Parameters


DELSPVC function block

DELSPVC function block

DELSPVC Input signals

DELSPVC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT REAL 0 Real Input

DELSPVC Output signals

DELSPVC Output signals
Name Type Description
START BOOLEAN Start of function
STRISE BOOLEAN Rise signal when input has increased
STLOW BOOLEAN Low signal when input has decreased
DELREAL REAL Delta value of real input

DELSPVC Group settings (basic)

DELSPVC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
MinStVal 0.1 – 99999.9 0.1 1.0 Minimum start value for release of delta function
DeltaT 6 – 100 cycle 1 10 Number of old execution cycle for delta calculation
DelSt> 0.1 – 9999999.9 0.1 10.0 Delta start level for real input
tHold 0.10 – 60.00 s 0.01 0.10 Hold time for start signal

Logics & highlights


Simplified logic diagram for DELSPVC

Simplified logic diagram for DELSPVC