ABB / Underfrequency protection (SAPTUF) _ Setting & highlights _ AB2057

Table of Contents

Overview

“Underfrequency protection (SAPTUF)” function measures frequency with high accuracy, and is used for load shedding systems, remedial action schemes, gas turbine startup and so on. Separate definite time delays are provided for operate and restore.

For more detailed information on “Underfrequency protection (SAPTUF)” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Underfrequency protection SAPTUF f < 81

Signals & Setting Parameters


SAPTUF function block

SAPTUF function block

SAPTUF Input signals

SAPTUF Input signals
Name Type Default Description
U3P GROUP SIGNAL Three phase group signal for voltage inputs
BLOCK BOOLEAN 0 Block of function
BLKTRIP BOOLEAN 0 Blocking operate output
BLKREST BOOLEAN 0 Blocking restore output

SAPTUF Output signals

SAPTUF Output signals
Name Type Description
TRIP BOOLEAN General trip signal
START BOOLEAN General start signal
RESTORE BOOLEAN Restore signal for load restoring purposes
BLKDMAGN BOOLEAN Blocking indication due to low amplitude
FREQ REAL Measured frequency

SAPTUF Group settings (basic)

SAPTUF Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
StartFrequency 35.00 – 75.00 Hz 0.01 48.80 Frequency set value
IntBlockLevel 0.0 – 100.0 %UB 1.0 50.0 Internal blocking level in % of UBase
tDelay 0.000 – 60.000 s 0.001 0.200 Operate time delay
tReset 0.000 – 60.000 s 0.001 0.000 Time delay for reset
tRestore 0.000 – 60.000 s 0.001 0.000 Restore time delay
RestoreFreq 45.00 – 65.00 Hz 0.01 49.90 Restore frequency value
TimerMode Definite timer
Volt based timer
Definite timer Setting for choosing timer mode
UNom 50.0 – 150.0 %UB 1.0 100.0 Nominal voltage for voltage based timer in % of UBase
UMin 50.0 – 150.0 %UB 1.0 90.0 Lower operation limit for voltage based timer in % of UBase
Exponent 0.0 – 5.0 0.1 1.0 For calculation of the curve form for voltage based timer
tMax 0.010 – 60.000 s 0.001 1.000 Maximum time operation limit for voltage based timer
tMin 0.010 – 60.000 s 0.001 1.000 Minimum time operation limit for voltage based timer

SAPTUF Non group settings (basic)

SAPTUF Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Voltage dependent inverse time characteristics for underfrequency protection SAPTUF. The time delay to operate is plotted as a function of the measured voltage, for the Exponent = 0, 1, 2, 3, 4 respectively

Voltage dependent inverse time characteristics for underfrequency protection SAPTUF

Simplified logic diagram for SAPTUF

Simplified logic diagram for SAPTUF