Overview

The “Loss of voltage check (LOVPTUV )” function is suitable for use in networks with an automatic system restoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, if all three phase voltages fall below the set value for a time longer than the set time and the circuit breaker remains closed. The operation of LOVPTUV is supervised by the fuse failure supervision FUFSPVC.

For more detailed information on “Loss of voltage check (LOVPTUV )” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of voltage check LOVPTUV 27

Signals & Setting Parameters


LOVPTUV function block


LOVPTUV Input signals

LOVPTUV Input signals
Name Type Default Description
U3P GROUP SIGNAL Voltage connection
BLOCK BOOLEAN 0 Block the all outputs
CBOPEN BOOLEAN 0 Circuit breaker open
VTSU BOOLEAN 0 Block from voltage circuit supervision

LOVPTUV Output signals

LOVPTUV Output signals
Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal

LOVPTUV Group settings (basic)

LOVPTUV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off/On
UPE 1 – 100 %UB 1 70 Operate voltage in % of base voltage UBase
tTrip 0.000 – 60.000 s 0.001 7.000 Operate time delay

LOVPTUV Group settings (advanced)

LOVPTUV Group settings (advanced)
Name Values (Range) Unit Step Default Description
tPulse 0.050 – 60.000 s 0.001 0.150 Duration of TRIP pulse
tBlock 0.000 – 60.000 s 0.001 5.000 Time delay to block when all 3ph voltages are not low
tRestore 0.000 – 60.000 s 0.001 3.000 Time delay for enable the function after restoration

LOVPTUV Non group settings (basic)

LOVPTUV Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Simplified diagram of Loss of voltage check LOVPTUV