Open or short circuited current transformer cores can cause unwanted operation of many protection functions such as differential, earth-fault current and negative-sequence current functions. “Current circuit supervision (CCSSPVC)” function compares the residual current from a three phase set of current transformer cores with the neutral point current on a separate input taken from another set of cores on the current transformer.

For more detailed information on “Current circuit supervision (CCSSPVC)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current circuit supervision CCSSPVC

Signals & Setting Parameters


CCSSPVC function block

CCSSPVC function block

CCSSPVC Input signals

CCSSPVC Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for three phase current input
IREF GROUP SIGNAL Residual reference current input
BLOCK BOOLEAN 0 Block of function

CCSSPVC Output signals

CCSSPVC Output signals
Name Type Description
FAIL BOOLEAN Detection of current circuit failure
ALARM BOOLEAN Alarm for current circuit failure

CCSSPVC Group settings (basic)

CCSSPVC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
IMinOp 10 – 200 %IB 1 20 Minimum operate current differential level in % of IBase

CCSSPVC Group settings (advanced)

CCSSPVC Group settings (advanced)
Name Values (Range) Unit Step Default Description
Ip>Block 20 – 500 %IB 1 150 Block of the function at high phase current, in % of IBase

CCSSPVC Non group settings (basic)

CCSSPVC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups