Overview

The “Fuse failure supervision (VDSPVC)” function is designed to detect fuse failures or faults in voltage measurement circuit, based on phase wise comparison of voltages of main and pilot fused circuits. VDSPVC blocking output can be configured to block functions that need to be blocked in case of faults in the voltage circuit.

For more detailed information on “Fuse failure supervision (VDSPVC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Fuse failure supervision VDSPVC

Signals & Setting Parameters


VDSPVC function block

VDSPVC function block

VDSPVC Input signals

VDSPVC Input signals
Name Type Default Description
U3P1 GROUP SIGNAL Main fuse voltage
U3P2 GROUP SIGNAL Pilot fuse voltage
BLOCK BOOLEAN 0 Block of function

VDSPVC Output signals

VDSPVC Output signals
Name Type Description
MAINFUF BOOLEAN Block of main fuse failure
PILOTFUF BOOLEAN Alarm of pilot fuse failure
U1L1FAIL BOOLEAN Fuse failure of Main fuse group phase L1
U1L2FAIL BOOLEAN Fuse failure of Main fuse group phase L2
U1L3FAIL BOOLEAN Fuse failure of Main fuse group phase L3
U2L1FAIL BOOLEAN Fuse failure of Pilot fuse group phase L1
U2L2FAIL BOOLEAN Fuse failure of Pilot fuse group phase L2
U2L3FAIL BOOLEAN Fuse failure of Pilot fuse group phase L3

VDSPVC Group settings (basic)

VDSPVC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Mode Off / On
Ud>MainBlock 10.0 – 80.0 %UB 0.1 20.0 Blocking picked up voltage level in % of UBase when main fuse fails
Ud>PilotAlarm 10.0 – 80.0 %UB 0.1 30.0 Alarm picked up voltage level in % of UBase when pilot fuse fails
SealIn Off
On
On Seal in functionality Off/On
USealIn 0.0 – 100.0 %UB 0.1 70.0 Operate level of seal-in voltage in % of UBase

VDSPVC Non group settings (basic)

VDSPVC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

VDSPVC Non group settings (advanced)

VDSPVC Non group settings (advanced)
Name Values (Range) Unit Step Default Description
ConTypeMain Ph-N
Ph-Ph
Ph-N Selection of connection type for main fuse group
ConTypePilot Ph-N
Ph-Ph
Ph-N Selection of connection type for pilot fuse group

VDSPVC Monitored data

VDSPVC Monitored data
Name Type Values (Range) Unit Description
UL1DIF_A REAL kV Differential voltage phase L1 for alarm functionality
UL2DIF_A REAL kV Differential voltage phase L2 for alarm functionality
UL3DIF_A REAL kV Differential voltage phase L3 for alarm functionality
UL1DIF_B REAL kV Differential voltage phase L1 for block functionality
UL2DIF_B REAL kV Differential voltage phase L2 for block functionality
UL3DIF_B REAL kV Differential voltage phase L3 for block functionality

Logics & highlights


Simplified logic diagram VDSPVC

Simplified logic diagram VDSPVC